HomeMy WebLinkAboutS001 - 100_BID AND PERMIT (08-27-20)GENERAL STRUCTURAL NOTES DESIGN CODES: 2012 INTERNATIONAL BUILDING CODE ASCE 7-10 MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER STRUCTURES. DESIGN LOADS: ROOF DEAD LOAD UNO GROUND SNOW LOAD (Pg) Ce = 1.0 Ct = 1.0 I = 1.0 ROOF SNOW LOAD (PLUS SNOW DRIFTING) INCLUDES 5 PSF RAIN ON SNOW SURCHARGE FLOOR LIVE LOAD ULTIMATE DESIGN WIND SPEED NOMINAL DESIGN WIND SPEED RISK CATEGORY EXPOSURE CATEGORY INTERNAL PRESSURE COEFFICIENT END ZONE WIDTH (a) NOTES: IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DESIGN AND PROVIDE ADEQUATE TEMPORARY SHORING AND LATERAL BRACING FOR ALL STRUCTURAL ELEMENTS INCLUDING WALLS, COLUMNS, BEAMS, LINTELS, ETC. FOR WIND, SOIL AND CONSTRUCTION LATERAL AND GRAVITY LOADS. THE BRACING MUST REMAIN IN PLACE UNTIL PERMANENT STRUCTURAL SUPPORTS, INCLUDING ROOF AND FLOOR DIAPHRAGMS ARE INSTALLED AND HAVE REACHED THEIR ALLOWABLE SERVICE STRESSES. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO ENSURE THAT CONSTRUCTION CONFORMS TO THE LATEST OSHA SAFETY REQUIREMENTS. NOTIFY THE ARCHITECT AND ENGINEER IMMEDIATELY IF ANY REVISIONS ARE REQUIRED TO THE DRAWINGS DUE TO OSHA SAFETY REQUIREMENTS. GEOTECHNICAL ENGINEER SHALL FIELD VERIFY SOIL BEARING CAPACITY. NOTIFY ARCHITECT AND ENGINEER IF ANY DISCREPANCIES ARE FOUND. THIS PROJECT IS NOT DESIGNED FOR FUTURE CONSTRUCTION. ALLOWABLE SOIL BEARING PRESSURE MODULUS OF SUBGRADE REACTION 15 PSF ----------------------------------- 20 PSF ----------------------------------- 25 PSF ----------------------------------- 125 PSF --------------------------------- 115 MPH --------------------------------- 90 MPH----------------------------------- II -------------------------------------------- B ------------------------------------------- ± 0.18 ------------------------------------- 8 FT --------------------------------------- COMPONENT AND CLADDING ULTIMATE WIND PRESSURES (PSF) INTERIOR ZONE END ZONE 25.9 31.2 24.5 28.2 23.3 25.9 20.8 20.8 20 FT² ZONE EFFECTIVE AREA SEISMIC IMPORTANCE FACTOR (I) RISK CATEGORY SITE CLASS SEISMIC DESIGN CATEGORY MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETER (SS) MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETER (S1) DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETER (SDS) DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETER (SD1) 1.0 ----------------------------------------- II -------------------------------------------- D ------------------------------------------- B ------------------------------------------- 0.147g ----------------------------------- 0.082g ----------------------------------- 0.157g------------------------------------ 0.131g------------------------------------ 50 FT² 100 FT² 500 FT² 1500 PSF-------------------------------- 125 PCI ---------------------------------- 1. 