HomeMy WebLinkAbout400130-IN-512459-REV02CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 20/OCT/20 ISSUED FOR PERMITTING
1 18/FEB/21 ISSUED FOR PERMITTING
2 13/MAY/21 ISSUED FOR PERMITTING - REVISED PER AHJ COMMENTS 02/14/2017 04:16 PM
20/OCT/20
DESIGNER
2R
J.P. MORGAN CHASE
10495 N MICHIGAN RD, CARMEL, IN 46032-7939
COVER PAGE
512459: 26.63 kWp
J.P. MORGAN CHASE
10495 N Michigan Rd
CARMEL, IN 46032-7939
ASSESSOR'S #: 29-13-07-019-002.000-018
AUTHORITIES HAVING JURISDICTION
BUILDING: CITY OF CARMEL
ZONING: CITY OF CARMEL
UTILITY: INDIANAPOLIS POWER & LIGHT (IPL)
DESIGN SPECIFICATIONS
OCCUPANCY: B
CONSTRUCTION: COMMERCIAL / INDUSTRIAL
GROUND SNOW LOAD: 20 PSF
WIND SPEED: 106 MPH
DESIGN SPECIFICATIONS
RISK CATEGORY: II
SITE CLASS: D (DEFAULT)
SEISMIC IMPORTANCE FACTOR: 1.0
SEISMIC DESIGN CATEGORY: B
SS: 0.173
S1: 0.082
SDS: 0.184
SD1: 0.131
ANALYSIS PROCEDURE: NONSTRUCTURAL COMPONENTS
DESIGN CODES & STANDARDS
BUILDING: 2018 INTERNATIONAL BUILDING CODE (SEE NOTE 1)
ELECTRICAL: 2008 NEC
FIRE: 2018 INTERNATIONAL FIRE CODE (SEE NOTE 2)
PROJECT INFORMATION
IN-512459-G10
KKT KKT TDG
TDG
SBJ SBJ
DRAWING INDEX
DRAWING NUMBER SHEET TITLE
G10 COVER PAGE
G20 SITE PLAN
E10 ELECTRICAL ROOF PLAN
E20 THREE LINE DIAGRAM & BILL OF MATERIALS
E21 ONE LINE DIAGRAM
E30 PLACARDS
REQUIRED STANDARD DRAWING INDEX
DRAWING NUMBER SHEET TITLE
SG10 COVER PAGE
SG20 GENERAL NOTES
SG21 GENERAL NOTES
SS20 PITCHED ROOF CONNECTION DETAILS
SS21 PITCHED ROOF CONNECTION DETAILS
SE10 ELECTRICAL DETAILS
SE11 ELECTRICAL DETAILS NEC 2008
SE20 METERING AND SURGE PROTECTION DETAILS 3-PHASE
SE21 AC PANEL DETAILS
SR10 THREE PHASE SYSTEM CUTSHEETS
SR25 ELECTRICAL DATA CUTSHEETS
SR26 ELECTRICAL DATA CUTSHEETS
SR30 STRUCTURAL COMPONENT CUTSHEETS
01 AERIAL PHOTO
NOT TO SCALE
02 VICINITY MAP
NOT TO SCALE
INDIANA
CLB CAMERON L. BRYANT
10505919CLB20/OCT/20
NOTE 1 : INTERNATIONAL BUILDING CODE 2018 REFERENCES THE MOST CURRENT DESIGN
PRACTICES RELATED TO STRUCTURAL ANALYSIS AND DESIGN OF ROOFTOP SOLAR
MODULE SYSTEMS. ANALYSIS AND DESIGN OF ROOFTOP SOLAR MODULE SYSTEMS WAS
PERFORMED IN ACCORDANCE WITH INTERNATIONAL BUILDING CODE 2018 AND MEETS
2014 INDIANA BUILDING CODE REQUIREMENTS.
NOTE 2 : INTERNATIONAL FIRE CODE 2018 REFERENCES THE MOST CURRENT DESIGN
PRACTICES RELATED TO DESIGN OF ROOFTOP SOLAR MODULE SYSTEMS. ANALYSIS AND
DESIGN OF ROOFTOP SOLAR MODULE SYSTEMS WAS PERFORMED IN ACCORDANCE WITH
INTERNATIONAL FIRE CODE 2018 AND MEETS 2014 INDIANA FIRE CODE REQUIREMENTS.
KKT TDG SBJ CLB CLB
SS30 TRANSFORMER FOUNDATION
KKT TDG SBJ CLB CLB
13-May-2021
06/08/21
SW2
T
PNL2
GTR1
PNL1
INV1
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 20/OCT/20 ISSUED FOR PERMITTING
1 18/FEB/21 ISSUED FOR PERMITTING
2 13/MAY/21 ISSUED FOR PERMITTING - REVISED PER AHJ COMMENTS 02/14/2017 04:16 PM
20/OCT/20
DESIGNER
2R IN-512459-G20
J.P. MORGAN CHASE
10495 N MICHIGAN RD, CARMEL, IN 46032-7939
SITE PLAN
ROOF DESIGN CLEARANCE TABLE (SEE LEGEND FOR APPLICABLE HATCH)
ITEM MINIMUM CLEARANCE DIMENSIONS
FLAT ROOF 4'-0"
PITCHED ROOF:
ALONG RIDGE 6'-0" (3'-0" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG HIPS/VALLEY 3'-0" (18" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG EAVE/FREE EDGE 0'-10"
PITCHED ROOF:
OTHER CLEARANCE ON ROOF PLANE 3'-0"
ROOF CONNECTION DETAIL TABLE
DRAWING DETAIL ROOF SLOPE FRAMING TYPE ROOF TYPE CONNECTION LOCATION NOTES
SS10 1 FLAT ROOF DECK VARIES SEE SITE PLAN SEE RACKING SITE SPECIFIC DRAWING PACKAGE IF APPLICABLE.
