HomeMy WebLinkAboutE002 - Electrical Specifications26 05 00 -BASIC MATERIALS AND METHODS 1. UTILITIES: 1.1. CONTRACTOR TO COORDINATE POWER, TELEPHONE, AND TELEVISION (CABLE) SERVICE REQUIREMENTS WITH LOCAL UTILITIES PRIOR TO SUBMIITING BID PROPOSAL. 2. SHOP DRAWINGS: 2.1. SUBMIT SHOP DRAWINGS TO INCLUDE MANUFACTURER CURRENT SPECIFICATION AND LITERATURE, HIGHLIGHTED WITH OPTIONS PROVIDED AS PART OF THIS PROJECT. PROVIDED SHOP DRAWINGS FOR WIRING DEVICES, STARTERS, CIRCUIT BREAKERS, LIGHTS, LAMPS, ELECTRONIC BALLAST, PANEL BOARDS, AUTOMATIC TRANSFER SWITCH, AND FIRE ALARM. 3. ALL ELECTRICAL CONNECTORS, LUGS, BREAKERS, EQUIPMENT, ETC., SHALL BE RATED A MINIMUM OF 75 DEGREES C. 26 05 19 -LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 1. 600 VOLTS, 98% CONDUCTIVITY, STRANDED COPPER, CLASS B, THHN/THWN INSULATION EXCEPT FOR WIRING #10 AWG AND SMALLER SHALL BE SOLID COPPER. NO ALUMINUM WIRING WILL BE ALLOWED. 26 05 33 -RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 2. ALL INDOOR CONDUIT SHALL BE ELECTRICAL METALLIC TUBING (EMT) AND SHALL BE A MINIMUM 3/4" UNLESS OTHERWISE NOTED. UTILIZE COMPRESSION TYPE FITTINGS. USE FOR EQUIPMENT CONNECTION, FEEDERS AND BRANCH CIRCUIT WIRING. ALL CONDUIT INSTALLED ABOVE GRADE OUTSIDE OF THE BUILDING SHALL BE RIGID STEEL. ALL CONDUIT INSTALLED UNDERGROUND SHALL BE SCHEDULE 40 PVC UNLESS OTHERWISE NOTED. NO PVC CONDUIT SHALL BE USED ABOVE THE FLOOR SLAB OR EXPOSED OUTSIDE THE BUILDING. 3. 26 27 26 -WIRING DEVICES 1. RECEPTACLES: NEMA 5-20R, DUPLEX, 20 AMP, 125 VAC, GROUNDING TYPE, HOSPITAL GRADE, COLOR TO MATCH EXISTING WITH FULL METAL STRAP. HUBBELL HBL8300GY OR EQUAL. MOUNT AT 18" A.F.F. UNLESS NOTED OTHERWISE. 2. DIMMER: FLUORESCENT DIMMER SHALL BE 1500 WATTS, THIN PROFILE, SIMILAR TO LUTRON NOVA-T SERIES. 3. GFCI TYPE RECEPTACLE: NEMA 5-20R GFI, DUPLEX, 20 AMP, 125 VAC, GROUNDING TYPE, HOSPITAL GRADE, 5 MILLIAMP SENSITIVITY TRIP TYPE. HUBBELL GFR8300SGGY OR EQUAL. 4. TOGGLE SWITCHES: 20 AMP, 120 VAC RATED, QUIET TYPE, SPECIFICATION GRADE SPST, 3-WAY, OR 4-WAY TYPE AS INDICATED ON THE DRAWINGS. HUBBELL 1221-I OR EQUAL. 5. COVER PLATES: INDOOR PLATES SHALL BE NYLONE TYPE TO MATCH THE EXISTING. WEATHERPROOF PLATES SHALL BE CAST ALUMINUM GASKETED, RAINTIGHT WHILE-IN-USE TYPE. 26 05 26 -GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 1. GROUNDING AND BONDING SYSTEM SHALL MEET REQUIREMENTS OF NEC ARTICLE 250H. BOND WATER PIPE, BUILDING STRUCTURE, AND GROUND ROD WITH BARE COPPER WIRE. GROUND ROD TO BE COPPER CLAD 3/ 4"D X 10'L. CONNECT BARE COPPER CABLE TO MAIN SERVICE DISTRIBUTION BUS. 26 24 16 -PANELBOARDS 1. DISTRIBUTION: 1.1. MAIN BUS, NEUTRAL AND GROUND BAR SHALL BE 98% COPPER, NEMA-1 CABINET, GRAY PAINT, NAME PLATE, U.L. LISTED. LISTED TO USE AS SERVICE ENTRANCE. AIC RATING TO BE 42,000 AMPS UNLESS OTHERWISE INDICATED. PANEL TO BE SIMILAR TO SQUARE "D" I- LINE, G.E. SPECTRA, CUTLER HAMMER PRL4, SIEMENS S5. 26 09 23 -LIGHTING CONTROL DEVICES 1. WALL MOUNTED SINGLE-CIRCUIT OCCUPANCY SENSORS: DUAL TECHNOLOGY TYPE. WATTSTOPEER/LEGRAND PW-203-I OR EQUIVALENT AS MANUFACTURED BY HUBBELL, SENSOR SWITCH, COOPER CONTROLS, OR PHILIPS. 2. 26 22 00 -LOW-VOLTAGE DRY TYPE TRANSFORMERS 1. TRANSFORMER HOUSING SHALL BE ENCLOSED IN VENTILATED, DRIP-PROOF CODE GAUGE STEEL HOUSING, REMOVABLE ACCESS PANELS, RODENT BARRIERS ON OPENING, PHOSPHATIZED, AND FINISH WITH CORROSION INHIBITING UNDERCOAT AND ANSI GRAY FINISH. 