2. 3. 4. SUBMITTALS: ALL SUBMITTED STRUCTURAL SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL CONFORMANCE WITH THE INFORMATION GIVEN AND DESIGN CONCEPTS EXPRESSED IN THE CONTRACT DOCUMENTS. REVIEW OF SUCH SUBMITTALS IS NOT CONDUCTED FOR THE PURPOSE OF DETERMINING THE ACCURACY AND COMPLETENESS OF DETAILS SUCH AS DIMENSIONS AND QUANTITIES AS REQUIRED BY THE CONTRACT DOCUMENTS. DEFERRED SUBMITTALS: THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL AS DEFERRED SUBMITTALS PER IBC SECTION 107.3.4.1: FOR ALL DEFERRED STRUCTURAL SUBMITTALS, INCLUDE CALCULATIONS PREPARED AND CERTIFIED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL SHOP DRAWING REQUIREMENTS. A. METAL STAIRS, LADDERS AND RAILINGS B. METAL BALCONIES, CANOPIES AND SUNSHADES SOILS AND FOUNDATIONS: FOUNDATIONS, RETAINING AND BASEMENT WALLS, SLABS ON GRADE AND OTHER ITEMS RELATED TO THE SOILS ARE DESIGNED AND SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE RECOMMENDATIONS OF ALT & WITZIG ENGINEERING, INC GEOTECHNICAL EVALUATION REPORT 20IN0285 DATED JUNE 17, 2020 AND REVISED JUNE 22, 2020. MINIMUM DEPTH FROM EXTERIOR GRADE TO BOTTOM OF BUILDING PERIMETER FOOTINGS SHALL BE 36". ALL FOOTINGS ARE CENTERED UNDER WALLS, PILASTERS AND COLUMNS ABOVE UNO. ALL FOUNDATION WALLS SHALL BE LATERALLY BRACED BEFORE BACKFILLING AND COMPACTING. DO NOT BACKFILL AROUND STEEL COLUMNS UNTIL CORROSION RESISTANT ASPHALTIC COATING HAS BEEN INSTALLED BY THE STRUCTURAL STEEL ERECTOR. COORDINATE ALL UNDERGROUND PIPING OR DUCTWORK LOCATIONS AND ELEVATIONS WITH THE MECHANICAL CONTRACTOR. ADJUST FOOTING ELEVATIONS AND PROVIDE SLEEVES PER WALL FOOTING AT UNDERGROUND LINES DETAIL. FOR PIPING OR DUCTWORK PARALLEL TO FOOTING, BOTTOM OF FOOTING ELEVATION SHOULD BE NO HIGHER THAN THE PIPE OR DUCTWORK INVERT ELEVATION PLUS THE HORIZONTAL DISTANCE BETWEEN EDGE OF FOOTING AND EDGE OF PIPING OR DUCTWORK. CONTRACTOR SHALL NOTIFY ARCHITECT AND ENGINEER FOR APPROVAL OF ANY DEVIATIONS PRIOR TO COMMENCING WORK. 1. 2. 3. 4. 5. 6. DESIGN CODES: IBC CHAPTER 19 & ACI 318-11, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE & ACI DETAILING MANUALS LATEST EDITION. MINIMUM COMPRESSIVE STRENGTH IS 28 DAYS. CAST-IN-PLACE CONCRETE: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. TYPE STRENGTH A ---------- f'c=3000 PSI ------------- B ---------- f'c=4000 PSI -------------- C ---------- f'c=4000 PSI -------------- D ---------- f'c=3000 PSI -------------- E ---------- f'c=4000 PSI -------------- F ---------- f'c=4500 PSI -------------- G ---------- f'c=4000 PSI -------------- H ---------- f'c=4000 PSI -------------- REINFORCING STEEL PROPERTIES: A. DEFORMED BARS - ASTM A615 GRADE 60 UNO. USE ASTM A706 GRADE 60 FOR WELDABLE REBAR. B. WELDED WIRE