SS10 2 FLAT ROOF DECK LOOSE GRAVEL
SS21 1 PITCHED WOOD MEMBERS ASPHALT SHINGLE SEE DRAWING SS20
SS21 2 PITCHED ROOF DECK SINGLE-PLY MEMBRANE SEE DRAWING SS20
SS21 3 PITCHED NA METAL STANDING SEAM SEE DRAWING SS20
SS21 4 PITCHED WOOD MEMBERS CORRUGATED METAL SEE DRAWING SS20
SS21 5 PITCHED STEEL MEMBERS ASPHALT SHINGLE SEE DRAWING SS20
SS22 1 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 2 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 3 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 4 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 5 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
NOTES:
1. ROOFS WITH SLOPE LESS THAN 7 DEGREES ARE CONSIDERED "FLAT". ROOFS WITH SLOPE GREATER THAN 7 DEGREES ARE CONSIDERED "PITCHED". REFER
TO SITE SPECIFIC DWG E10 FOR ROOF SLOPE.
2. FRAMING TYPE AND ROOF TYPE SHALL BE VERIFIED ON SITE PRIOR TO INSTALLATION.
01 SITE PLAN
NOT TO SCALE
PARCEL DATA FROM LANDGRID.COM
KKT KKT TDG
TDG
SBJ SBJ
INDIANA
CLB CAMERON L. BRYANT
10505919CLB20/OCT/20
LEGEND:
FLAT ROOF CLEARANCE AREA
PITCHED ROOF CLEARANCE AREA
(E) EXISTING
(E) PROPERTY LINE
NEW TREE
NOTES:
1. CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS AND ROOF SLOPES
AND COORDINATE WITH ALL REFERENCE DRAWINGS AS REQUIRED. IF THE
CONTRACTOR ENCOUNTERS CONDITIONS OTHER THAN WHAT IS SHOWN ON
THE DRAWINGS, CONTRACTOR SHALL NOTIFY THE ENGINEER
OF RECORD PRIOR TO START OF CONSTRUCTION.
2. SEE SHEET SG20 AND SG21 FOR GENERAL NOTES, LEGEND AND SYMBOLS.
4. OBSTRUCTIONS IN CLEARANCE AREA PATHWAYS SHALL BE KEPT TO A
MINIMUM.
5. SOLAR ASSEMBLY DOES NOT INCREASE EXISTING BUILDING HEIGHT FOR
PITCHED ROOFS. FOR FLAT ROOFS, SOLAR ASSEMBLY EXTENDS 11 3/8"
MAXIMUM ABOVE ROOF SURFACE WITH UNIRAC RMDT RACKING AND EXTENDS
1'-1 7/8" MAXIMUM ABOVE ROOF SURFACE WITH IRONRIDGE BX RACKING.
3. EVEREST RACKING RAIL MAXIMUM ALLOWABLE SPAN
SHALL BE 4'-0" UNLESS NOTED OTHERWISE.
ROOF MEMBRANE: ASPHALT SHINGLES
ROOF DECK: PLYWOOD
CONNECTION DETAIL: SS21-1
RACKING TYPE: EVEREST CROSSRAIL SHARED – 48-X
MAXIMUM CONNECTION SPACING: 4'-0"
KKT TDG SBJ CLB CLB
32'-6"
NOTES:
1. THE PROVISIONS OF THE INTERNATIONAL FIRE CODE 2018, SEC. 1204.2.1
PERTAINING TO GROUP R-3 BUILDINGS (ONE OR TWO FAMILY DWELLINGS)
SPECIFIES SETBACKS AND PATHWAYS FOR PITCHED ROOFS. EXCEPTION
TO SEC. 1204.3 STATES THAT IF THE FIRE CODE OFFICIAL DETERMINES
THAT THE ROOF CONFIGURATION FOR A BUILDING OTHER THAN GROUP R-3
IS SIMILAR TO THAT OF A GROUP R-3 OCCUPANCY, THE RESIDENTIAL
ACCESS REQUIREMENTS IN SEC. 1204.2.1 ARE A SUITABLE ALTERNATIVE.
THEREFORE, CONSIDERING FIREFIGHTING OPERATIONS, BUILDINGS WITH A
PITCHED ROOF HAVE BEEN CONSIDERED SIMILAR TO THAT OF A GROUP R-3
BUILDING AND THE PROVISIONS OF SEC. 1204.2.1 WERE USED.
KKT TDG SBJ CLB CLB
13-May-2021
06/08/21
SW2
T
PNL 2
GT R1
PN L1
INV 1
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 20/OCT/20 ISSUED FOR PERMITTING
1 18/FEB/21 ISSUED FOR PERMITTING
2 13/MAY/21 ISSUED FOR PERMITTING - REVISED PER AHJ COMMENTS 02/14/2017 04:16 PM
20/OCT/20
DESIGNER
2R IN-512459-E10
J.P. MORGAN CHASE
10495 N MICHIGAN RD, CARMEL, IN 46032-7939
ELECTRICAL ROOF PLAN
ROOF DESIGN CLEARANCE TABLE (SEE LEGEND FOR APPLICABLE HATCH)
ITEM MINIMUM CLEARANCE DIMENSIONS
FLAT ROOF 4'-0"
PITCHED ROOF:
ALONG RIDGE 6'-0" (3'-0" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG HIPS/VALLEY 3'-0" (18" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG EAVE/FREE EDGE 0'-10"
PITCHED ROOF:
OTHER CLEARANCE ON ROOF PLANE 3'-0"
01 ELECTRICAL ROOF PLAN
NOT TO SCALE
SBJ SBJ APN
APN
SBJ SBJ JDL JASON D. LEIMBACK
11100106
INDIANA
JDL
20/OCT/20
LEGEND:
FLAT ROOF CLEARANCE AREA
PITCHED ROOF CLEARANCE AREA
(E) EXISTING
NOTES:
1. CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS AND ROOF SLOPES
AND COORDINATE WITH ALL REFERENCE DRAWINGS AS REQUIRED. IF THE
CONTRACTOR ENCOUNTERS CONDITIONS OTHER THAN WHAT IS SHOWN ON
THE DRAWINGS, CONTRACTOR SHALL NOTIFY THE ENGINEER
OF RECORD PRIOR TO START OF CONSTRUCTION.
2. SEE SHEET SG20 AND SG21 FOR GENERAL NOTES, LEGEND AND SYMBOLS.
3. SEE SHEETS SE10 AND SE11 FOR ELECTRICAL DETAILS.
4. FOR THREE PHASE SYSTEMS, MODULES OF SIMILAR
ORIENTATION SHALL BE PAIRED WITH ONE OPTIMIZER
WHERE POSSIBLE.