2. CORE AND COIL ASSEMBLY SHALL BE CONSTRUCTED OF CONTINUOUS COPPER WINDING, HIGH GRADE, NON-AGING, GRAIN ORIENTED SILICON STEEL CORE, COMPLETELY ISOLATED FROM THE ENCLOSURE USING VIBRATION ABSORBING MOUNT, FLEXIBLE GROUNDING STRAP. 3. TWO 2-1/ 2% FCAN AND FOUR 2-1/ 2% FCBN TAPS. 4. INSULATION SHALL BE 600 VAC, DRY TYPE, AIR COOLED, 150° C. RISE, 220° C INSULATION CLASS. 5. NOISE LEVEL SHALL BE LESS THAN ANSI STANDARD. 6. DRY TYPE TRANSFORMER SHALL BE SIMILAR TO SQUARE "D" WATCHDOG SERIES, GE QL SERIES, CUTLER-HAMMER D33/DT3 SERIES, AND SIEMENS EQUIVALENT. 26 51 00 -LIGHTING FIXTURES AND ACCESSORIES 1. LIGHTING: 1.1. FIXTURES AND ACCESSORIES SHALL BE U.L. LISTED AND LABELED. 1.2. FIXTURES SHALL BE CODE GAUGE STEEL WITH 85% REFLECTANCE BAKED ENAMEL FINISH, 660 WATTS RATED LAMP HOLDER, BALLAST SHALL BE HIGH FREQUENCY 10% THD ELECTRONIC TYPE, LENSES SHALL BE 100% VIRGIN ACRYLIC MATERIALS KSH-12, CLEAR. 1.3. OUTDOOR FIXTURE SHALL INCLUDE WEATHERPROOF HOUSING, WET/DAMP LABEL, AND -20°F COLD TEMPERATURE BALLAST/DRIVER 1.4. LED FIXTURES: 1.5.1. FLUORESCENT BALLAST SHALL BE HIGH FREQUENCY TYPE, OPERATING LAMPS WITH LESS THAN 2% LAMP FLICKER. POWER FACTOR TO BE GREATER THAN 95% AND TOTAL HARMONIC DISTORTION LESS THAN 10%. BALLASTS TO BE NON-PCB, COMPLY WITH EMI AND RFI LIMITS SET BY THE FCC PART 18, "A" SOUND RATING, AND MEET ANSI AND U.L. STANDARDS, CLASS, TYPE 1 OUTDOOR. BALLAST SHALL CARRY MINIMUM 5 YEAR WARRANTY. BALLASTS TO BE MULTIVOLT TO OPERATE ON 120 VAC OR 277 VAC. 1.6.1. HID FIXTURES SHALL BE LISTED AND LABELED TO COMPLY WITH THERMAL PROTECTION, 600 VAC RATED LAMP HOLDER. 2. LAMPS/LIGHT SOURCE: 2.2. FLUORESCENT LAMPS SHALL BE LOW-MERCURY T8, TCLP-COMPLIANT, 3500°K WITH MINIMUM CRI OF 84 UNLESS OTHERWISE INDICATED. 2.3. COMPACT FLUORESCENT LAMPS SHALL BE LOW-MERCURY QUAD OR TRIPLE TUBE AS INDICATED, TCLP-COMPLIANT, 3500°K WITH MINIMUM CRI OF 84 UNLESS OTHERWISE INDICATED. 2.4. INTERIOR HID LAMPS SHALL BE PHOSPHOR COATED, 4000°K WITH SELF-EXTINGUISHING SAFETY ARC TUBE AND A MINIMUM CRI OF 70 AND UNLESS OTHERWISE INDICATED. MAIN BUS, NEUTRAL BUS, AND GROUND BAR SHALL BE 98% COPPER, NEMA-1 CABINET, GRAY PAINT, NAME PLATE, BOLT-ON BREAKERS, DOOR AND TRIM WITH DOOR-IN-DOOR CONSTRUCTION, U.L. LISTED. AIC RATING TO BE 22,000 AMPS UNLESS OTHERWISE INDICATED. PANEL DIRECTORY. PANEL TO BE SIMILAR TO CUTLER-HAMMER PRL-1, SQUARE "D" NQ, G.E. AQ, SIEMENS S1. 2. 2.1. BRANCH PANEL: 2. ALL PANELBOARD FEEDERS AND BRANCH CIRCUIT WIRING SHALL BE INSTALLED IN CONDUIT. 3. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS CONDUCTORS PER CIRCUIT. SHARED NEUTRAL CONDUCTORS WILL NOT BE ALLOWED. 2. PROVIDE SEPARATE INSULATED GREEN GROUND WIRE WITH EACH BRANCH CIRCUIT AS THE EQUIPMENT GROUNDING MEANS FOR ALL ELECTRICAL DEVICES AND EQUIPMENT. PROVIDE NAME PLATE LABEL (IDENTIFICATION) ON SERVICE EQUIPMENT, SWITCHBOARDS, PANELBOARDS, DISCONNECT SWITCHES AND SIMILAR EQUIPMENT TO INCLUDE ENGRAVED PLASTIC LABEL IDENTIFYING THE EQUIPMENT AND WHERE IT IS FED FROM. ALL BRANCH DEVICES IN SWITCHBOARDS SHALL HAVE AN ENGRAVED PLASTIC LABEL. ALL PANELBOARDS SHALL INCLUDE A TYPEWRITTEN DIRECTORY. PROVIDE LABEL TO IDENTIFY CIRCUIT NUMBERS AT JUNCTION BOXES AND DEVICE BOXES USING BLACK MARKER FOR NORMAL CIRCUITS AND RED MARKER FOR EMERGENCY CIRCUITS. 