FABRIC - ASTM A1064. LOCATION MASONRY CORE FILL AND BOND BEAMS W/ 3/8" MAX AGGREGATE SIZE AND 8" TO 11" SLUMP INTERIOR SLABS ON GRADE ≤5" DEEP W/ 3/4" MAX AGGREGATE SIZE AND 3" TO 5" SLUMP INTERIOR SLABS ON GRADE > 5" DEEP W/ 1 1/2" MAX AGGREGATE SIZE AND 3" TO 5" SLUMP FOOTINGS PIERS AND FOUNDATION WALLS EXPOSED EXTERIOR CONCRETE AIR ENTRAINED 6% +/- 1%. MAX WATER/CEMENT RATIO = 0.45. CONCRETE TOPPING OVER STEEL DECK ALL OTHER CONCRETE W/ 3/4" MAX AGGREGATE SIZE ALL REINFORCING SHALL BE DETAILED, FABRICATED AND PLACED IN ACCORDANCE WITH THE LATEST ACI MANUALS. FOR PIERS WITH A CROSS SECTION LARGER THAN 18"x18" AND WITH MORE THAN 4 LONGITUDINAL BARS, ADDITIONAL CROSS TIES (TYPE T9 PER ACI 315) OF SAME SIZE AND SPACING AS MAIN TIES, SHALL BE PROVIDED TO ENSURE THAT ALL NON CORNER BARS ARE LATERALLY SUPPORTED BY THE CORNER OF A TIE. A. SHOP DRAWINGS FOR REINFORCING STEEL AND CONCRETE MIX DESIGNS SHALL BE SUBMITTED FOR APPROVAL. SUBMIT PROPOSED LAYOUT OF SLAB ON GRADE CONTROL/CONSTRUCTION JOINTS FOR APPROVAL. PLACE ALL ITEMS PER APPROVED SHOP DRAWINGS AND APPROVED MIX DESIGNS. PROVIDE ALL ACCESSORIES, CHAIRS, SPACER BARS AND SUPPORTS NECESSARY TO SECURE REINFORCING PER "ACI DETAILING MANUAL" NO OTHER METHODS OR MATERIALS WILL BE ACCEPTABLE. PROVIDE PLASTIC CHAIRS AND SUPPORTS IN ALL AREAS OF EXPOSED CONCRETE. PROVIDE MINIMUM CONCRETE COVER FOR ALL REINFORCING AS FOLLOWS UNO: CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH CONCRETE EXPOSED TO EARTH OR WEATHER: #6 THROUGH #18 BARS #5 BARS AND SMALLER CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: SLABS, WALLS, JOISTS: #14 AND #18 BARS #11 BARS AND SMALLER BEAMS, COLUMNS: PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS A. B. C. -------------------------------- 3" -------------------------------- 2" --------------------------- 1 1/2" --------------------------- 1 1/2" -------------------- 3/4" --------------------------- 1 1/2" PROVIDE CONTINUOUS WALL FOOTING THICKNESS AND BOTTOM REINFORCING AS FOLLOWS (PLACE LONGITUDINAL REINFORCING ABOVE TRANSVERSE REINFORCING): FOOTING WIDTH THICKNESS LONG REINF TRANSV REINF 1'-8" OR LESS 10" (2) #5 ------------- 1'-9" TO 2'-8" 12" (2) #5 ------------- 2'-9" TO 3'-4" 12" (3) #5 #4 @ 12" O.C. 3'-5" TO 4'-0" 12" (4) #5 #6 @ 12" O.C. 4'-1" TO 5'-0" 12" (5) #5 #7 @ 12" O.C. 5'-1" TO 6'-0" 14" (6) #5 #7 @ 12" O.C. PROVIDE 100% VIRGIN POLYPROPYLENE FIBER REINFORCING IN ALL INTERIOR CONCRETE SLABS ON GRADE UNO. (FIBERMESH 300, MASTER FIBER F100, GENESIS FIBER, POLYMESH OR APPROVED EQUAL). DOSAGE RATE TO BE PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE FOOTING DOWELS FOR CONCRETE OR MASONRY WALLS AND COLUMNS. DOWELS SHALL BE SAME SIZE AND SPACING AS WALL AND COLUMN VERTICAL REINFORCING AND SHALL PROJECT FROM FOOTINGS