HomeMy WebLinkAboutE04.0SYMBOL CATALOG # REMARKS
LIGHTING FIXTURE SCHEDULE
MARK DESCRIPTION INPUT WATTAGE
A. ELECTRICAL CONTRACTOR TO COORDINATE SURFACE MOUNTED FIXTURE MOUNTING WITH ALL MECHANICAL DUCTWORK AND PLUMBING PIPING. WHERE INTERFERENCE'S OCCUR, ELECTRICAL CONTRACTOR TO STEM MOUNT
FIXTURES BELOW ALL DUCTWORK AND PIPING.
B. ELECTRICAL CONTRACTOR TO REFER TO DRAWING E1.0A AND ARCHITECTS REFLECTED CEILING PLAN FOR LOCATION OF ALL LIGHT FIXTURES.
C. NO DUCTWORK OR PIPING TO BE RUN ABOVE ELECTRICAL PANELS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL TRADES FOR EQUIPMENT LAYOUTS PRIOR TO ROUGH-IN OF ALL SYSTEMS
D. DEVICES IN THE FLOOR ARE NOT TO BE SCALED FROM THESE DRAWINGS. LOCATIONS SHALL BE VERIFIED WITH THE DICKS ON SITE REPRESENTATIVE AND OR DIMENSIONS TAKEN IN THE FIELD.
E. ELECTRICAL CONTRACTOR TO CONFIRM ALL REQUIREMENTS AND LOCATIONS OF ALL EXIT SIGNS, EMERGENCY LIGHTS AND FIRE ALARM DEVICES WITH LOCAL FIRE AUTHORITIES PRIOR TO ROUGH-IN.
F. ELECTRICAL CONTRACTOR TO CONFIRM LIGHT FIXTURE CATALOG NUMBERS WITH ALL LIGHT FIXTURES SPECIFIED ON PLANS FOR FIXTURE TRIMS, VOLTAGES, LAMPS ETC.
G. ELECTRICAL CONTRACTOR TO CONFIRM LOCATIONS OF ALL ELECTRICAL DEVICES WITH FIXTURING LOCATIONS PRIOR TO ROUGH-IN.
H. ELECTRICAL CONTRACTOR TO VERIFY ALL EQUIPMENT ELECTRICAL CHARACTERISTIC PRIOR TO ROUGH-IN.
I. ALL FLUORESCENT LIGHTING FIXTURES SHALL HAVE ELECTRONIC BALLASTS.
J. VENDOR FOR ALL LIGHTING FIXTURES IS VENDOR #18.
K. VERIFY COMPATIBILITY OF BALLAST WITH VENDOR #19 SECURITY SYSTEM.
L. VERIFY VOLTAGE PRIOR TO ORDERING FIXTURES.
M. CONDUIT ROUTING IS SHOWN ON DRAWINGS IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. UNLESS NOTED OTHERWISE, ALL CONDUIT SHALL BE CONCEALED. WHERE SHOWN EXPOSED, CONCEAL IN WALLS AT
MAXIMUM HEIGHT POSSIBLE FOR RUNS TO FLUSH DEVICE BOXES.
N. NO ELECTRICAL ROUGH-IN BOXES ARE PERMITTED ON WALL GRAPHICS.
O. CONTRACTORS BIDDING THIS PROJECT SHALL HAVE PRIOR EXPERIENCE WORKING IN THIS JURISDICTION AND MUST LIST ON BID FORM ANY LOCAL REQUIREMENTS THAT ARE NOT SHOWN ON THE DRAWINGS. SUBMISSION
OF A BID SHALL BE EVIDENCE THAT THE CONTRACTOR'S BID INCLUDES ALL JURISDICTIONAL REQUIREMENTS.
DATA CABLE LOCATION.
T THERMOSTAT - PROVIDED BY MECH. CONTRACTOR. WIRED AND MOUNTED BY E.C. MTD. 4'-0" UNLESS NOTED OTHERWISE.
REVERSE ACTING THERMOSTAT - PROVIDED BY MECH. CONTRACTOR. WIRED AND MOUNTED BY E.C. MTD. 4'-0" UNLESS NOTED OTHERWISE.