26 05 53 -IDENTIFICATION FOR ELECTRICAL SYSTEMS 1. 2. ALL SWITCHES AND RECEPTACLES SHALL HAVE CIRCUIT NUMBERS TYPEWRITTEN ON THE FRONT FACE OF THEIR COVERPLATES USING SELF-ADHESIVE, THERMAL PRINTED LABELS. CLEAN FACEPLATES BEFORE APPLYING LABELS. 3. WHERE MULTIPLE SWITCHES ARE GANGED TOGETHER THE SWITCHES SHALL BE IDENTIFIED AS TO WHAT EACH CONTROLS.4. ALL CONDUIT INSTALLED ABOVE GRADE OUTSIDE OF THE BUILDING SHALL BE RIGID STEEL. 26 28 13 -FUSES 1. FUSES SHALL HAVE 200,000 RMS SYMMETRICAL AMPERES INTERRUPTING CAPACITY AT 600 VAC OR LESS, CURRENT LIMITING TYPE, TIME DELAY CHARACTERISTICS, REJECTION FEATURE. CEILING MOUNTED OCCUPANCY SENSORS: DUAL TECHNOLOGY TYPE. 360 DEGREE COVERAGE. HUBBELL OMNIDT TYPE OR EQUIVALENT AS MANUFACTURED BY WATTSTOPPER, SENSOR SWITCH, COOPER CONTROLS, OR PHILIPS. 26 01 00 -GENERAL PROVISIONS 1. WORK CONSISTS OF FURNISHING LABOR, MATERIALS, EQUIPMENT, AND SERVICES REQUIRED FOR THE COMPLETE INSTALLATION OF ELECTRICAL WORK SHOWN IN THE CONTRACT DOCUMENTS AND SPECIFIED IN DIVISIONS 26, 27 AND 28 GENERAL ELECTRICAL SPECIFICATIONS -APPLY TO ALL ELECTRICAL SHEETS 2. INCLUDE ALL PARTS AND LABOR, WHICH ARE INCIDENTAL AND NECESSARY, FOR A COMPLETE OPERABLE INSTALLATION EVEN THOUGH NOT SPECIFICALLY MENTIONED IN THE CONTRACT DOCUMENTS. SUCH ITEMS INCLUDE NUTS, BOLTS, ANCHORS, BRACKETS, SLEEVES, OFFSETS IN CONDUIT, FITTINGS, RELAYS, ETC. 4. OBTAIN ALL TEMPORARY AND PERMANENT PERMITS AND LICENSES REQUIRED IN CONNECTION WITH THE WORK OF DIVISIONS 26, 27 AND 28. PAY ALL FEES AND EXPENSES REQUIRED FOR SUCH PERMITS AND LICENSES. 3. ARRANGE WITH THE OWNER OR LANDLORD TO PROVIDE TEMPORARY AND PERMANENT UTILITY SERVICES AS REQUIRED AND COORDINATE THEIR INSTALLATION WITH CONSTRUCTION PROGRESS OF THIS PROJECT. PAY ALL FEES AND COSTS CHARGED BY UTILITY COMPANIES FOR UTILITY SERVICES. 5. REQUEST INSPECTIONS AS REQUIRED BY REGULATING AGENCIES AND/OR REGULATORS. PAY ALL CHARGES FOR INSPECTIONS BY REGULATING AGENCIES OF INSTALLATIONS OF PLANS AND SPECIFICATIONS 6. INCLUDE STATE AND LOCAL SALES TAXES IN THE BID. KEEP ACCURATE RECORDS OF THESE TAXES AND FURNISH SUCH RECORDS TO THE OWNER, TENANT, OR LANDLORD UPON REQUEST 7. MEET OR EXCEED ALL CURRENT APPLICABLE CODES, ORDINANCES, AND REGULATIONS FOR ALL INSTALLATIONS. PROMPTLY NOTIFY THE ENGINEER, IN WRITING, IF THE CONTRACT DOCUMENTS APPEAR TO CONFLICT WITH GOVERNING CODES AND REGULATIONS. CONTRACTOR ASSUMES ALL RESPONSIBILITY AND COSTS FOR CORRECTING NON-COMPLYING WORK INSTALLED WITHOUT NOTIFYING THE ENGINEER 8. HIGHER QUALITY OF WORKMANSHIP AND MATERIALS INDICATED IN THE CONTRACT DOCUMENTS TAKES PRECEDENCE OVER THAT ALLOWED IN REFERENCED CODES AND STANDARDS. 9. THE TERMS DEFINED BELOW APPLY TO ALL WORK INCLUDED IN DIVISIONS 26, 27 AND 28. 9.1. THE TERM 'WORK' MEANS THE CONSTRUCTION AND SERVICES REQUIRED BY THE CONTRACT DOCUMENTS AND INCLUDES ALL OTHER LABOR, MATERIALS, EQUIPMENT, AND SERVICES PROVIDED OR TO BE PROVIDED BY THE CONTRACTOR TO FULFILL THE CONTRACTOR'S CONTRACTUAL OBLIGATIONS. 9.2. FURNISH -TO OBTAIN IN NEW CONDITION READY FOR INSTALLATION INTO THE WORK. 9.3. INSTALL -TO STORE, SET IN PLACE, CONNECT AND PLACE INTO OPERATION IN THE THE WORK. 9.4. PROVIDE -TO FURNISH AND INSTALL. 