HomeMy WebLinkAboutA121 - Reflected Ceiling PlanELNELNELNSNSNSNSNS N
SN SNSNSN SNSN SN SN SNSNS N SNSNREFLECTED
CEILING PLAN
A121
PROVIDE ADDITIONAL COOLING UNIT IN TENANT'S SERVER ROOM.
COORDINATE WITH TENANT AND BUILDING MANAGEMENT AS
REQUIRED.
CONTROL ENTRY 201, OPEN OFFICE 206 AND HUDDLE 218
LIGHTING WITH SWITCH AT THIS LOCATION. PROVIDE MULTIPLE
SWITCHES AS REQUIRED.
PROVIDE NEW CEILING GRID AND TILE AS SHOWN TO MATCH AND
ALIGN WITH EXISTING SUCH THAT NEW AND EXISTING CEILINGS
APPEAR CONTINUOUS.
EXHAUST FAN TO BE CONTROLLED BY THERMOSTAT. COORDINATE
WITH TENANT ON EXACT REQUIREMENTS.
PLAN NOTES
LIGHT SWITCH, 3-WAY
LIGHT SWITCHN
N3 3
EXIT LIGHT FIXTURE
LIGHT FIXTURE, 2'x2', LED,
BUILDING STANDARD
LIGHT FIXTURE, 2'x4', LED,
BUILDING STANDARD
RELOCATED DIFFUSER,
LAY-IN, 4"x 2'
RELOCATED DIFFUSER,
LAY-IN, 2'x2'
CEILING GRID,
SUSPENDED, 2'x4'
NEW OR RELOCATED EXISTING TO REMAIN
EXIT LIGHT FIXTURE
LIGHT SWITCH, 3-WAY
LIGHT SWITCH
CEILING GRID,
SUSPENDED, 2'x4'
DIFFUSER,
LAY-IN, 4"x 2'
DIFFUSER,
LAY-IN, 2'x2'
LIGHT FIXTURE, 2'x2',
FLUORESCENT, PRISMATIC
LIGHT FIXTURE, 2'x4',
FLUORESCENT, PRISMATIC
LEGEND
REFLECTED CEILING PLANAREA NOT IN CONTRACT
AREA OF WORK
DESCRIPTIONDATE
ISSUE
04.01.21 REVIEW SET
04.07.21 PERMIT SET
04.08.21 CONSTRUCTION SET
REVISIONS
DESCRIPTIONMARK DATE DB
04.12.21 JR A121 REV
04.26.21 JR A131 REV
05.10.21 JR REVISIONS
2
3
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700PROJECT NUMBER
DRAWN BYPROJ. MGR PSI SERVICES11590 MERIDIAN CROSSING | SUITE 220CARMEL, IN 46032JRACM
2020.313
2ND FLOOR
N
1
0 2'4' 8' 16'
EMERGENCY LIGHT FIXTURE EMERGENCY LIGHT FIXTURE
MECHANICAL DIFFUSER RELOCATION
A121
1
*REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION
EXISTING VAV BOXES OR
HEAT PUMP AND MAIN SUPPLY
DUCTS TO REMAIN
RELOCATE DIFFUSERS &
FLEXDUCT IF REQUIRED
VAV /
HEAT PUMP
EXHAUST FAN, 2'x2' EXHAUST FAN,
2'x2'
A121
1
1. REUSE EXISTING CEILING GRID UNLESS OTHERWISE NOTED. EXISTING
GRID IS 2x4 AT 8'-3" A.F.F. REPAIR ANY DAMAGED GRID TO MATCH
EXISTING. BASE BID: PROVIDE NEW CEILING TILE UP TO $3,000
ALLOWANCE. PROVIDE SEPARATE PRICE FOR NEW, ARMSTRONG
DUNE REVEAL EDGE CEILING TILE THROUGHOUT.
2. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN
SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI
OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT
IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT
INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1,
CONTRACTOR MUST NOTIFY SDI.
4. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS; PROVIDE COMBO
UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH A
ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE
LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF
INCLUDED AREA IS DETECTED. PROVIDE CEILING MOUNTED
OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED.
5. NEW DEVICES AND FACE PLATES TO MATCH EXISTING. WHERE
POSSIBLE, GANG MULTIPLE SWITCHES TO ACCOMMODATE
MULTI-SWITCH PLATE WHEN SWITCHES ARE SHOWN ADJACENT ON
PLAN.
6. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS.¬ ALL ELECTRICAL WORK IS LIMITED TO
ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND
LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING
ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS
TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED
SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH
ALL APPLICABLE CODES.
GENERAL NOTES
1. MECHANICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS.¬NO NEW MAIN MECHANICAL
APPLIANCES OR MAIN EQUIPMENT ARE BEING PROVIDED.¬ ALL
MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND
FLEX DUCT PER NEW WALL LAYOUT. IF IN GOOD CONDITION, EXISTING
H.V.A.C. DIFFUSERS SALVAGED FROM DECONSTRUCTION MAY BE
SUBSTITUTED FOR NEW. NO NEW HARD DUCTWORK OR EQUIPMENT IS
BEING ADDED;¬ MECHANICAL CONTRACTOR IS TO NOTIFY
APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT
ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH THE
INDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES.
MECHANICAL NOTES
1
3