AFF DIMENSION ABOVE FINISHED FLOOR TO BOTTOM OF DEVICE
R
T
CODED DRAWING NOTE
(2) DUPLEX RECEPTACLE OUTLETS, WITH FLUSH SQUARE 2 GANG CAST IRON FLOOR BOX. PROVIDE BRASS COVER PLATE - HUBBEL OR EQUAL
EDWARD'S #340-4G5 - 24V AC 4" BELL WITH 120V AC / 24V AC TRANSFORMER. E.C. TO INSTALL AND WIRE AT BACKDOOR.
PULL BOX, FLUSH MOUNTED OR ABOVE CEILING, UNLESS OTHERWISE NOTED. SIZE AS REQUIRED.
SPECIAL PURPOSE RECEPTACLE AS REQUIRED. VERIFY EXACT LOCATION IN FIELD WITH DICK'S REPRESENTATIVE.
T
S
D
B
PB
M
F1
F1
TWO GANG WALL OUTLET BOX AND 20 AMP TWO DUPLEX RECEPTACLES.
"IG" INDICATES ISOLATED GROUND RECEPTACLE -
"VCR" INDICATES WALL MOUNTED VCR RECEPTACLE.
"WPG" INDICATES WEATHERPROOF GFI RECEPTACLE.
"TV" INDICATES CEILING MOUNTED TELEVISION RECEPTACLE.
"GFI" INDICATES GROUND FAULT INTERRUPTING RECEPTACLE.
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE. MOUNT 18" AFF., UNLESS NOTED. COLOR OF RECEPTACLE SHALL BE WHITE WITH WHITE COVER PLATE
TELEPHONE LINE WALL OUTLET BOX AND PLATE WITH MINIMUM 3/4" CONDUIT TO ABOVE ACCESSIBLE FINISHED CEILING. PROVIDE PULL CORD. ANALOG LINE.
IG
ORANGE IN COLOR.
EMERGENCY LIGHTING FIXTURE, INTEGRAL BATTERY
EXIT LIGHT FIXTURE, WALL MOUNTED
EXIT LIGHT FIXTURE
CEILING OUTLET BOX AND FLUORESCENT LIGHTING FIXTURE.
CEILING OUTLET BOX AND FLUORESCENT LIGHTING FIXTURE WITH "EM" - EMERGENCY BATTERY PACK REQUIRED.
INDUSTRIAL OR STRIP FLUORESCENT LIGHTING FIXTURE, INDICATES "EM" - EMERGENCY BATTERY PACK REQUIRED.
GH GLOBAL HUMIDITY SENSOR
S ONE HR. TIMER SWITCH FURNISHED BY MECH. CONTRACTOR, INSTALLED AND WIRED BY E.C.
SPECIALTY TYPE SIMPLEX RECEPTACLE, 15 AMPERE, MOUNT AS INDICATED, HUBBELL 5235
CONDUIT RUN IN OR BELOW FLOOR SLABS - MAINTAIN 2" MINIMUM CONCRETE COVER ABOVE CONDUIT
EQUIPMENT CONNECTION, WITH DESIGNATION FROM ELECTRIC EQUIPMENT AND CONTROL SCHEDULE
LOCATION OF ONE OR MORE EQUIPMENT CONTROL DEVICES AS SCHEDULED ON ELECTRIC EQUIPMENT AND CONTROL SCHEDULE. NUMBER REFERS TO EQUIPMENT CONTROLLED
NON FUSED DISCONNECT SWITCH, VOLTAGE TO MATCH EQUIPMENT SERVED.
FUSED DISCONNECT SWITCH, VOLTAGE RATING TO MATCH EQUIPMENT SERVED.
POWER CONNECTION TO LOCAL DOOR ALARM
J
J
H HUMIDITY SENSOR
GFI
WIRELESS CALL BOX
ANTENNA LOCATION
A
#
AP ACCESS POINTS IN CEILING.
Sm
OS
M1
PB
B
EDWARDS #692, 120V, PUSH BUTTON BY E.C. FOR FRONT OF STORE.
VIKING SR-1, 120V AC/13.8V AC 1.25A, WITH MODEL 25AE.
BY E.C. FOR RETAIL FLOOR AND OFFICE SUITE.
FLUSH SINGLE GANG CAST IRON FLOOR BOX FOR DATA / TELEPHONE CABLING. PROVIDE BRASS COVER PLATE - HUBBEL OR EQUAL
ALL WALL SWITCHES SHALL BE MOUNTED AT 46" ABOVE FINISHED FLOOR IN ACCORDANCE TO ADA REQUIREMENTS.