9.5. CONNECT -TO BRING SERVICE TO THE EQUIPMENT AND MAKE FINAL ATTACHMENT INCLUDING NECESSARY SWITCHES, OUTLETS, BOXES, TERMINATIONS, ETC. 9.6. CONDUIT -INCLUDES IN ADDITION TO CONDUIT, ALL FITTINGS, PULL BOXES, HANGERS, AND OTHER SUPPORTS AND ACCESSORIES RELATED TO SUCH CONDUIT. 9.7. CONCEALED -HIDDEN FROM SIGHT IN CHASES, FURRED SPACES, SHAFTS, HUNG CEILINGS, EMBEDDED IN CONSTRUCTION, IN CRAWL SPACES, OR BURIED. 9.8. EXPOSED -NOT INSTALLED UNDERGROUND NOR CONCEALED AS DEFINED ABOVE. 4. WORKING SPACE AROUND ELECTRICAL EQUIPMENT TO BE MARKED OFF IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODES, FIRE CODES, AND OTHER APPLICABLE CODES. 1. ENCASE ALL CONDUCTORS IN A CONTINUOUS RACEWAY SYSTEM. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED BY THE NATIONAL ELECTRICAL CODE (NEC). SIZE ALL RACEWAYS PER THE NEC WITH OVERSIZE CONDUITS AS INDICATED. PROVIDE A MINIMUM 3/4-INCH CONDUIT. 4. ALL CONDUIT INSTALLED UNDERGROUND SHALL BE SCHEDULE 40 PVC UNLESS OTHERWISE NOTED. PROVIDE COATED RIGID STEEL ELBOWS FOR ALL UNDERGROUND ELBOWS USED WITH PVC RACEWAY. NO PVC CONDUIT SHALL BE USED ABOVE THE FLOOR SLAB OR EXPOSED OUTSIDE THE BUILDING. 5. PROVIDE RIGID STEEL OR CONCRETE-ENCASED PVC CONDUIT FOR SERVICE ENTRANCE CONDUCTORS. 6. PROVIDE FLEXIBLE METAL CONDUIT FOR CONNECTIONS TO TRANSFORMERS, MOTORS, AND OTHER EQUIPMENT THAT VIBRATE. PROVIDE LIQUIDTIGHT CONDUIT FOR ALL CONNECTIONS IN DAMP OR WET LOCATIONS. PROVIDE GROUNDING TYPE FITTINGS AND GROUNDING CONDUCTOR INSIDE ALL FLEXIBLE CONDUITS. ADJUST CONDUIT SIZE AS REQUIRED. 7. PROVIDE EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING EXPANSION JOINTS. 8. RUN ALL EXPOSED CONDUIT IN A NEAT, WORKMANLIKE MANNER PARALLEL TO THE BUILDING LINES, TIGHT TO THE WALL AND CEILING SURFACES, AND FIRMLY SUPPORTED WITH CONDUIT CLAMPS OR HANGERS. PROVIDE TWO-HOLE MOUNTING STRAPS, MINIMUM OF THREE FEET ON CENTER FOR ALL SURFACE CONDUIT MOUNTED ON WALLS LESS THAN SIX FEET ABOVE FINISHED FLOOR. PLACE CONDUITS AT LEAST 8 INCHES AWAY FROM ALL HOT PIPING AND SURFACES INCLUDING DOMESTIC HOT WATER LINES. 9. PROVIDE GALVANIZED CODE GAUGE STEEL JUNCTION AND PULL BOXES WITH SCREW-ON COVERS OF TYPE, SHAPE, AND SIZE REQUIRED TO SUIT EACH INSTALLATION. PROVIDE GASKETING IN DAMP AND DUSTY LOCATIONS. PROVIDE CAST BOXES IN WEATHERPROOF, VAPORTIGHT, AND EXPOLOSION-PROOF ENVIRONMENTS. 10. BOXES TO BE GLAVANIZED STEEL, MINIMUM OF 4" SQUARE WITH ONE-GANG OR TWO-GANG PLASTER RING AS REQUIRED. MINIMUM DEPTH OF 3-1/ 2" DEEP BOXES WHERE INSTALLED IN MASONRY WALLS; MINIMUM DEPTH OF 2-1 /8" ALL OTHER LOCATIONS. 11. MOUNT OUTLET BOXES IN EXPOSED MASONRY WALLS WITH THE BOTTOM OF THE BOX ON THE TOP OF THE MORTAR JOINT AND THE CENTER-LINE OF THE BOX EITHER ON THE MORTAR JOINT OR ON THE CENTER-LINE OF THE MASONRY UNIT. PLUMB AND ACCURATELY ALIGN ALL WALL OUTLETS IN ROWS. MOUNT CEILING BOXES SYMMETRICALLY WITH WALLS, BEAMS, AND/OR TILES. MOUNTING HEIGHTS INDICATED ON THE DRAWINGS ARE FROM THE CENTER OF THE OUTLET BOX TO THE FINISHED FLOOR DIRECTLY BELOW THE OUTLET UNLESS NOTED OTHERWISE. EXTERIOR HEIGHTS ARE FROM INSIDE ADJACENT DOOR, OR IF NO DOOR, FROM THE FIRST FLOOR ABOVE GRADE, UNLESS NOTED OTHERWISE. 12. COORDINATE THE LOCATIONS OF ALL OUTLETS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS BEFORE INSTALLATION. COORDINATE ALL DOOR SWINGS IN THE FIELD BEFORE LOCATING SWITCHES. 