5. OBSTRUCTIONS IN CLEARANCE AREA PATHWAYS SHALL BE KEPT TO A
MINIMUM. WHERE CONDUIT INTERSECTS CLEARANCE AREA PATHWAYS,
CONDUIT SHALL BE PLACED TRANSVERSE TO CLEARANCE AREA PATHWAYS.
6. GROUNDING TRANSFORMER SHALL BE GROUND MOUNTED PER DETAILS ON
SS30.
7. SUBCONTRACTOR SHALL MAINTAIN MINIMUM 3' RADIAL CLEARANCE FROM
GAS RISER METER.
8. SUBCONTRACTOR SHALL PAINT CONDUIT, IF VISIBLE FROM GRADE, TO
MATCH THE BUILDING SURFACE IT IS ATTACHED TO (EAVE PORTION SHOULD
BE PAINTED TO MATCH EAVE; BRICK PORTION SHOULD BE PAINTED TO MATCH
BRICK). SUBCONTRACTOR SHALL PAINT TRANSFORMER ENCLOSURE,
INVERTER DISCONNECT SWITCH ENCLOSURE, GROUNDING TRANSFORMER
ENCLOSURE, PV EFFECTIVE GROUNDING AC PANEL ENCLOSURE, METERING
AND SURGE PROTECTION CABINET, IF VISIBLE FROM GRADE, TO MATCH THE
BUILDING SURFACE IT IS ATTACHED TO. SUBCONTRACTOR SHALL ENSURE
THAT EQUIPMENT NAMEPLATES AND LABELS ARE NOT PAINTED. THE
INVERTER SHALL REMAIN UNPAINTED.
9. SEE G10 FOR LANDSCAPING DETAILS.
1-1
1-1
1-2
1-2
M
UDS
(N) INVERTER
NOTE 8
ARRAY 1 - 10.875 kW
[x29] (N) MODULES
TILT: 26.5 DEGREES
ROOF PITCH: 6:12
AZIMUTH: 162 DEGREES SOUTHEAST
(N) GROUNDING TRANSFORMER
NOTE 6
(N) PV EFFECTIVE GROUNDING AC PANEL
NOTE 8
(N) METERING AND SURGE PROTECTION CABINET
NOTE 8
(N) TRANSFORMER
NOTE 8
ARRAY 2 - 7.50 kW
[x20] (N) MODULES
TILT: 26.5 DEGREES
ROOF PITCH: 6:12
AZIMUTH: 72 DEGREES NORTHEAST
(E) ELECTRICAL ROOM WITH ELECTRICAL SERVICE PANEL
(N) PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH
(E) COMBINATION CT ENCLOSURE AND UTILITY METER
ARRAY 3 - 3.75 kW
[x10] (N) MODULES
TILT: 25 DEGREES
ROOF PITCH: 5.6:12
AZIMUTH: 162 DEGREES SOUTHEAST
ARRAY 4 - 4.50 kW
[x12] (N) MODULES
TILT: 25.74 DEGREES
ROOF PITCH: 5.8:12
AZIMUTH: 162 DEGREES SOUTHEAST
(N) INVERTER DISCONNECT SWITCH
NOTE 8
G
(E) GAS RISER METER
NOTE 7
(N) NEMA 3R LOCKABLE WIREWAY
SBJ APN SBJ JDL JDL
03 ELECTRICAL EQUIPMENT ELEVATION VIEW
NOT TO SCALE
(N) INVERTER
(N) INVERTER DISCONNECT SWITCH
(N) GROUNDING TRANSFORMER
NOTE 6
(N) PV EFFECTIVE GROUNDING AC PANEL
(N) METERING AND SURGE PROTECTION CABINET
(N) TRANSFORMER
(N) PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH
SBJ APN SBJ JDL JDL
02 ELECTRICAL EQUIPMENT ELEVATION VIEW
NOT TO SCALE
NOTE 9
13-MAY-2021
06/08/21
L1L2L3G
G
N
(N) MODULESPM
IN
STRING
IN
STRING
OPT
(N) DC OPTIMIZERS
INV1
(N) INVERTER
01 01
37 34
LEGEND
(N) -NEW EQUIPMENT
(E) -EXISTING EQUIPMENT
NOTES:
1. THIS CABLE SIZE AND INSTALLATION ALSO APPLIES TO
THE CABLE INTERCONNECTING MODULES IN THE SAME
STRING WHERE IT IS NOT PROTECTED UNDERNEATH THE PV
ARRAY. THE CONDUIT SIZE IS CALCULATED BASED ON THE
MAXIMUM SET OF STRINGS ROUTED TO A SINGLE INVERTER.
2. AC SURGE PROTECTOR (SP1) AND OWNER REVENUE
GRADE METER (RGM) SHOWN ON THE THREE LINE DIAGRAM
ARE INSTALLED IN PNL2. REFER TO SE20D FOR TYPICAL
WIRING DIAGRAM DETAILS.
3. SUBCONTRACTOR SHALL PURCHASE AND INSTALL
LOCKABLE NEMA 3R WIREWAY BELOW METER BASE AND
INTERCONNECT USING POLARIS CONNECTORS OR
ENGINEER APPROVED EQUIVALENT.
4. REFER TO ELECTRICAL DETAILS DRAWING SE10 FOR THE
COMMUNICATION DETAIL.
5. NEW PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT
SWITCH TO BE LOCATED CLOSE TO EXISTING METER PER
UTILITY REQUIREMENTS.
6. SUBCONTRACTOR SHALL USE LOCKS PROVIDED BY
DISTRIBUTOR TO LOCK THE PV EFFECTIVE GROUNDING AC
PANEL PANEL AND METERING AND SURGE PROTECTION
CABINET INVERTER FUSED DISCONNECT SWITCH, PV
SYSTEM UTILITY DISCONNECT SWITCH, AND NEMA 3R
LOCKABLE WIREWAY.
7. SUBCONTRACTOR SHALL INSTALL A SEPARATELY
DERIVED GROUND ON 480/277V SIDE OF THE TRANSFORMER
AND ENSURE THAT THE NEUTRAL IS GROUNDED ON ONLY
ONE SIDE OF THE TRANSFORMER.