ULTRASONIC CEILING MOUNT OCCUPANCY SENSOR - WATTSTOPPER #W500A OR EQUAL (FOR USE WITH WATTSTOPPER #BZ-50 POWER PACK). BY VENDOR #18
INFRARED CEILING MOUNT OCCUPANCY SENSOR - WATTSTOPPER #HB3500/HB-L1M OR EQUAL OMNI-DIRECTIONAL. BY VENDOR #18
M218 INFRARED CEILING MOUNT OCCUPANCY SENSOR - WATTSTOPPER #HB3500/HB-L3 OR EQUAL BI-DIRECTIONAL. BY VENDOR #
120/277V AUTOMATIC WALL SWITCH WITH OCCUPANCY SENSING AND TIMED SHUT OFF. WATT STOPPER MODEL #PW-101W. BY VENDOR #18
EDWARD'S #600 - 48V BRASS WEATHERPROOF PUSH BUTTON E.C. TO INSTALL AND WIRE AT BACKDOOR.
NF
DWW HORIZONTAL TRACK WALL WASH LED AMERLUX #DWW-H-28-WT-XX-120-WW-35-LE/TE
28W
THC COMBINED TEMPERATURE / RELATIVE HUMIDITY / CARBON DIOXIDE SENSOR
TEMPERATURE SENSOR
120 VOLT BRANCH CIRCUITS UP TO 10 AMPS
TOTAL WIRE LENGTH (FEET) WIRE SIZE (AWG)
#12
101' #10
151' #8
241' #6
277 VOLT BRANCH CIRCUITS UP TO 16 AMPS
RUN DISTANCE IN FEET WIRE SIZE AWG
#12
#10
226' #8
346' #6
VOLTAGE DROP SCHEDULE
MINIMUM LIGHTING CIRCUIT WIRING IS #12 AWG. CONTRACTOR SHALL INCREASE WIRE SIZE BASED ON SCHEDULE ABOVE.
140'
225'
345'
546'
100'
150'
240'
380'
120 VOLT BRANCH CIRCUITS UP TO 14 AMPS
TOTAL WIRE LENGTH (FEET) WIRE SIZE (AWG)
#12
76' #10
116' #8
186' #6
75'
115'
185'
290'
A. ON 20 AMP, 1 POLE CIRCUITS, HOMERUNS SHALL BE 2 #12 AWG + #12 GND IN 3/4" CONDUIT MINIMUM (INCLUDE
ADDITIONAL ISOLATED GROUND CONDUCTOR SIZED TO MATCH GROUND CONDUCTOR IS IDENTIFIED AS ISOLATED
GROUND CIRCUIT). INCREASE WIRE SIZE AS REQUIRED PER VOLTAGE DROP TABLE ON THIS DRAWING.
a. VOLTAGE DROPS ARE BASED ON FEEDER CONDUCTORS SIZED FOR A MAXIMUM VOLTAGE DROP OF 2% AT DESIGN
LOAD. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF 3% AT DESIGN LOAD.
B. ALL CIRCUITS SHALL HAVE INDIVIDUAL NEUTRAL CONDUCTORS CONTINUOUS FROM PANEL. SHARED NEUTRALS
ARE NOT PERMITTED.
PC INDOOR PHOTOCELL FURNISHED BY VENDOR #18 AND INSTALLED AND WIRED BY E.C.
CORD REEL WITH HUBBELL 5969 VBLK CONNECTOR, WHITE WITH WHITE CORD. SIMILAR TO HUBBELL #HBLC25123C (25' 12/3 SJT CABLE, RATED 20 AMPS) PROVIDED BY VENDOR #18
GFLW LED HEAD WITH DRIVER CTL183H35D-P-DSG (WHITE)
47W
GF1 LED HEAD WITH DRIVER CTL8253VM35D-P-DSG (WHITE)
36W
A 2'x2' LED FLP22-D38W35 38W
LG1 4' LED STRIP C48LV52W6700LVDMV40K
LG1EM 4' LED STRIP WITH EMERGENCY DRIVER C48LV52W6700LVDMV40K-EM PROVIDE EMERGENCY BATTERY DRIVER
52W
52W
S6 DECORATIVE PENDANT (BRONZE IN COLOR) CONTECH LIGHTING # P161-DSG2020 15W 8'-6" A.F.F., LAMP PROVIDED WITH FIXTURE
S10 3" LED PENDANT WITH CANOPY STYLE DRIVER SISTEMALUX LIGHTING #1770CPHO-SPS014614 19.5W 8'-6" A.F.F., LAMP PROVIDED WITH FIXTURE
S5 ADJUSTABLE TRACK MOUNTED LED CONTECH # CTL-8063-V-M-4C-D-P
10'-6" A.F.F.