TO PROVIDE LAP SPLICES AS INDICATED BELOW OR IN THE MASONRY NOTES. PROVIDE 90 DEGREE STANDARD HOOK IN COLUMN AND FREE STANDING WALL FOOTING DOWELS UNO. PROVIDE LAP SPLICES FOR CONCRETE REINFORCING AS FOLLOWS: A. TYPICAL LAP SPLICES SHALL BE UNO: #6 BARS AND SMALLER ----------------------- 44 BAR DIAMETERS #7 THROUGH #11 BARS ----------------------- 56 BAR DIAMETERS B. TENSION LAP SPLICES FOR CONCRETE RETAINING WALLS AND BEAMS SHALL BE 1.3 TIMES TYPICAL LAP SPLICES. C. FOR TOP BARS, THE SPLICE LENGTHS SHALL BE INCREASED AN ADDITIONAL 1.3 TIMES THE LENGTHS DETAILED ABOVE. D. THE MINIMUM LAP SPLICE LENGTH FOR ALL SPLICES FOR CONCRETE REINFORCING SHALL BE 24". PROVIDE MINIMUM CONCRETE WALL REINFORCING AS FOLLOWS UNO: WALL THICKNESS VERT REINF HORIZ REINF 6" AND 8" #4 @ 16" O.C. CTRD #4 @ 12" O.C. CTRD 10" #4 @ 16" O.C. EF #4 @ 16" O.C. EF 12" AND 14" #4 @ 12" O.C. EF #4 @ 12" O.C. EF 16" AND 18" #4 @ 12" O.C. EF #5 @ 16" O.C. EF PROVIDE EXTRA REINFORCING ON ALL SIDES OF ALL CONCRETE WALL AND SLAB OPENINGS EQUAL TO ONE HALF THE INTERRUPTED REINFORCING IN EACH DIRECTION, UNO ON THE DRAWINGS. A MINIMUM OF (1) #5 SHALL BE PROVIDED FOR EACH LAYER OF REINFORCEMENT. EXTEND BARS PAST EDGE OF OPENING THE LAP SPLICE NOTED ABOVE. PROVIDE AN ADDITIONAL #4x4'-0" DIAGONAL BAR AT EACH CORNER FOR EACH LAYER OF REINFORCING. HOT WEATHER AND COLD WEATHER CONCRETE PROVISIONS OF ACI 305R-10 AND ACI 306R-16 SHALL BE FOLLOWED. DESIGN CODES: IBC CHAPTER 21 AND ACI 530-11 MSJC-BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES. HOLLOW CONCRETE MASONRY UNITS SHALL BE NORMAL WEIGHT UNITS PER ASTM C90 REQUIREMENTS. F'm=2000 PSI. ALL MORTAR FOR LOAD BEARING WALLS BELOW GRADE SHALL BE TYPE 'M' MORTAR. MORTAR FOR LOAD BEARING WALLS ABOVE GRADE SHALL BE TYPE 'S'. TYPE 'N' MORTAR WILL BE ALLOWED FOR INTERIOR ABOVE GRADE NON-LOAD BEARING PARTITIONS. MORTAR PER ASTM C270. MINIMUM 28 DAY COMPRESSIVE STRENGTH: TYPE 'M'=2500 PSI, TYPE 'S'=1800 PSI, TYPE 'N'=750 PSI. COARSE GROUT PER ASTM C476. MINIMUM 28 DAY COMPRESSIVE STRENGTH=3000 PSI. NO GROUT IS TO BE HAND MIXED ON SITE. MASONRY CEMENT SHALL NOT BE USED IN MORTAR OR GROUT. REINFORCING STEEL: A. DEFORMED BARS: ASTM GRADE 60. B. JOINT REINFORCEMENT: ASTM A82. SUBMIT MORTAR AND GROUT DESIGN MIXES FOR APPROVAL. SUBMIT SHOP DRAWINGS FOR REINFORCING STEEL. PROVIDE MINIMUM 8" FULL DEPTH AND WIDTH BEARING FOR ALL MASONRY LINTELS. WIRE JOINT REINFORCING FOR CONCRETE BLOCK WALLS SHALL BE STANDARD CORROSION RESISTANT 9 GAGE LADDER TYPE (PROVIDE TRI-ROD LADDER FOR MULTI WYTHE WALLS). INSTALL JOINT REINFORCING PER MANUFACTURER'S RECOMMENDATIONS AT A MAXIMUM SPACING 16" O.C. UNO ON DRAWINGS OR PROJECT SPECIFICATIONS. INSTALL MASONRY VERTICAL AND HORIZONTAL REINFORCING PER IBC REQUIREMENTS AND AS FOLLOWS: A. SEE PLANS, DETAILS