8. REFER TO SE20D FOR WIRING DIAGRAM DETAILS.
02
G
(N) PHOTOVOLTAIC SYSTEM
UTILITY DISCONNECT SWITCH
NOTE 5 & 7 SW1
F1
RGM
(N) OWNER REVENUE GRADE METER
NOTES 2, 4 & 6
(10 FEET OR LESS)
OUTSIDE
INSIDE
06
F1-R
CB-SP
G
N
(E) LOADS
(E) ELECTRICAL SERVICE PANEL
208/120V, 3 PHASE
MAIN BUS: 225A
MAIN BREAKER: 225A
(E) GROUNDING
ELECTRODE
L1
L2L3
L2
TO UTILITY
GRID
(E) MAIN
AWG GEC TIED TO BLDG/SITE
GROUNDING ELECTRODE SYSTEM
6 S/NG L1N L2 L3
05
PNL1
CB1
CB2
(N) PV EFFECTIVE
GROUNDING AC PANEL
NOTE 6
(N) AC SURGE PROTECTOR
NOTE 2
SP1
N
CB3
07
(N) GROUNDING TRANSFORMER
GTR1
04
G
(N) INVERTER FUSED
DISCONNECT SWITCH
SW2
F2
CB-RGM
03N
NOTE 8
GROUND FAULT
RELAY
15A
30A
CB4
15A
NOTE 8
AUX CONTACT/RELAY
POWER
CB520A
PNL2 THERMOSTAT
AND HEATER
NOTE 8
30A
150A
150A
NOTE 2
(E) CT RATED
BI-DIRECTIONAL
UTILITY METER
(E) COMBINATION
CT ENCLOSURE
(N) ( KVA) 480/277V - 208/120V
TRANSFORMER
TR1
30
AWG GEC TIED TO NEW
GROUND ROD
NOTE 7
6 N
NOTE 3
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 20/OCT/20 ISSUED FOR PERMITTING
1 18/FEB/21 ISSUED FOR PERMITTING
2 13/MAY/21 ISSUED FOR PERMITTING - REVISED PER AHJ COMMENTS 02/14/2017 04:16 PM
20/OCT/20
DESIGNER
2R IN-512459-E20
J.P. MORGAN CHASE
10495 N MICHIGAN RD, CARMEL, IN 46032-7939
THREE LINE DIAGRAM AND BILL OF MATERIALS
CONDITIONS OF USE CONDUCTOR EGC CONDUIT CIRCUIT INFORMATION
CIRCUIT
ID DESCRIPTION
NUMBER OF TYPICAL
CIRCUITS
INSULATION
TEMP. RATING
RACEWAY
LOCATION
MODIFIED
AMBIENT
TEMPERATURE
# CURRENT
CARRYING
CONDUCTORS
CONDUIT FILL
DERATE
FACTOR
TEMPERATURE
DERATE
FACTOR MINIMUM SPECIFICATION MINIMUM SPECIFICATION MIN SIZE
# OF
CONDUCTORS # OF EGC
CONDUIT FILL
%
CONDUCTOR
AMPACITY
CONDUCTOR
DERATED
AMPACITY
CONT.
CURRENT
MAXIMUM
CURRENT OCPD
ESTIMATED
CIRCUIT LENGTH
% VOLTAGE
DROP
% AVERAGE
LOSSES
01 STRING TO INVERTER (NOTE 1) 2 90 °C > 0.5" & < 3.5" 54 °C 2 0.8 0.76 8 AWG, COPPER, PV WIRE 10 AWG, COPPER, RHW-2 1", EMT 4 1 39% 55 A 33 A 18.0A 22.5A 25 310 FT 0.91% 0.91%
02 20KW INVERTER TO INVERTER DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 10 AWG, COPPER, THWN-2 10 AWG, COPPER, THWN-2 0.75", EMT 4 1 20% 40 A 38 A 24.0A 30.0A 30 10 FT 0.10% 0.10%
03 INVERTER DS TO TRANSFORMER 1 90 °C UNDER ROOF 32 °C 3 1 0.96 10 AWG, COPPER, THWN-2 8 AWG, COPPER, THWN-2 0.75", EMT 4 1 23% 40 A 38 A 24.0A 30.0A 30 10 FT 0.10% 0.10%
04
TRANSFORMER TO PV EFFECTIVE GND
PNL 1 90 °C UNDER ROOF 32 °C 3 1 0.96 1/0 AWG, COPPER, THWN-2 6 AWG, COPPER, THWN-2 1.5", EMT 3 1 30% 170 A 163 A 55.4A 69.2A 150 10 FT 0.06% 0.06%
05 PV EFFECTIVE GND PNL TO UTILITY DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 4 AWG, COPPER, THWN-2 8 AWG, COPPER, THWN-2 1.25", EMT 4 1 24% 95 A 91 A 55.4A 69.2A 70 20 FT 0.29% 0.29%
06 UTILITY DS TO POI 1 90 °C UNDER ROOF 32 °C 3 1 0.96 4 AWG, COPPER, THWN-2 NA 1.25", RMC 4 0 22% 95 A 91 A 55.4A 69.2A 70 10 FT 0.14% 0.14%
07 EFFECTIVE GND PNL TO GND XFMR 1 90 °C UNDER ROOF 32 °C 3 1 0.96 10 AWG, COPPER, THWN-2 10 AWG, COPPER, THWN-2 0.75" EMT 4 1 20% 40 A 38 A 0 A 10 A 15 10 FT 0.00``% 0.00%
TOTAL 1.68% 1.68%
SYSTEM INFORMATION DC WIRING LOSSES AT STC
STRING
INPUTS
MODULES IN
SERIES
DC POWER
(STC)
TOTAL DC
POWER (STC)
INVERTER
AC POWER ILR
INVERTER
OUTPUT
CURRENT
ESTIMATED
CIRCUIT
LENGTH
% VOLTAGE
DROP % STC LOSS
INVERTER-1 STRING 1-1 37 13,875 W 26,625 W 20,000 W 1.33 24.0A 327 1.00% 1.00%
STRING 1-2 34 12,750 W 292 0.82% 0.82%
STRING 1-3 NA NA NA NA NA