20W
S15 PENDANT LED CONTECH LIGHTING # CYL8-3-30K-MVD-FC-N-CLR-B20FT-DSG 20W
S16 PENDANT LED CONTECH LIGHTING # CYL8-5-35K-MVD-FC-N-CLR-B 37W
11'-0" A.F.F.
12'-0" A.F.F.
{NOTE:
SPACE ABOVE CEILINGS IS UTILIZED AS A RETURN AIR PLENUM.
ALL MATERIALS ABOVE CEILINGS SHALL BE PLENUM RATED.}
R5 EM UNIT - LED PGW 3W FITTING ROOMS - MOUNT BELOW TRELLIS @ 9'-0" AFF TO CENTER OF FIXTURE
FR DECORATIVE PENDANT WITH LED LAMPS RLM60325-N (10' CORD) 54W ((3) 18W LAMPS) E.C. TO MOUNT BOTTOM OF FIXTURE 8'-2" A.F.F. E.C. TO PAINT MOUNTING UNISTRUT WHITE.
Y2A MURAL LED LIGHT WITH ARM BRACKET CTLI82SL25MVD-GRN-DSG 41W JUNCTION BOX FOR FIXTURE TO BE SECURELY MOUNTED TO RECESSED BLOCKING
LGEM 8' LED STRIP WITH EMERGENCY DRIVER LSA-8-8000-35K-HTA-U80-UNI-EM7
LG 8' LED STRIP LSA-8-8000-35K-HTA-U80-UNI
PROVIDE EMERGENCY BATTERY DRIVER
66W
66W
WIRE GUARD INCLUDED WITH FIXTURE
AEM 2'x2' LED WITH EMERGENCY DRIVER FLP22-D38W35EM 38W PROVIDE EMERGENCY BATTERY DRIVER
S2 SGL FACE EXIT WITH EMERGENCY DRIVER APX7R MOUNTED AT 9'-6" AFF.
1W
RR RESTROOM LED DOWNLIGHT 20SMPR9DIM/930 20W
Mar 26, 2021 - 17:37:27 DWG Name: D:\Jobs\MCG\Dick's Sporting Goods\IN Carmel\Remodel\01-Bid Permit\12810B_E4.0.dwg Updated By: rvan
E4.0
MISCELLANEOUS
SCHEDULES
PJN
CONTRACTOR MUST VERIFY
DIMENSIONS ALL CLEARANCES IN AND FIELD
Drawn By:
Project No.:
Date Issue
SPORTING GOODS
Design and construction documents as
instruments of service are given in
confidence and remain the property of
MCG Architects. The use of this design
and these construction documents for
purposes other than the specific project
named herein is strictly prohibited
without expressed written consent of
MCG Architects, Incorporated.
STORE # 183
21042.10
C MCG ARCHITECTS 2021
ALL RIGHTS RESERVED
**With exception of the National Account Vendors that DSG is purchasing directly from as noted on the vendor
matrix, all work, materials, and systems shown in these plans and specifications is the sole responsibility of the
General Contractor to purchase and install complete as shown and referenced. The General Contractor is required
to coordinate, schedule and supervise all National Account Vendors as well as their subcontractors. The Tenant
(Dick's Sporting Goods) has no scope of work and/or responsibility shown in these plans and/or specifications.**
25001 Emery Road, Suite #200
Warrensville Heights, Ohio 44128
Phone: 216-292-4696
Fax: 216-292-5874
Email: mail@mchenryassociates.com
Issued for
Bid-Permit
03-26-21
T F
\pxql;216.520.1551
\pxql;216.520.1567
03-26-21
SM
CLAY TERRACE
14350 CLAY TERRACE BLVD.
CARMEL, IN 46032
05/11/21