AND SCHEDULES FOR REQUIRED REINFORCING. B. PROVIDE FULL MORTAR BEDDED FACE SHELLS AND WEBS AROUND ALL GROUTED CELLS FOR BEARING AND TO PREVENT LEAKAGE INTO ADJACENT CELLS. C. PLACE VERTICAL REINFORCING PRIOR TO PLACING GROUT. D. PROVIDE REINFORCEMENT POSITIONERS TO HOLD VERTICAL REINFORCEMENT IN PROPER POSITION AT TOP AND BOTTOM OF ALL LIFTS. LENGTH OF REINFORCING BARS TO BE COORDINATED WITH CONCRETE AND MASONRY CONTRACTORS. E. GROUT ALL CORES CONTAINING REINFORCING SOLID. F. MASONRY WALL CELLS TO BE GROUTED WITH CONCRETE SHALL BE FILLED IN MAXIMUM 4'-0" LIFTS. REMOVAL ALL OVERHANGING OBSTRUCTION AND DEBRIS FROM THE CELLS PRIOR TO GROUTING. G. CONSOLIDATE ALL GROUT BY RODDING OR VIBRATING. H. PROVIDE REINFORCEMENT LAP SPLICES PER TABLES BELOW: J. PROVIDE CORNER BAR WITH 2'-0" + 2'-0" LEGS FOR EACH HORIZONTAL BOND BEAM BAR AT CORNERS AND INTERSECTING WALLS. PROVIDE CONTINUOUS BOND BEAMS WITH (2) #5 CONTINUOUS AT THE TOP OF ALL BEARING AND END WALLS AS FOLLOWS: A. WHEN SINGLE HEIGHT BOND BEAMS ARE USED, MAINTAIN MINIMUM 8" HEIGHT. B. WHERE JOIST BEARING BOND BEAMS, MASONRY LINTELS, ETC. REQUIREMENTS EXCEED 8" HEIGHT. USE 16" HIGH UNITS ONLY WHERE ACCEPTABLE FOR ARCHITECTURAL AND VISUAL REQUIREMENTS. WHERE ARCHITECTURAL AND VISUAL CONDITIONS AND REQUIRE USE OF 8" HIGH UNITS, PLACE 8" HIGH POUR THROUGH UNITS ON TOP 8" HIGH BOND BEAM UNIT. REINFORCE AND POUR THE BUILT UP BOND BEAM AS ONE UNIT. C. WHERE TOP OF BOND BEAM ELEVATIONS ARE NOT AT MASONRY COURSING ELEVATIONS DUE TO JOIST, DECK OR SLAB ELEVATIONS, ROOF SLOPES, ETC., PROVIDE BUILT UP BOND BEAM AS DESCRIBED IN ITEM 'B' ABOVE. STEP BOND BEAMS AS REQUIRED TO MAINTAIN A MINIMUM OF 8" BOND BEAM HEIGHT. CUT OR NOTCH UPPER BOND BEAM UNIT. REINFORCE AND POUR THE BUILT UP BOND BEAM PORTION TO REQUIRED ELEVATIONS. D. LENGTH AND HEIGHT OF ALL BOND BEAMS AND BUILT UP BOND BEAM UNITS SHALL CONFORM TO ALL ARCHITECTURAL AND VISUAL REQUIREMENTS. E. SEE PLANS, SCHEDULES AND DETAILS FOR EMBEDDED ANGLES, PLATES, ANCHOR BOLTS, ETC. CAST IN BOND BEAMS, WALLS, PIERS ETC. PROVIDE CONTINUOUS 8" HIGH x WALL THICKNESS BOND BEAM WITH (2) #5 CONTINUOUS AT ALL MASONRY WALL BRICK LEDGE ELEVATIONS. GROUT SOLID BELOW ALL STEEL BEARINGS A MINIMUM OF FIVE COURSES DOWN FOR 16" LENGTH OF WALL, UNO ON DRAWINGS. ALL STEEL BEAMS SHALL BEAR A MINIMUM OF 8" ON SOLID GROUTED MASONRY UNITS, UNO. INSTALL LINTELS FOR ALL MASONRY WALL OPENINGS AS FOLLOWS, UNO ON PLANS, DETAILS AND SCHEDULES: A. PROVIDE ONE 8" HIGH COURSE LINTEL W/ (2) #5 BOTTOM FOR ALL 2'-0" WIDE OR LESS OPENINGS IN LOAD BEARING MASONRY WALLS AND ALL 4'-0" WIDE OR LESS OPENINGS IN NON-LOAD BEARING MASONRY WALLS. PROVIDE TWO 8" HIGH COURSE LINTEL W/ (2) #5 BOTTOM FOR SPANS UP TO 6'-4" IN NON-LOAD BEARING WALL. B. VERIFY SIZE AND LOCATIONS OF ALL