WEIGHTED AVERAGE 0.91% 0.91%
DESIGN PARAMETERS
ASHRAE EXTREME LOW -23.8 °C
ASHRAE 2% HIGH 32.4 °C
SERVICE VOLTAGE 208V, 3Ф
UTILITY IPL
ELECTRICAL CODE NEC 2008
SYSTEM SUMMARY
TOTAL DC POWER 26,625 W
TOTAL AC POWER 20,000 W
WEIGHTED ILR 1.33
INVERTER OUTPUT RATED VOLTAGE 480 V
MAX AC CURRENT (480 V) 24.0A
TRANSFORMATION VOLTAGE 208 V
MAX AC CURRENT (208 V) 55.4A
01 THREE LINE DIAGRAM
NOT TO SCALE
SBJ SBJ APN
APN
SBJ SBJ JDL JASON D. LEIMBACK
11100106
INDIANA
JDL
20/OCT/20
MODULE
MAKE
MISSION
SOLAR
MODEL MSE375SQ9S
POWER OUTPUT 375 W
SHORT CIRCUIT Isc 9.83 A
OPEN CIRCUIT VOLTAGE Voc 48.16 V
RATED CURRENT Imp 9.43 A
RATED VOLTAGE Vmp 39.76 V
TEMPERATURE COEFFICIENT OF Voc -0.28%/C
TEMPERATURE COEFFICIENT OF Isc 0.046%/C
DISTRIBUTOR BILL OF MATERIAL
REF CATEGORY MAKE MODEL QTY UNIT DESCRIPTION
PM MODULE MISSION SOLAR MSE375SQ9S 71 EA 375WP, 72 CELL SOLAR MODULE (PROVIDED BY JPMC)
OPT DC OPTIMIZER SOLAREDGE P850 36 EA SOLAREDGE POWER OPTIMIZER
INV1 20KW INVERTER SOLAREDGE SE20KUS 1 EA
UTILITY INTERACTIVE DC-TO-AC INVERTER: 3-PHASE, 4-WIRE,
480/277VAC, NEMA 3R, NEC 2014 and 2017 RAPID
SHUTDOWN COMPLIANT
CELL1 CELLULAR CDMA KIT SOLAREDGE SE-CELL-B-R05-S-S4 1 EA CDMA MODEM W/SIM, INV≤33.3KVA, 5YRS, HB 15MIN
PNL2
METERING AND SURGE
PROTECTION CABINET VARIES DETAIL 01 1 EA REFER TO DRAWING SE20D FOR CABINET DESIGN AND BOM
TR1 TRANSFORMER HPS 226426 1 EA
TRANSFORMER 30kVA, 480/277 WYE-GND/208VAC DELTA,
NEMA 3R
SW1 PV SYSTEM DISCONNECT EATON DG324NRK 1 EA
240VAC, 200A, 3 POLE GENERAL-DUTY,FUSIBLE,
SINGLE-THROW DISCONNECT SWITCH, NEMA 3R
F1 PV SYSTEM DISCONNECT FUSE BUSSMANN FRN-R-70 3 EA FUSE, 70A, 250VAC, SCCR 200 kA
PNL1
PV EFFECTIVE GROUNDING AC
PANEL EATON DETAIL 01-Q 1 EA REFER TO DRAWING SE23 FOR PANEL DESIGN AND BOM
F1-R FUSE REDUCER BUSSMANN 2621-R 3 EA
250V CLASS R FUSE REDUCER 65 TO 100A FOR 200A
DISCONNECT
GTR1 GROUNDING TRANSFORMER HPS TBD 1 EA
ZIG-ZAG GROUNDING TRANSFORMER, 30A CONTINUOUS
NEUTRAL, NEMA 3R, 150:5 NEUTRAL CURRENT
TRANSFORMER
SW2 INVERTER DISCONNECT EATON DH361NRK 1 EA
600VAC, 30A, HEAVY-DUTY,FUSIBLE, SINGLE-THROW
DISCONNECT
F2 INVERTER DISCONNECT FUSE BUSSMANN FRS-R-30 3 EA FUSE, 30A, 600VAC, SCCR, 200kA
INVERTER
MAKE SOLAREDGE
MODEL SE20KUS
MAXIMUM AC POWER OUTPUT 20,000 W
AC RATED VOLTAGE 480Y/277 V
MAX CONTINUOUS OUTPUT CURRENT 24.0 A
RATED INPUT VOLTAGE 840 V
MAXIMUM INPUT CURRENT 26.5 A
MAXIMUM SHORT CIRCUIT CURRENT 45.0 A
MAXIMUM INPUT VOLTAGE 980 V
TRANSFORMER-LESS, UNGROUNDED YES
OPTIMIZER
MAKE SOLAR EDGE
MODEL P850
RATED INPUT DC POWER 850 W
MAXIMUM SYSTEM VOLTAGE 1000 V
MAXIMUM OUTPUT CURRENT 18.0 A
MAXIMUM OUTPUT VOLTAGE 85 V
MAXIMUM INPUT VOLTAGE 120 V
MAXIMUM SHORT CIRCUIT CURRENT 12.5 A
MINIMUM MODULES IN SERIES 27
MAXIMUM MODULES IN SERIES 40
(N) NEMA 3R LOCKABLE WIREWAY
SBJ APN SBJ JDL JDL
SBJ APN SBJ JDL JDL
13-MAY-2021
06/08/21
INV1
(N) INVERTER
LEGEND
(N) - NEW EQUIPMENT
(E) - EXISTING EQUIPMENT
02
01
PHOTOVOLTAIC
STRINGS
PM
OPT
20 12 9
# REFER TO E30 FOR PLACARD LABELING
7 5
NOTES:
1. THIS CABLE SIZE AND INSTALLATION ALSO APPLIES TO
THE CABLE INTERCONNECTING MODULES IN THE SAME
STRING WHERE IT IS NOT PROTECTED UNDERNEATH THE PV
ARRAY. THE CONDUIT SIZE IS CALCULATED BASED ON THE
MAXIMUM SET OF STRINGS ROUTED TO A SINGLE INVERTER.
2. AC SURGE PROTECTOR (SP1) AND OWNER REVENUE
GRADE METER (RGM) SHOWN ON THE THREE LINE DIAGRAM
ARE INSTALLED IN PNL2. REFER TO SE20D FOR TYPICAL
WIRING DIAGRAM DETAILS.
