HomeMy WebLinkAboutH801 - HVAC Schedules and DetailsGRILLE SCHEDULE
TAG NOM SIZE NECK MAX NC TYPE MFR MODEL FINISH NOTES
R1 24 x 12 - 20 EGGCRATE GRILLE PRICE 80 WHITE 1 , 2
NOTES:
1.CONFIRM FINAL FINISHES WITH ARCHITECT.
2.PROVIDE FRAME STYLE APPROPRIATE FOR CEILING TYPE (I.E. LAY-IN, SURFACE MOUNT, SIDEWALL, ETC.) REFER TO DRAWINS AND ARCHITECTURAL CEILING
PLANS FOR LOCATIONS. COLOR AND FINISH TO BE APPROVED BY ARCHITECT.
AIR CHANGE SCHEDULE
ROOM NUMBER ROOM NAME
AREA
(SQ.
FT)
OCCUPANTS
CEILING
HEIGHT
(FT.)
% OA ROOM
CLASSIFICATION
ASHRAE 170 - 2017 2012 MECHANICAL CODE / ASHRAE 62.1
MINIMUM AIR VOLUME MAXIMUM AIR VOLUME
EXHAUSTMIN OA
ACH
REQ'D
MIN
AIRFLOW
ACH
REQUIRED
PRESSURE
RELATIONSHIP TO
ADJACENT AREAS
ALL
ROOM
EXHAUSTED
DIRECTLY
OUTDOORS
OUTDOOR
AIRFLOW
RATE
(CFM/PERSON)
OUTDOOR
AIRFLOW
RATE
(CFM/SQ FT)
MINIMUM
OUTSIDE AIR OA
SUPPLIED SPACE AIRFLOW OA ACH ACH AIRFLOW OA ACH ACH
1 WAITING 348 5 11 19% RECEPTION AREA - - - - 5 0.06 57 60 315 0.9 4.9 630 1.9 9.9
2 OFFICE 95 1 8.5 19% OFFICE - - - - 5 0.06 13 32 165 2.3 12.3 250 3.5 18.6
3 RECEPTION 175 4 11 19% RECEPTION AREA - - - - 5 0.06 38 47.8 250 1.5 7.8 500 3.0 15.6
4 MD NURSE 163 4 8.5 19% OFFICE - - - - 5 0.06 37 47.8 250 2.1 10.8 500 4.1 21.7
5 W&M 133 0 10 19% CORRIDOR - - - - 0 0.06 10 6.7 35 0.3 1.6 35 0.3 1.6
6 PATIENT RR 53 0 8.5 19% TOILET ROOM - 10 NEGATIVE YES - - - 15.3 80 - 10.7 - - - 80
7 EXAM 1 113 2 8.5 19% GENERAL EXAM 2 4 NR NR - - - 35.3 185 2.2 11.6 260 3.1 16.2
8 EXAM 2 122 2 8.5 19% GENERAL EXAM 2 4 NR NR - - - 35.3 185 2.0 10.7 260 2.9 15.0
9 EXAM 3 117 2 8.5 19% GENERAL EXAM 2 4 NR NR - - - 33.4 175 2.0 10.6 300 3.5 18.1
10 STORAGE 33 0 8.5 19% CLEAN LINEN STORAGE 0 2 POSITIVE NR 5 0.06 2 5.7 30 1.2 6.4 20 0.8 4.3
11 EXAM 4 94 2 8.5 19% GENERAL EXAM 2 4 NR NR - - - 26.7 140 2.0 10.5 140 2.0 10.5
12 WORK ALCOVE 90 1 8.5 19% OFFICE - - - - 5 0.06 13 13.0 68 1.0 5.3 70 1.0 5.5
1
2
DUCTWORK/DIFFUSER SHALL BE SUPPORTED
INDEPENDENTLY FROM STRUCTURE
(NOT SUPPORTED BY CEILING) INSIDE
OF PLENUM TO BE PAINTED FLAT BLACK.
INSULATED FLEXIBLE DUCTWORK
ADJUST AIR FLOW SLOTS
PER SCHEDULE AND PLANS.
PLAN NOTES
1. A MAXIMUM OF FIVE (5) FEET LENGTH OF FLEXIBLE DUCT SHALL BE PROVIDED TO EACH DIFFUSER. DUCTWORK
SHALL CONTAIN 180° OF BENDING. FLEX DUCT SHALL NOT CONTACT CEILING AND SHALL BE PROPERLY
SUPPORTED SO AS TO HAVE NO KINKS.
2. TIE-WRAP CONNECT FLEX DUCT HELICAL COIL TO ROUND METAL DIFFUSER NECK AND TO ROUND METAL
DUCTWORK AT OTHER END OF FLEX DUCT. PULL FLEX DUCT VAPOR BARRIER OVER LOWER TIE-WRAP AND
INSTALL SECOND TIE-WRAP OVER THE VAPOR BARRIER. INSULATE METAL DUCT OR DIFFUSER OVER TOP OF
SECOND TIE-WRAP AND INSTALL INSULATOR'S TAPE ON EDGES.
ROUND BRANCH DUCT TO MAIN
(SEE SCHEDULE FOR SIZE)
PLENUM BOX
HEIGHT = ROUND
DUCT DIAMETER + 4"
SLOT DIFFUSER
(THREE SLOT SHOWN)
EXTERNALLY
INSULATE PLENUM.
INTERNAL INSULATION
IS NOT ALLOWED.
RETURN GRILLE
8"
SHEETMETAL DUCT BOOT. COVER
INSIDE WITH 3/4" ARMAFLEX INSULATION.
CEILING
SUPPORT ROD
24"
SUPPORT RETURN GRILLE AND SOUND
BOOT FROM STRUCTURE ABOVE.
MINIMUM 8" OR HIGHER TO CLEAR
LIGHTS AND ASSOCIATED
ACCESS ABOVE LIGHTS.8"
www.studio3design.net
Phone: (317) 595.1000
8604 Allisonville Road, Suite 330
Indianapolis, IN 46250
A
B
C
D
E
1 2 3 4 5 6 7
A
B
C
D
E
THESE DRAWINGS ARE THE PROPERTY
OF STUDIO 3 DESIGN, INC. ALL RIGHTS
RESERVED
PROJECT NUMBER:
DATE:
CERTIFICATION:
SHEET DESCRIPTION:
SHEET NUMBER:
REVISION SCHEDULE:
1 2 3 4 5 6 7
21019 IUH SPRINGMILLGI CLINIC RENOVATION: PHASE IApril 9, 2021
HVAC Schedules
and Details
H80110300 N. ILLINOIS ST.INDIANAPOLIS, IN 46290# Revision Description
Date
Issued
NO SCALE2LINEAR SLOT DIFFUSER DETAIL
NO SCALE3RETURN GRILLE WITH SOUND BOOT DETAIL