HomeMy WebLinkAboutE801 - Electrical Schedules and DetailsFACE PLATE
CONFIGURATION
DATA ONLY
(1) 1-1/4" EMT CONDUIT
WITH NYLON BUSHING
STUBBED TO ACCESSIBLE
CEILING
4-11/16" x 4-11/16"
SQUARE BOX
2-7/8" DEEP
5-8 DATA
OUTLETS
4-11/16" x 4-11/16"
SQUARE BOX
2-7/8" DEEP
2-GANG TILE
RING 1/2" DEEP
(2) 1-1/4" EMT CONDUITS WITH NYLON
BUSHING STUBBED TO ACCESSIBLE
CEILING
1-4 DATA
OUTLETS
1/2" DEEP
TILE RING
M
C
FFRDRA ST
V
A A
R
SF F
EXISTING
FIRE ALARM
CONTROL
PANEL
TYPICAL FOR EACH FLOOR
120V
FIRE ALARM
POWER
PROVIDE SIGNAL
EXPANDER/AMPLIFIER POWER
SUPPLY ON EACH FLOOR FOR
SIGNAL DEVICES. LOCATE
EQUIPMENT IN ELECTRICAL
ROOM.
PROVIDE SPARE CAPACITY TO
ADD (2) SIGNAL DEVICES (TYP.
OF EACH SIGNAL CIRCUIT)
ADDRESSABLE RELAY FOR CONTROL PROVIDE ONE
AT EACH AHU SUPPLY AND RETURN FAN
STARTERS, AT EACH FIRE/SMOKE DAMPER AND AT
EACH DOOR HOLD RELEASE DEVICE
PROVIDE SPARE CAPACITY
TO ADD 20% FUTURE DEVICES ON
EACH INITIATION LOOP
TYPICAL
FIRE/SMOKE
DAMPER
TYPICAL DOOR
HOLD/RELEASE
DEVICE
TYPICAL
HVAC UNIT
STARTER
PROVIDE CONTROL WIRING
IN CONDUIT AS REQUIRED
TO OTHER DEVICES
SEE
FLOOR PLANS
NOTES:
1. ALL FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT
COMPLETE.
2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITIES.
3. EXISTING FIRE ALARM PANEL WORK SHALL INCLUDE ALL NEW CARDS,
EQUIPMENT AND PROGRAMMING NECESSARY TO SUPPORT THE NEW
DEVICES AS INDICATED.
4. LABEL ALL FIRE ALARM DEVICES AS DIRECTED BY THE OWNER WITH
EXTERNAL TAGS AND LABELS ON DEVICE bASES.
TYPICAL SMOKE
DETECTOR WITH
SOUNDER BASE
ELECTRICAL 1012
SUPPORT STRUCTURE
NOTE: FOR STEEL STRUCTURAL SYSTEM
COMBINATION BEAM CLAMP AND
CONDUIT HANGER OR EQUIVALENT
CADDY SCREW
GUN BRACKET
NOTE: FOR METAL STUD WALL CONSTRUCTION ONLY.
4" SQUARE BOX
METAL STUDS
CONDUIT
BOX MOUNTING
BRACKET
REFER TO DETAIL ON THIS SHEET
FOR ADDITIONAL INFORMATION.
LOCATED AS SHOWN ON
DRAWINGS.
CAT 6A CABLE
1-1/4" CONDUIT TO CABLE
TRAY. TERMINATE CONDUITS
WITH BUSHING. (TYPICAL)
FIRST FLOOR
NOTES:
1. SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT,
DUCTWORK, PIPING,STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT
ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT
IS NOT INSTALLED IN AN ACCEPTABLE MANNER.
2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY.
3. PROVIDE PLENUM RATED WIRE / CABLE AS REQUIRED.
4. PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW
DEVICE QUANTITIES AND LOCATIONS.
EXISTING
DATA RACK
NUMBER INDICATES
QUANTITY OF CABLES TO
BE INSTALLED
2
EXISTING CABLE TRAY
TELECOMMUNICATIONS
CABLE TO BE TERMINATED
AT IDF BY CONTRACTOR.
TELECOM
EQUIPMENT
PROVIDED BY
OWNER AS
REQUIRED.
1
WAP
COMPUTER 1006
SUPPORT CONNECTED TO STRUCTURE ABOVE
12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE
LAY-IN CEILING
LAY-IN CEILING
JUNCTION BOX
W/#12 WIRE (6' MAX.)
FLEXIBLE CONDUIT
LAY-IN CEILING
LAY-IN CEILING
SEISMIC
CLIP
www.studio3design.net
Phone: (317) 595.1000
8604 Allisonville Road, Suite 330
Indianapolis, IN 46250
A
B
C
D
E
1 2 3 4 5 6 7
A
B
C
D
E
THESE DRAWINGS ARE THE PROPERTY
OF STUDIO 3 DESIGN, INC. ALL RIGHTS
RESERVED
PROJECT NUMBER:
DATE:
CERTIFICATION:
SHEET DESCRIPTION:
SHEET NUMBER:
REVISION SCHEDULE:
1 2 3 4 5 6 7
21019 IUH SPRINGMILLGI CLINIC RENOVATION: PHASE IApril 9, 2021
Electrical
Schedules and
Details
E80110300 N. ILLINOIS ST.INDIANAPOLIS, IN 46290LIGHT FIXTURE SCHEDULE - SUITE 1200
FIXTURE
TYPE FIXTURE NAME DESCRIPTION VOLTAGE WATTAGE LAMP LUMENS COLOR
TEMPERATURE
ACCEPTABLE
MANUFACTURERS
L1 FLAT PANEL 2' X 4' LED FLAT PANEL, WHITE HOUSING, WHITE FROSTED LENS, 0-10V DIMMING
277 V 61 W LED 6000 3500K
LITHONIA EPANL,
METALUX 24FP,
COLUMBIA CFP,
OR APPROVED EQUAL
L2 FLAT PANEL 2' X 2' LED FLAT PANEL, WHITE HOUSING, WHITE FROSTED LENS, 0-10V DIMMING
277 V 41 W LED 4000 3500K
LITHONIA EPANL,
METALUX 24FP,
COLUMBIA CFP,
OR APPROVED EQUAL
L3 DOWNLIGHT 8" APERTURE X 8" HIGH OPEN DOWNLIGHT, LOW IRIDESCENT SEMI SPECULAR CLEAR
ALUMINUM RELFECTOR, SELF TRIM WITH WHITE FLANGE. 0-10V DIMMING DRIVER
(1%-100%).277 V 28 W LED 1800 3500K
LITHONIA - LDN4
ELITE LIGHTING - HH4
HALO - HC4
PRESCOLITE - LF4LED
NO SCALE1FLUSH MOUNTED DATA OUTLET
NO SCALE2FIRE ALARM SYSTEM SCHEMATIC
NO SCALE32" AND SMALLER CONDUIT SUPPORT DETAIL
NO SCALE4WALL BOX INSTALLATION DETAIL
NO SCALE5TELECOM SYSTEM DETAIL
NO SCALE6LAY IN LIGHT FIXTURE DETAIL