MECHANICAL LOUVERS, DUCTS AND ALL OTHER OPENINGS WITH MECHANICAL CONTRACTOR AND OTHER CONCERNED DISCIPLINES. C. SEE PLANS, SCHEDULES AND DETAILS FOR LINTEL TYPES AND LOCATIONS. CONTACT ARCHITECT FOR LINTEL TYPE AND SIZE FOR ALL REQUIRED OPENINGS GREATER THAN 2'-0' WIDE IN LOAD BEARING WALLS NOT SHOWN ON STRUCTURAL PLANS, DETAILS AND SCHEDULES. MASONRY VERTICAL CONTROL JOINTS: A. COORDINATE JOINTS AND CONSTRUCTION DETAILS WITH ARCHITECT. MAXIMUM JOINT SPACING IS 24'-0". B. LOCATE JOINTS 2'-0" FROM ALL CORNERS AND EDGE OF ALL OPENING EXCEPT AS NOTED PER SECTIONS AND DETAILS. C. FOR LOAD BEARING MASONRY, CONTINUE BOND BEAM REINFORCING AND GROUT THROUGH CONTROL JOINTS. D. FORM CONTROL JOINTS IN BLOCK WITH JAMB BLOCK WITH NEOPRENE INSERTS, OR ROD AND CAULK. CONTRACTOR OPTION: USE STANDARD BLOCK, LINE ONE SIDE WITH BUILDING PAPER AND GROUT SOLID TO FORM KEYWAY. E. PROVIDE CONTROL JOINTS AT INTERSECTIONS OF BEARING AND NON-BEARING WALLS. MASONRY: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. BARS CENTERED IN WALL BAR SIZE 6" CMU 8" CMU 10" CMU & UNDER #4 #5 #6 #7 24" ----- ----- ----- 24" 30" 38" ----- 24" 30" 36" 42" BARS PLACED AT INSIDE OR OUTSIDE FACE OF WALL BAR SIZE 6" CMU 8" CMU 10" CMU & UNDER #4 #5 #6 #7 ----- ----- ----- 24" 30" 57" ----- 24" 30" 36" 42" ----- DESIGN CODES: IBC CHAPTER 22, AISC 360-10, SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS AND AISC 303-10, CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES. STEEL PROPERTIES: A. ASTM A992 (Fy=50 KSI) FOR WIDE FLANGE SHAPES B. ASTM A500 GRADE B (Fy=46 KSI) FOR TUBULAR MEMBERS C. ASTM A36 STEEL (Fy=36 KSI) FOR ALL OTHER MEMBERS UNO D. ASTM F3125 GRADE A325 OR GRADE F1852 UNO FOR CONNECTION BOLTS E. ASTM F1554 GRADE 36 FOR ANCHOR BOLTS UNO F. ASTM A108 FOR HEADED STUDS G. WELDS = AMERICAN WELDING SOCIETY (AWS) E70XX ELECTRODES H. EXPANSION ANCHORS = HILTI KWIK BOLT 3 OR APPROVED EQUAL J. SCREW ANCHORS = SIMPSON TITEN HD OR APPROVED EQUAL K. POWDER ACTUATED FASTENERS (PAF) = HILTI "X-U" OR APPROVED EQUAL PROVIDE 5000 PSI NON-SHRINK GROUT UNDER ALL STEEL BASE AND BEARING PLATES PER THE SECTIONS AND DETAILS. GROUT PLATES PRIOR TO LOADING ROOF MEMBERS WITH PRECAST PLANK OR DECKING MATERIALS. PROVIDE CORROSION RESISTANT ASPHALTIC COATING OR EQUAL AROUND ALL STRUCTURAL STEEL BELOW GRADE. ALL WELDS SHALL BE MADE BY CERTIFIED WELDERS AND IN ACCORDANCE WITH AMERICAN WELDING SOCIETY (AWS) - D1.1 LATEST EDITION. STRUCTURAL STEEL FABRICATOR SHALL FURNISH ALL PLATES AND ANGLES CAST IN CONCRETE AND MASONRY FOR CONNECTING STEEL JOISTS, BEAMS, COLUMNS, DECK, ETC. UNO. SEE APPLICABLE NOTES ON THIS SHEET AND COORDINATE WITH MASONRY AND CONCRETE CONTRACTORS. ALL STEEL BEAMS AND LINTELS TO BEAR A MINIMUM OF 8" UNO. ALL COLUMN BASE AND CAP PLATES TO BE WELDED AROUND