3. SUBCONTRACTOR SHALL PURCHASE AND INSTALL
LOCKABLE NEMA 3R WIREWAY BELOW METER BASE AND
INTERCONNECT USING POLARIS CONNECTORS OR
ENGINEER APPROVED EQUIVALENT.
4. REFER TO ELECTRICAL DETAILS DRAWING SE10 FOR THE
COMMUNICATION DETAIL.
5. NEW PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT
SWITCH TO BE LOCATED CLOSE TO EXISTING METER PER
UTILITY REQUIREMENTS.
6. SUBCONTRACTOR SHALL USE LOCKS PROVIDED BY
DISTRIBUTOR TO LOCK THE PV EFFECTIVE GROUNDING AC
PANEL PANEL AND METERING AND SURGE PROTECTION
CABINET INVERTER FUSED DISCONNECT SWITCH, PV
SYSTEM UTILITY DISCONNECT SWITCH, AND NEMA 3R
LOCKABLE WIREWAY.
7. SUBCONTRACTOR SHALL INSTALL A SEPARATELY
DERIVED GROUND ON 480/277V SIDE OF THE TRANSFORMER
AND ENSURE THAT THE NEUTRAL IS GROUNDED ON ONLY
ONE SIDE OF THE TRANSFORMER.
8. REFER TO SE20D FOR WIRING DIAGRAM DETAILS.
(N) ( KVA)
480/277V - 208/120V
TRANSFORMER TR1
30
05
(N) PHOTOVOLTAIC SYSTEM
UTILITY DISCONNECT SWITCH
SW1
F1
RGM
(N) OWNER REVENUE
GRADE METER
06
78 6 117 11
F1-R
2
04
CB1
(N) AC SURGE
PROTECTOR
SP1
(N) PV EFFECTIVE GROUNDING
AC PANEL
PNL1 22
CB2
6 3 CB-SP2
07
CB3
(N) GROUNDING TRANSFORMER
GTR1
(E) MAIN
(E) ELECTRICAL SERVICE PANEL
208/120V, 3 PHASE
MAIN BUS: 225A
MAIN BREAKER: 225A
TO UTILITY
GRID15 4 3
13
(E) LOADS
03
SW2
F2
2 6 21 (N) INVERTER DISCONNECT
GROUND FAULT RELAY
N
AUX CONTACT/RELAY
POWER
PNL2 THERMOSTAT
AND HEATER
15A CB4
20A CB530A
15A150A
150A CB-RGM 30A
(E) CT RATED
BI-DIRECTIONAL
UTILITY METER
(E) COMBINATION
CT ENCLOSURE15 23
23
(10 FEET OR LESS)
(N) NEMA 3R LOCKABLE WIREWAY
24
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 20/OCT/20 ISSUED FOR PERMITTING
1 18/FEB/21 ISSUED FOR PERMITTING
2 13/MAY/21 ISSUED FOR PERMITTING - REVISED PER AHJ COMMENTS 02/14/2017 04:16 PM
20/OCT/20
DESIGNER
2R IN-512459-E21
J.P. MORGAN CHASE
10495 N MICHIGAN RD, CARMEL, IN 46032-7939
ONE LINE DIAGRAM
01 ONE LINE DIAGRAM
NOT TO SCALE
SBJ SBJ APN
APN
SBJ SBJ JDL JASON D. LEIMBACK
11100106
INDIANA
JDL
20/OCT/20
SYSTEM INFORMATION DC WIRING LOSSES AT STC
STRING
INPUTS
MODULES IN
SERIES
DC POWER
(STC)
TOTAL DC
POWER (STC)
INVERTER
AC POWER ILR
INVERTER
OUTPUT
CURRENT
ESTIMATED
CIRCUIT
LENGTH
% VOLTAGE
DROP % STC LOSS
INVERTER-1 STRING 1-1 37 13,875 W 26,625 W 20,000 W 1.33 24.0A 327 1.00% 1.00%
STRING 1-2 34 12,750 W 292 0.82% 0.82%
STRING 1-3 NA NA NA NA NA
WEIGHTED AVERAGE 0.91% 0.91%
DESIGN PARAMETERS
ASHRAE EXTREME LOW -23.8 °C
ASHRAE 2% HIGH 32.4 °C
SERVICE VOLTAGE 208V, 3Ф
UTILITY IPL
ELECTRICAL CODE NEC 2008
SYSTEM SUMMARY
TOTAL DC POWER 26,625 W
TOTAL AC POWER 20,000 W
WEIGHTED ILR 1.33
INVERTER OUTPUT RATED VOLTAGE 480 V
MAX AC CURRENT (480 V) 24.0A
TRANSFORMATION VOLTAGE 208 V
MAX AC CURRENT (208 V) 55.4A
MODULE
MAKE
MISSION
SOLAR
MODEL MSE375SQ9S
POWER OUTPUT 375 W
SHORT CIRCUIT Isc 9.83 A
OPEN CIRCUIT VOLTAGE Voc 48.16 V
RATED CURRENT Imp 9.43 A
RATED VOLTAGE Vmp 39.76 V
TEMPERATURE COEFFICIENT OF Voc -0.28%/C
TEMPERATURE COEFFICIENT OF Isc 0.046%/C
INVERTER
MAKE SOLAREDGE
MODEL SE20KUS
MAXIMUM AC POWER OUTPUT 20,000 W
AC RATED VOLTAGE 480Y/277 V
MAX CONTINUOUS OUTPUT CURRENT 24.0 A
RATED INPUT VOLTAGE 840 V
MAXIMUM INPUT CURRENT 26.5 A
MAXIMUM SHORT CIRCUIT CURRENT 45.0 A
MAXIMUM INPUT VOLTAGE 980 V
TRANSFORMER-LESS, UNGROUNDED YES
OPTIMIZER
MAKE SOLAR EDGE
MODEL P850
RATED INPUT DC POWER 850 W
MAXIMUM SYSTEM VOLTAGE 1000 V
MAXIMUM OUTPUT CURRENT 18.0 A
MAXIMUM OUTPUT VOLTAGE 85 V
MAXIMUM INPUT VOLTAGE 120 V
MAXIMUM SHORT CIRCUIT CURRENT 12.5 A
MINIMUM MODULES IN SERIES 27
MAXIMUM MODULES IN SERIES 40
DISTRIBUTOR BILL OF MATERIAL
REF CATEGORY MAKE MODEL QTY UNIT DESCRIPTION
PM MODULE MISSION SOLAR MSE375SQ9S 71 EA 375WP, 72 CELL SOLAR MODULE (PROVIDED BY JPMC)
OPT DC OPTIMIZER SOLAREDGE P850 36 EA SOLAREDGE POWER OPTIMIZER
INV1 20KW INVERTER SOLAREDGE SE20KUS 1 EA
UTILITY INTERACTIVE DC-TO-AC INVERTER: 3-PHASE, 4-WIRE,
480/277VAC, NEMA 3R, NEC 2014 and 2017 RAPID
SHUTDOWN COMPLIANT
CELL1 CELLULAR CDMA KIT SOLAREDGE SE-CELL-B-R05-S-S4 1 EA CDMA MODEM W/SIM, INV≤33.3KVA, 5YRS, HB 15MIN
