HomeMy WebLinkAboutElectrical Roof PlanCHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x22020/OCT/20 ISSUED FOR PERMITTING
118/FEB/21 ISSUED FOR PERMITTING
02/14/2017 04:16 PM
20/OCT/20
DESIGNER
1R IN-512459-E10
J.P. MORGAN CHASE
10495 N MICHIGAN RD, CARMEL, IN 46032-7939
ELECTRICAL ROOF PLAN
ROOF DESIGN CLEARANCE TABLE (SEE LEGEND FOR APPLICABLE HATCH)
ITEM MINIMUM CLEARANCE DIMENSIONS
FLAT ROOF 4'-0"
PITCHED ROOF:
ALONG RIDGE 6'-0" (3'-0" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG HIPS/VALLEY 3'-0" (18" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG EAVE/FREE EDGE 0'-10"
PITCHED ROOF:
OTHER CLEARANCE ON ROOF PLANE 3'-0"
01 ELECTRICAL ROOF PLAN
NOT TO SCALE
SBJ SBJ APN
APN
SBJ SBJ JDL JASON D. LEIMBACK
11100106
INDIANA
JDL
20/OCT/20
LEGEND:
FLAT ROOF CLEARANCE AREA
PITCHED ROOF CLEARANCE AREA
(E) EXISTING
NOTES:
1. CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS AND ROOF SLOPES
AND COORDINATE WITH ALL REFERENCE DRAWINGS AS REQUIRED. IF THE
CONTRACTOR ENCOUNTERS CONDITIONS OTHER THAN WHAT IS SHOWN ON
THE DRAWINGS, CONTRACTOR SHALL NOTIFY THE ENGINEER
OF RECORD PRIOR TO START OF CONSTRUCTION.
2. SEE SHEET SG20 AND SG21 FOR GENERAL NOTES, LEGEND AND SYMBOLS.
3. SEE SHEETS SE10 AND SE11 FOR ELECTRICAL DETAILS.
4. FOR THREE PHASE SYSTEMS, MODULES OF SIMILAR
ORIENTATION SHALL BE PAIRED WITH ONE OPTIMIZER
WHERE POSSIBLE.
5. OBSTRUCTIONS IN CLEARANCE AREA PATHWAYS SHALL BE KEPT TO A
MINIMUM. WHERE CONDUIT INTERSECTS CLEARANCE AREA PATHWAYS,
CONDUIT SHALL BE PLACED TRANSVERSE TO CLEARANCE AREA PATHWAYS.
6. GROUNDING TRANSFORMER SHALL BE GROUND MOUNTED PER DETAILS ON
SS30.
7. SUBCONTRACTOR SHALL MAINTAIN MINIMUM 3' RADIAL CLEARANCE FROM
GAS RISER METER.INV1
PNL1
GTR1
PNL 2
T
1-1
1-1
1-2
1-2
M
UDS
(N) INVERTER
ARRAY 1 - 10.875 kW
[x29] (N) MODULES
TILT: 26.5 DEGREES
ROOF PITCH: 6:12
AZIMUTH: 162 DEGREES SOUTHEAST
(N) GROUNDING TRANSFORMER
NOTE 6
(N) PV EFFECTIVE GROUNDING AC PANEL
(N) METERING AND SURGE PROTECTION CABINET
(N) TRANSFORMER
ARRAY 2 - 7.50 kW
[x20] (N) MODULES
TILT: 26.5 DEGREES
ROOF PITCH: 6:12
AZIMUTH: 72 DEGREES NORTHEAST
(E) ELECTRICAL ROOM WITH ELECTRICAL SERVICE PANEL
(N) PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH
(E) COMBINATION CT ENCLOSURE AND UTILITY METER
ARRAY 3 - 3.75 kW
[x10] (N) MODULES
TILT: 25 DEGREES
ROOF PITCH: 5.6:12
AZIMUTH: 162 DEGREES SOUTHEAST
ARRAY 4 - 4.50 kW
[x12] (N) MODULES
TILT: 25.74 DEGREES
ROOF PITCH: 5.8:12
AZIMUTH: 162 DEGREES SOUTHEAST
S W2
(N) INVERTER DISCONNECT SWITCH G
(E) GAS RISER METER
NOTE 7
(N) NEMA 3R LOCKABLE WIREWAY
SBJ APNSBJ JDL JDL
03
ELECTRICAL EQUIPMENT ELEVATION VIEW
NOT TO SCALE
(N) INVERTER
(N) INVERTER DISCONNECT SWITCH
(N) GROUNDING TRANSFORMER
NOTE 6
(N) PV EFFECTIVE GROUNDING AC PANEL
(N) METERING AND SURGE PROTECTION CABINET
(N) TRANSFORMER
(N) PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH
02 ELECTRICAL EQUIPMENT ELEVATION VIEW
NOT TO SCALE
18-FEB-2021
06/08/21