ALL SIDES. PRIME PAINT PER AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS SECTION 6.5, UNO ON ANY CONSTRUCTION DOCUMENTS. CLEAN STEEL BUT OMIT PRIMER AT STEEL MEMBERS RECEIVING SPRAY FIREPROOFING. COORDINATE W/ ARCH DRAWINGS. ALL EXTERIOR LOOSE LINTELS AND BOTTOM PLATE LINTELS SHALL BE HOT-DIP GALVANIZED. STRUCTURAL STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL. MISCELLANEOUS STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL, INCLUDING STRUCTURAL CALCULATIONS FOR STAIRS, LADDERS, RAILINGS AND THEIR CONNECTIONS CERTIFIED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED. PROVIDE BEAM CONNECTIONS AS SHOWN BELOW. ALTERNATE CONNECTIONS WILL BE ALLOWED PROVIDED THAT CONNECTION DESIGN CALCULATIONS, CERTIFIED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED, ARE SUBMITTED BY THE FABRICATOR FOR REVIEW. STEEL - STRUCTURAL: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. BOLTED/WELDED BEAM CONNECTION REQUIREMENTS ... . 3 1/2"DEPTHBEAMLENGTH(2) L 4x3 1/2 BEAM SIZE # OF 3/4"Ø A325 BOLTS EA SIDE CONN ANGLES THICKNESS LENGTH WELD SIZE W36 10 3/8" 2'-5 1/2" 1/4" W33 9 3/8" 2'-2 1/2" 1/4" W30 8 3/8" 1'-11 1/2" 1/4" W27 7 3/8" 1'-8 1/2" 1/4" W24 6 3/8" 1'-5 1/2" 1/4" W21 5 3/8" 1'-2 1/2" 1/4" W18 4 3/8" 0'-11 1/2" 1/4" W16 4 5/16" 0'-11 1/2" 1/4" W14 3 0'-8 1/2" 1/4" W12 3 0'-8 1/2" 1/4" W10 2 0'-5 1/2" 1/4" W8 2 0'-5 1/2" 1/4" W6 1 0'-4" 3/16" 5/16" 5/16" 5/16" 5/16" 5/16" NOTES: USE E70XX ELECTRODES. OUTSTANDING LEGS OF CONNECTION ANGLES MAY BE REDUCED TO 3" WHEN BEAM FRAMES INTO W8 COLUMN WEB. SEE TABLE FOR CONNECTION ANGLES, NUMBER OF BOLTS AND WELD SIZES. BOLTS SHALL BE TIGHTENED IN PROPERLY ALIGNED HOLES TO A SNUG-TIGHT CONDITION AS DEFINED BY THE LATEST EDITION OF AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS" UNO. USE BENT PLATES AS REQUIRED AT SKEWED BEAMS. 1. 2. 3. 4. 5. DESIGN CODE: STEEL DECK INSTITUTE (SDI): "DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS AND ROOF DECKS" LATEST EDITION. STEEL DECK SHALL CONFORM TO ASTM A-653 OR A-446 AND HAVE A MINIMUM YIELD STRENGTH OF 33,000 PSI AT ROOF DECK; 50,000 PSI MINIMUM AT FLOOR DECK AND INTERIOR WALL PANELS. DECK SIZE, TYPE AND GAUGE TO BE AS INDICATED ON PLANS. FASTEN STEEL DECK TO ALL INTERIOR STEEL SUPPORTS AS SHOWN ON PLANS. PROVIDE FASTENING AT 6" O.C. TO PLATE, ANGLE OR BEAM AT BUILDING PERIMETER UNO. SIDELAP FASTENING SHALL BE AS INDICATED ON PLANS. SPAN DECK SECTION MINIMUM 3 SPANS CONTINUOUS, UNO. THE STEEL DECK FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL. FLOOR DECK AND UNDERSIDE OF ROOF DECK SHALL BE GALANIZED (G60 MIN), CONFIRM W/ ARCH. TOP OF ROOF DECK SHALL BE SHOP PRIMED W/ STANDARD GRAY PRIMER. CONCENTRATED LOADS IN EXCESS OF 75# SHALL NOT BE HUNG DIRECTLY FROM ROOF DECK. CONCENTRATED LOADS 75# OR LESS ARE ALLOWED BUT SHALL ONLY BE FASTENED TO THE SIDE OF DECK FLUTES. STEEL - DECK: 1. 