PNL2
METERING AND SURGE
PROTECTION CABINET VARIES DETAIL 01 1 EA REFER TO DRAWING SE20D FOR CABINET DESIGN AND BOM
TR1 TRANSFORMER HPS 226426 1 EA
TRANSFORMER 30kVA, 480/277 WYE-GND/208VAC DELTA,
NEMA 3R
SW1 PV SYSTEM DISCONNECT EATON DG324NRK 1 EA
240VAC, 200A, 3 POLE GENERAL-DUTY,FUSIBLE,
SINGLE-THROW DISCONNECT SWITCH, NEMA 3R
F1 PV SYSTEM DISCONNECT FUSE BUSSMANN FRN-R-70 3 EA FUSE, 70A, 250VAC, SCCR 200 kA
PNL1
PV EFFECTIVE GROUNDING AC
PANEL EATON DETAIL 01-Q 1 EA REFER TO DRAWING SE23 FOR PANEL DESIGN AND BOM
F1-R FUSE REDUCER BUSSMANN 2621-R 3 EA
250V CLASS R FUSE REDUCER 65 TO 100A FOR 200A
DISCONNECT
GTR1 GROUNDING TRANSFORMER HPS TBD 1 EA
ZIG-ZAG GROUNDING TRANSFORMER, 30A CONTINUOUS
NEUTRAL, NEMA 3R, 150:5 NEUTRAL CURRENT
TRANSFORMER
SW2 INVERTER DISCONNECT EATON DH361NRK 1 EA
600VAC, 30A, HEAVY-DUTY,FUSIBLE, SINGLE-THROW
DISCONNECT
F2 INVERTER DISCONNECT FUSE BUSSMANN FRS-R-30 3 EA FUSE, 30A, 600VAC, SCCR, 200kA
CONDITIONS OF USE CONDUCTOR EGC CONDUIT CIRCUIT INFORMATION
CIRCUIT
ID DESCRIPTION
NUMBER OF TYPICAL
CIRCUITS
INSULATION
TEMP. RATING
RACEWAY
LOCATION
MODIFIED
AMBIENT
TEMPERATURE
# CURRENT
CARRYING
CONDUCTORS
CONDUIT FILL
DERATE
FACTOR
TEMPERATURE
DERATE
FACTOR MINIMUM SPECIFICATION MINIMUM SPECIFICATION MIN SIZE
# OF
CONDUCTORS # OF EGC
CONDUIT FILL
%
CONDUCTOR
AMPACITY
CONDUCTOR
DERATED
AMPACITY
CONT.
CURRENT
MAXIMUM
CURRENT OCPD
ESTIMATED
CIRCUIT LENGTH
% VOLTAGE
DROP
% AVERAGE
LOSSES
01 STRING TO INVERTER (NOTE 1) 2 90 °C > 0.5" & < 3.5" 54 °C 2 0.8 0.76 8 AWG, COPPER, PV WIRE 10 AWG, COPPER, RHW-2 1", EMT 4 1 39% 55 A 33 A 18.0A 22.5A 25 310 FT 0.91% 0.91%
02 20KW INVERTER TO INVERTER DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 10 AWG, COPPER, THWN-2 10 AWG, COPPER, THWN-2 0.75", EMT 4 1 20% 40 A 38 A 24.0A 30.0A 30 10 FT 0.10% 0.10%
03 INVERTER DS TO TRANSFORMER 1 90 °C UNDER ROOF 32 °C 3 1 0.96 10 AWG, COPPER, THWN-2 8 AWG, COPPER, THWN-2 0.75", EMT 4 1 23% 40 A 38 A 24.0A 30.0A 30 10 FT 0.10% 0.10%
04
TRANSFORMER TO PV EFFECTIVE GND
PNL 1 90 °C UNDER ROOF 32 °C 3 1 0.96 1/0 AWG, COPPER, THWN-2 6 AWG, COPPER, THWN-2 1.5", EMT 3 1 30% 170 A 163 A 55.4A 69.2A 150 10 FT 0.06% 0.06%
05 PV EFFECTIVE GND PNL TO UTILITY DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 4 AWG, COPPER, THWN-2 8 AWG, COPPER, THWN-2 1.25", EMT 4 1 24% 95 A 91 A 55.4A 69.2A 70 20 FT 0.29% 0.29%
06 UTILITY DS TO POI 1 90 °C UNDER ROOF 32 °C 3 1 0.96 4 AWG, COPPER, THWN-2 NA 1.25", RMC 4 0 22% 95 A 91 A 55.4A 69.2A 70 10 FT 0.14% 0.14%
07 EFFECTIVE GND PNL TO GND XFMR 1 90 °C UNDER ROOF 32 °C 3 1 0.96 10 AWG, COPPER, THWN-2 10 AWG, COPPER, THWN-2 0.75" EMT 4 1 20% 40 A 38 A 0 A 10 A 15 10 FT 0.00``% 0.00%
TOTAL 1.68% 1.68%
SBJ APN SBJ JDL JDL
SBJ APN SBJ JDL JDL
13-MAY-2021
06/08/21
SW2
T
PNL2
GTR1
PNL1
INV1
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 20/OCT/20 ISSUED FOR PERMITTING
1 18/FEB/21 ISSUED FOR PERMITTING
2 13/MAY/21 ISSUED FOR PERMITTING - REVISED PER AHJ COMMENTS 02/14/2017 04:16 PM
20/OCT/20
DESIGNER
2R
J.P. MORGAN CHASE
10495 N MICHIGAN RD, CARMEL, IN 46032-7939
PLACARDS
SERVICE DISCONNECTING
MEANS
PV ARRAY
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
IN-512459-E30
PHOTOVOLTAIC SYSTEM
UTILITY DISCONNECT
SWITCH
SBJ SBJ APN
APN
SBJ SBJ JDL JASON D. LEIMBACK
11100106
INDIANA
JDL
20/OCT/20
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE
PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10
SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS [NEC 690.4(D)]
AT THE SERVICE ENTRANCE (ELECTRICAL SERVICE PANEL) AND
PHOTOVOLTAIC SYSTEM DISCONNECT SWITCH
OPERATING DC CURRENT: 36 A
OPERATING DC VOLTAGE: 840 V
MAX SHORT CURRENT: 45 A
MAX VOLTAGE: 980 V
AT EACH 20 KW INVERTER DC DISCONNECTING MEANS
[NEC 690.53]
20
PHOTOVOLTAIC
AC DISCONNECT
AT POINT OF INTERCONNECTION, MARKED AT
DISCONNECTING MEANS
[NEC 690.54]
OPERATING AC CURRENT: 55.4A
OPERATING AC VOLTAGE: 208V, 3Ф
! WARNING !