10. THE DRAWINGS AND SPECIFICATIONS CONSTITUTE THE CONTRACT DOCUMENTS. ANY ITEM NOTED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS IS INCLUDED IN THE CONTRACT DOCUMENTS. 11. ALL ELECTRICAL DETAILS AND DRAWINGS ARE DIAGRAMMATIC, UNLESS SPECIFICALLY NOTED OTHERWISE. FIELD VERIFY ALL DIMENSIONS AND NOTIFY THE ENGINEER OF ANY CONFLICTS OR DISCREPANCIES, IN WRITING, PRIOR TO INSTALLATION. 12. INITIATE, MAINTAIN, AND SUPERVISE ALL SAFETY PRECAUTIONS REQUIRED WITH THIS WORK IN ACCORDANCE WITH THE REGULATIONS OF THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) AND OTHER GOVERNING AGENCIES. 13. DO NOT REMOVE OR DISTURB ANY ASBESTOS CONTAINING MATERIALS FROM THE PROJECT. IMMEDIATELY STOP WORK AND NOTIFY THE OWNER, TENANT, OR LANDLORD IF ASBESTOS CONTAINING MATERIALS ARE SUSPECTED. 14. BEFORE SUBMITTING A PROPOSAL ON THE WORK CONTEMPLATED, EXAMINE THE SITE OF THE PROPOSED WORK AND BECOME THOROUGHLY FAMILIAR WITH THE EXISTING CONDITIONS AND LIMITATIONS. NO EXTRA COMPENSATION WILL BE ALLOWED BECAUSE OF MISUNDERSTANDINGS AS TO THE AMOUNT OF WORK INVOLVED NOR BIDDERS LACK OF KNOWLEDGE OF EXISTING CONDITIONS WHICH COULD HAVE BEEN DISCOVERED OR REASONABLY ANTICIPATED PRIOR TO BIDDING. 15. CONDUITS, PIPES, DUCTS, LIGHTS, DEVICES, SPEAKERS, ETC., SHOWN ON THE DRAWINGS AS EXISTING HAVE BEEN BASED ON EXISTING PLANS AND MAY NOT BE INSTALLED AS ORIGINALLY SHOWN. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VISIT THE SITE AND MAKE EXACT DETERMINATION OF THE EXISTENCE, LOCATION, AND CONDITION OF SUCH FACILITIES PRIOR TO SUBMITTING AS BID. 16. CONSULT THE DRAWINGS AND SPECIFICATIONS OF MECHANICAL AND OTHER TRADES FOR CORRELATING INFORMATION AND LAYOUT WORK SO THAT THE ELECTRICAL WORK WILL COORDINATE WITH OTHER TRADES. VERIFY DIMENSIONS AND CONDITIONS (I.E. FINISHED CEILING HEIGHTS, FOOTING AND FOUNDATION ELEVATIONS, BEAM DEPTHS, ETC.) WITH THE ARCHITECTURAL AND STRUCTURAL DRAWINGS. NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS THAT CANNOT BE RESOLVED, IN THE FIELD, BY AFFECTED TRADES. REPLACEMENT OF WORK DUE TO LACK OF COORDINATION AND FAILURE TO VERIFY EXISTING CONDITIONS WILL BE COMPLETED AT NO COST TO THE OWNER, TENANT, OR LANDLORD. 17. INSTALL ALL CONDUITS, CABLE TRAY, BUS DUCT, EQUIPMENT, ETC., ALLOWING PROPER CODE AND MAINTENANCE CLEARANCES AND TO AVOID BLOCKING PASSAGEWAYS AND ACCESS PANELS. 18. WHERE WORK MUST BE REPLACED DUE TO THE FAILURE OF THE CONTRACTOR TO VERIFY THE CONDITIONS EXISTING ON THE PROJECT, SUCH REPLACEMENT MUST BE ACCOMPLISHED AT NO COST TO THE TENANT OR LANDLORD. THIS APPLIES TO SHOP FABRICATED WORK AS WELL AS TO WORK FABRICATED IN PLACE. 19. THROUGHOUT THE COURSE OF THE WORK, MINOR CHANGES AND ADJUSTMENTS TO THE INSTALLATION MY BE REQUESTED BY THE ENGINEER. THE CONTRACTOR SHALL MAKE ADJUSTMENTS WITHOUT ADDITIONAL COST TO THE TENANT OR LANDLORD, WHERE SUCH ADJUSTMENTS ARE NECESSARY TO THE PROPER INSTALLATION AND OPERATION WITHIN THE INTENT OF THE CONTRACT DOCUMENTS. THIS DOES NOT INCLUDED WORK ALREADY COMPLETED. 20. OBTAIN EXACT LOCATION OF CONNECTION TO EQUIPMENT FURNISHED BY OTHERS FROM THE PERSON FURNISHING THE EQUIPMENT. 21. DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND WHAT IS CALLED FOR IN EITHER ONE IS AS BINDING AS IF CALLED FOR IN BOTH. 22. PROVIDE THE BETTER QUALITY, GREATER QUANTITY, OR HIGHER COST FOR AN ITEM OR ARRANGEMENT WHERE A DISAGREEMENT EXISTS IN THE DRAWING AND SPECIFICATIONS. 23. GUARANTEE AND MAINTAIN THE STABILITY OF WORK AND MATERIALS, AND KEEP SAME IN PERFECT REPAIR AND CONDITION FOR THE PERIOD OF ONE (1) YEAR AFTER THE FINAL COMPLETION OF THE WORK. 24. DEFECTS OF ANY KIND DUE TO THE FAULTY WORK OR MATERIALS APPEARING DURING THE ABOVE MENTIONED GUARANTEE PERIOD MUST BE IMMEDIATELY MADE GOOD BY THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE TENANT AND ARCHITECT AND ENGINEER. INCLUDE DAMAGE TO THE FINISH OR THE BUILDING RESULTING FROM THE ORIGINAL DEFECT OR REPAIRS. 25. REPLACE ALL RECEPTACLES, SWITCHES, COVERPLATES, ETC., DAMAGED BY ANY CONTRACTOR DURING THE COURSE OF CONSTRUCTION. 26. MATERIALS FURNISHED FOR THE TEMPORARY LIGHTING AND POWER SYSTEM REMAIN THE CONTRACTOR'S PROPERTY. REMOVE WHEN THERE IS NO LONGER ANY NEED FOR TEMPORARY LIGHTING AND POWER. 27. COORDINATE/SCHEDULE ALL WORK WITH THE OWNER, TENANT, OR LANDLORD TO MINIMIZE ANY DISRUPTIONS. CONFINE ALL INTERRUPTIONS TO THE SMALLEST POSSIBLE AREA. PROVIDE TEMPORARY CONNECTIONS IF REQUIRED TO PROVIDE CONTINUITY OF SERVICE. 28. INSPECT ALL AREAS AFFECTED BY THE INTERRUPTIONS AND RETURN ALL AUTOMATICALLY CONTROLLED EQUIPMENT, ELECTRICALLY OPERATED EQUIPMENT TO THE SAME OPERATING CONDITION PRIOR TO THE INTERRUPTION. 29. NO FIRE ALARM SYSTEMS ARE TO REMAIN INACTIVE AT THE END OF THE WORK DAY. ASSURE THAT THE FIRE ALARM SYSTEM IS OPERATIONAL AT THE END OF EACH WORK DAY. COORDINATE WITH THE OWNER OR LANDLORD. 30. DO NOT DISTURB NORMAL USE OF THE FACILITY, EXCEPT WITH THE IMMEDIATE CONSTRUCTION AREA. KEEP WALKS, DRIVEWAYS, ENTRANCES, ETC., FREE AND CLEAR OF EQUIPMENT, MATERIALS, AND DEBRIS. 31. STORE ALL EQUIPMENT AND MATERIALS IN A PLACE AND MANNER THAT MINIMIZES CONGESTION AND IS APPROVED BY THE OWNER, TENANT, AND LANDLORD. 32. PROVIDE NEW MATERIAL AND EQUIPMENT, UNLESS NOTED OTHERWISE. PROTECT EQUIPMENT AND MATERIAL FROM DAMAGE, DIRT, AND THE WEATHER. 33. PROVIDE THE HIGHEST QUALITY WORKMANSHIP, AND PERFORM ALL WORK ONLY BY SKILLED MECHANICS. INSTALL MATERIAL AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, INSTRUCTIONS, AND CURRENT NECA STANDARDS. 34. THE OWNER, TENANT, AND LANDLORD RESERVES THE RIGHT TO REJECT MATERIAL, EQUIPMENT, OR WORKMANSHIP NOT IN ACCORDANCE WITH THE SPECIFICATIONS, BEFORE OR AFTER INSTALLATION. 35. PERFORM ALL CUTTING AND PATCHING NECESSARY TO WORK, UNLESS SPECIFICALLY DELEGATED TO THE GENERAL CONTRACTOR. OBTAIN SPECIAL PERMISSION FROM THE OWNER OR LANDLORD BEFORE CUTTING STRUCTURAL MEMBERS OR FINISHED MATERIAL. PERFORM ALL PATCHING IN SUCH AS MANNER AS TO LEAVE NO VISIBLE TRACE AND RETURN THE AREA AFFECTED TO THE CONDITION OF UNDISTURBED WORK. PERFORM ALL PATCHING BY WORKS EXPERIENCED, SKILLED, AND LICENSED FOR THE PARTICULARLY TYPE OF WORK INVOLVED. INFERIOR WORK WILL NOT BE ACCEPTED. 36. PATCH ALL HOLES LEFT AS A RESULT OF DEMOLITION OF ELECTRICAL EQUIPMENT AND DEVICES. 37. PREVENT THE SPREAD OF DUST, DEBRIS, AND OTHER MATERIAL INTO ADJACENT AREAS. 38. REPLACE ALL CEILING TILES DAMAGED DURING INSTALLATION OF THE WORK WITH NEW TILE MATCHING THE EXISTING. 