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
AT EACH JUNCTION, COMBINER, DISCONNECT AND
DEVICE WHERE ENERGIZED UNGROUNDED
CONDUCTORS MAY BE EXPOSED DURING SERVICE
[NEC 690.35(F)]
! WARNING !
ELECTRIC SHOCK HAZARD.
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE UNGROUNDED
AND MAY BE ENERGIZED.
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
PHOTOVOLTAIC
DC DISCONNECT
PHOTOVOLTAIC
SYSTEM UTILITY
DISCONNECT SWITCH
WARNING: PHOTOVOLTAIC
POWER SOURCE
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
INVERTER OUTPUT CONNECTION.
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
PHOTOVOLTAIC SYSTEM METER INTERACTIVE
PHOTOVOLTAIC SYSTEM CONNECTED
AT UTILITY METER
[NEC 690.56(B)]
PLAQUE
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTHEAST SIDE OF THE BUILDING
! WARNING !
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
DC VOLTAGE IS ALWAYS PRESENT WHEN
SOLAR MODULES ARE EXPOSED TO SUNLIGHT
! WARNING !
TURN OFF PHOTOVOLTAIC AC DISCONNECT
PRIOR TO WORKING INSIDE PANEL
AT EACH BREAKER PANEL AND MAIN SERVICE
DISCONNECT.
[NEC 110.27(C)]
! WARNING !
PHOTOVOLTAIC SYSTEM DATA
ACQUISITION SYSTEM
AUTHORIZED PERSONNEL ONLY
THE PV DAS SHALL BE LABELED WITH THE FOLLOWING
INFORMATION
AT EACH AC DEDICATED PHOTOVOLTAIC SYSTEM
COMBINER PANEL AND DISCONNECT.
[NEC 110.16]
! WARNING !
ARC FLASH HAZARD.
APPROPRIATE PPE REQUIRED.
FAILURE TO COMPLY MAY RESULT IN
INJURY OR DEATH.
REFER TO NFPA 70 E.
AT EACH PHOTOVOLTAIC SYSTEM
SERVICE DISCONNECT SWITCH.
! DANGER !
ARC FLASH AND SHOCK HAZARD PRESENT
DO NOT OPEN DOOR WHILE ENERGIZED
INCIDENT ENERGY EXCEEDS MAX PPE PROTECTION
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
PHOTOVOLTAIC
SYSTEM SERVICE
DISCONNECT SWITCH
DEDICATED PHOTOVOLTAIC
SYSTEM COMBINER PANEL DO NOT
ADD LOADS TO THIS PANEL
AT DEDICATED PHOTOVOLTAIC
SYSTEM COMBINER PANEL (IF
APPLICABLE)
NET GENERATION
OUTPUT METER
AT NET GENERATION OUTPUT
METER
AT THE ELECTRICAL SERVICE PANEL
! WARNING !
A GENERATION SOURCE IS CONNECTED TO THE SUPPLY (UTILITY) SIDE OF THE
SERVICE DISCONNECTING MEANS. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES
TO ENSURE THE PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH IS OPENED
PRIOR TO PERFORMING WORK ON THE DEVICE.
1 2 3
5
1716 15 14
13 12 9 10 11
6 7 8
419 18
AT EACH AC DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.17]
AT EACH DC DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.17]
AT PHOTOVOLTAIC SYSTEM SERVICE
DISCONNECT SWITCH [NEC 690.14(C)(2)]
AT PHOTOVOLTAIC SYSTEM UTILITY
DISCONNECT SWITCH [NEC 690.14(C)(2)]
AT EACH DC DISCONNECTING MEANS
[NEC 690.14(C)(2)]
AT EACH DISTRIBUTION EQUIPMENT ADJACENT TO
THE BACK-FED BREAKER FROM THE INVERTER.
[NEC 705.12(D)(7)]
AT POINT OF INTERCONNECTION; LABEL
MUST IDENTIFY PHOTOVOLTAIC SYSTEM
[NEC 705.12(D)(4)]
AT POINT OF INTERCONNECTION; LABEL
MUST IDENTIFY PHOTOVOLTAIC SYSTEM
[NEC 705.12(D)(4)]
AT PHOTOVOLTAIC SYSTEM DISCONNECT SWITCH
[NEC 2014 - 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE [IFC 605.11.1.1].
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS;
SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY
ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.
[NEC 690.31(E)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2008 NATIONAL ELECTRICAL CODE.
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT FOR WHICH THEY ARE INSTALLED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
DEDICATED PV
EFFECTIVE
GROUNDING AC PANEL
AT PV EFFECTIVE GROUNDING AC PANEL
22
PHOTOVOLTAIC
SYSTEM INVERTER
DISCONNECT SWITCH
AT INVERTER DISCONNECT
21
23
24
SBJ APN SBJ JDL JDL
SBJ APN SBJ JDL JDL
13-MAY-2021
06/08/21