39. REFINISH ALL ELECTRICAL EQUIPMENT DAMAGED DURING SHIPPING AND/OR INSTALLATION TO ITS ORIGINAL CONDITION. REMOVE ALL RUST, PRIME, AND PAINT PER MANUFACTURER'S RECOMMENDATIONS FOR FINISH EQUAL TO ORIGINAL. 40. PAINT ALL NEW RACEWAY SYSTEMS IN EXPOSED FINISHED AREAS. 41. AFTER TESTS HAVE BEEN MADE AND ACCEPTED, CLEAN LIGHT FIXTURES, PANELS, AND OTHER EQUIPMENT INSTALLED BY THE CONTRACTOR, LEAVING THE ENTIRE WORK AREA IN A CLEAN AND COMPLETE WORKING ORDER. 42. OPERATE EQUIPMENT AND SYSTEMS IN ALL THEIR OPERATING MODES TO VERIFY PROPER OPERATION PRIOR TO FINAL INSPECTION AND OWNER INSTRUCTIONS. NOTIFY THE ENGINEER, IN WRITING, THAT ALL SYSTEMS HAVE BEEN TESTED AND ARE FUNCTIONING AND OPERATING PROPERLY. 43. INCLUDE DOCUMENTATION OF INSTRUCTIONS IN THE OPERATION AND MAINTENANCE MANUALS. 44. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO ELECTRICAL EQUIPMENT OR MATERIALS UNTIL FINAL ACCEPTANCE OF THE ENTIRE PROJECT BY THE TENANT. KEEP ALL EQUIPMENT AND MATERIALS CLEAN UNTIL FINAL ACCEPTANCE OF THE ENTIRE PROJECT BY THE OWNER, TENANT, AND/OR LANDLORD. 45. ROOF PENETRATIONS: COORDINIATE WITH THE OWNER, TENANT, AND/OR LANDLORD. 46. MECHANICAL SUBSTITUTIONS: INVOICE MECHANICAL CONTRACTOR, NOT TENANT, FOR COSTS INCLUDED DUE TO SUBSTITUTION OF MECHANICAL EQUIPMENT HAVING ELECTRICAL REQUIREMENTS DIFFERING FROM THOSE INDICATED ON PLANS. 6. PROVIDE ALL SWITCH AND RECEPTACLE WIRING DEVICES FROM A SINGLE MANUFACTURER. PROVIDE ALL DIMMERS FROM A SINGLE MANUFACTURER. 2. ACCEPTABLE MANUFACTURERS: BUSSMAN, MERSEN, LITTELFUSE, OR PRE-APPROVED EQUAL. 3. ALL FUSES FOR MAIN, FEEDER, AND BRANCH CIRCUITS SHALL BE BY THE SAME MANUFACTURER IN ORDER TO RETAIN SELECTIVITY AND ELECTRICAL COORDINATION AS DESIGNED. 4. APPLY FUSE MANUFACTURER'S AMBIENT TEMPERATURE ADJUSTMENT FACTORS TO FUSE RATINGS WHERE AMBIENT TEMPERATURES TO WHICH FUSES ARE DIRECTLY EXPOSED ARE LESS THAN 40 DEGREES f OR GREATER THAN 100 DEGREES 4. 1.6.2. HID BALLAST SHALL BE PULSE-START, CONSTANT WATTAGE SECONDARY SINGLE LAMP TYPE, 90% POWER FACTOR, BUILT-IN THERMAL PROTECTION 10% VOLTAGE/WATTAGE REGULATOR, DUAL VOLTAGE, INCLUDE CORE AND COIL, CAPACITOR, IGNITER, ETC., IN A SINGLE PACKAGE. 1.5. FLUORESCENT FXITURES: 1.6. HIGH INTENSITY DISCHARGE (HID) FIXTURES: 1.4.1. LED ENGINE PACKAGE SHALL BE RATED FOR A MINIMUM OPERATIONAL LIFE OF 50,000 HOURS FOR 40 DEGREES C. AMBIENT TEMPERATURE UNLESS OTHERWISE INDICATED.. 1.4.2. RATED OPERATING TEMEPERATURE RANGE OF -30 DEGREES C TO +40 DEGREES C. 1.4.3. PHOTOMETRY TO BE COMPLIANT WITH IESNA-LEM-79 AND CONDUCTED AT 35 DEGREES C. AMBIENT TEMPERATURE. 1.4.4. DRIVER TO BE U.L. LISTED, HAVE CLASS "A" SOUND RATING, AND PROVIDE FLICKER-FREE PERFORMANCE, POWER FACTOR OF 0.90 OR GREATER, TOTAL HARMONIC DISTORTION (CURRENT AND VOLTAGE) NOT TO EXCEED 20%, AND INTEGRAL SURGE SUPPRESSION. 2.1. LED SOURCES SHALL BE 3500°K WITH MINIMUM CRI OF 80 UNLESS OTHERWISE INDICATED 2.5. EXTERIOR HID LAMPS SHALL BE CLEAR ENVELOPE, 4000°K WITH SELF-EXTINGUISHING SAFETY ARC TUBE AND A MINIMUM CRI OF 65 UNLESS OTHERWISE INDICATED. 2.6. INCANDESCENT LAMPS SHALL BE EXTENDED LIFE TYPE UNLESS OTHERWISE INDICATED. 27 05 00 -COMMON WORK RESULTS FOR COMMUNICATIONS SYSTEMS 1. PROVIDE SLEEVES FOR SYSTEM WIRING AND CABLING PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS. USE PIPE SLEEVES UNLESS PENETRATION ARRANGEMENT REQUIRES RECTANGULAR SLEEVE OPENING. EXTEND SLEEVES INSTALLED IN FLOORS TO 2 INCHES ABOVE FINISHED FLOOR LEVEL. SEAL ANNULAR SPACE BETWEEN SLEEVE AND PATHWAY OR CABLE WITH JOINT SEALANT APPROPRIATE FOR SIZE, DEPTH, AND LOCATION OF JOINT. FIRESTOP ALL FIRE RATED ASSEMBLY PENETRATIONS. 2. GIVE RIGHT-OF-WAY TO PIPING SYSTEMS INSTALLED THAT REQUIRE SLOPE. 27 15 00 -COMMUNICATIONS HORIZONTAL CABLING 1. ALL SYSTEM BACKBOARDS, PATHWAYS, HARDWARE, CONNECTORS, JACKS, AND CABLING SHALL BE IN ACCORDANCE I.U. HEALTH TELECOM STANDARDS. 2. INSTALL ALL TELECOMMUNICATIONS SYSTEM EQUIPMENT, HARDWARE, AND CABLING IN ACCORDANCE I.U. HEALTH TELECOM STANDARDS. 27 60 00 -COMMUNICATIONS SYSTEMS ROUGH-IN REQUIREMENTS 1. SYSTEM OUTLET BOXES TOTAL DEPTH, WITH PLASTER RING, TO BE A MINIMUM OF 2 5/8" DEEP . 2. RACEWAYS TO BE EMT WITH CONDUIT BUSHING AT BOTH ENDS. MINIMUM SIZES SHALL BE AS FOLLOWS: COMMUNICATIONS HORIZONTAL CABLING: 1" TRADE SIZE.2.1 ACCESS CONTROL SYSTEMS: 3/4" TRADE SIZE.2.2 CATV AND VIDEO SURVEILLANCE SYSTEMS: 3/4" TRADE SIZE.2.3 28 05 00 -COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SYSTEMS 1. PROVIDE SLEEVES FOR SYSTEM WIRING AND CABLING PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS. USE PIPE SLEEVES UNLESS PENETRATION ARRANGEMENT REQUIRES RECTANGULAR SLEEVE OPENING. EXTEND SLEEVES INSTALLED IN FLOORS TO 2 INCHES ABOVE FINISHED FLOOR LEVEL. SEAL ANNULAR SPACE BETWEEN SLEEVE AND PATHWAY OR CABLE WITH JOINT SEALANT APPROPRIATE FOR SIZE, DEPTH, AND LOCATOIN OF JOINT. FIRESTOP ALL FIRE RATED ASSEMBLY PENETRATIONS. 2. GIVE RIGH-OF-WAY TO PIPING SYSTEMS INSTALLED THAT REQUIRE SLOPE. 28 31 00 -FIRE ALARM SYSTEM 1. EXTEND/MODIFY THE EXISTING FIRE ALARM SYSTEM AS INDICATED FOR THE INDICATED RENOVATION WORK. MAINTAIN AND EXTEND ALL FEATURES AND FUNCTIONS OF THE EXISTING SYSTEM FOR THE NEW WORK. INSTALLER SHALL BE AUTHORIZED TO PERFORM THE WORK BY THE EXISTING FIRE ALARM SYSTEM MANUFACTURER. 3.1. NOTIFY THE LOCAL FIRE MARSHAL PRIOR TO ANY DISRUPTION OF THE SYSTEM. 2. ALL NEW SYSTEM EQUIPMENT AND WIRING SHALL BE COMPATIBLE WITH THE EXISTING SYSTEM AND SHALL BE APPROVED FOR USE WITH THE EXISTING SYSTEM BY THE MANUFACTURER OF EXISTING SYSTEM. 3. KEEP THE EXISTING FIRE ALAM SYSTEM OPERATIONAL AT ALL TIMES DURING THE WORK, EXCEPT FOR APPROVED SHUTDOWNS REQUIRE FOR THE INDICATED WORK. 3.2. MAKE ALL SYSTEM CHANGES OR SHUTDOWNS SO AS TO PROVIDE MINIMUM INTERFERENCE TO THE OPERATION OF THE FACILITY. NOTIFY THE OWNER, TENANT, AND/OR LANDLORD NOT LESS THAN 24 HOURS IN ADVANCE OF A SHUTDOWN/CHANGEOVER, AND OBTAIN APPROVAL FROM THE OWNER, TENANT, AND/OR LANDLORD. 4. INSTALL ALL SYSTEM WIRING AND CABLING IN CONDUIT OR FIRE ALAM ARMORED CABLE. MINIMUM OF #14 THHN WIRES. 5. GIVE RIGHT-OF-WAY TO PIPING SYSTEMS INSTALLED THAT REQUIRE SLOPE. 7. COLOR: DEVICES AND COVERPLATES SHALL MATCH EXISTING COLOR FOR NORMAL AND EMERGENCY. www.studio3design.net Phone: (317) 595.1000 8604 Allisonville Road, Suite 330 Indianapolis, IN 46250 A B C D E 1 2 3 4 5 6 7 A B C D E THESE DRAWINGS ARE THE PROPERTY OF STUDIO 3 DESIGN, INC. ALL RIGHTS RESERVED PROJECT NUMBER: DATE: CERTIFICATION: SHEET DESCRIPTION: SHEET NUMBER: REVISION SCHEDULE: 1 2 3 4 5 6 7 21019 IUH SPRINGMILLGI CLINIC RENOVATION: PHASE IApril 9, 2021 Electrical Specifications E00210300 N. ILLINOIS ST.INDIANAPOLIS, IN 46290# Revision Description Date Issued 06/08/21