2. 3. 4. 5. 6. 7. DESIGN CODES: A. IBC CHAPTER 22, SECTION 2210 AND 2211-COLD FORMED STEEL AND LIGHT-FRAMING CONSTRUCTION. SEE PLANS FOR SIZE AND THICKNESS OF STUDS. B. 2010 AISI NORTH AMERICAN SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS. SEE PLANS, ELEVATIONS, SECTIONS AND DETAILS FOR SIZE AND THICKNESS OF STUDS. YIELD STRESS SHALL BE 33KSI FOR 33 MIL. AND 43 MIL. MEMBERS AND 50KSI FOR ALL OTHER MEMBERS. COLD FORMED STEEL FRAMING 600S162-43 . . . . 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. FLANGE WIDTH OF MEMBER IN HUNDREDS OF INCHES (EX. 162=1 5/8", 200=2") MEMBER THICKNESS IN MILS MEMBER DEPTH IN HUNDREDS OF INCHES (EX. 600=6") MEMBER TYPE S=STUD, T=TRACK ALL STEEL STUD FASTENERS SHALL BE WELDED CONNECTIONS, OR SHALL BE #10-16 "TEK" SCREWS MANUFACTURED BY "ITW BUILDEX" OR APPROVED EQUAL UNO. ALL WELDS SHALL BE MADE BY CERTIFIED WELDERS AND IN ACCORDANCE WITH AMERICAN WELDING SOCIETY (AWS)-D13 LATEST EDITION. THE CENTER-TO- CENTER SPACING AND EDGE DISTANCE FOR ALL SCREW FASTENERS SHALL BE AT LEAST 3x (NOMINAL DIAMETER) UNO. ALL POWDER ACTUATED FASTENERS (PAFS) SHALL BE HILTI "X-U" OR APPROVED EQUAL UNO. SPLICES IN WALL STUDS, JOISTS OR HEADERS SHALL NOT BE PERMITTED UNLESS SPLICE CONNECTIONS ARE PROVIDED IN SECTIONS AND DETAILS. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR MEMBERS, DO NOT TORCH CUT. MEMBERS SHALL BE HELD POSITIVELY IN PLACE UNTIL PROPERLY FASTENED. STUDS SHALL BE PLUMBED, ALIGNED AND SECURELY ATTACHED TO THE FLANGE OR WEB OF BOTH UPPER AND LOWER TRACKS. STUDS SHALL HAVE FULL BEARING AGAINST INSIDE TRACK WEB PRIOR TO STUD AND TRACK ATTACHMENT. SEE ARCH FOR GYPSUM BOARD AND GYPSUM SHEATHING AT ALL EXTERIOR WALLS. FASTEN TO STUDS WITH #6 MINIMUMx1" FLAT HEAD SCREWS SPACED AT 12" O.C. AT PANEL INTERMEDIATE SUPPORTS AND 6" O.C. AT PANEL EDGES. WALL STUD BRIDGING SHALL BE ATTACHED IN A MANNER TO PREVENT STUD ROTATION. BRIDGING ROWS SHALL BE SPACED AT 4'-0" O.C. MAXIMUM. INSTALLATION OF ALL REQUIRED WALL STUD BRIDGING SHALL BE COMPLETED BEFORE ANY LOADS ARE APPLIED TO THE SYSTEM. CONTINUOUS TOP AND BOTTOM RUNNER TRACKS FOR ALL WALLS SHALL BE FASTENED TO EACH STUD WITH (2) #10-16 SCREWS MINIMUM UNO. THE CONTRACTOR IS RESPONSIBLE FOR AVOIDING THE OVERLOAD OF COLD FORMED STEEL MEMBERS DURING ERECTION AND FOR PROVIDING ADEQUATE TEMPORARY BRACING UNTIL THE PERMANENT BRIDGING AND SHEATHING ARE IN PLACE. THE COLD FORMED STEEL SUPPLIER SHALL SUBMIT FOR APPROVAL DETAILED SHOP DRAWINGS INDICATING MEMBER SIZES, THICKNESS, SPACING AND ALL CONNECTIONS AS SHOWN ON THE DRAWINGS. TOUCH-UP WELDS SHALL BE WITH ZINC-RICH PAINT PER ASTM A-780. MILS TO GAUGE CONVERSION CHART MILS 20 GA 18 GA 16 GA 14 GA 33 43 54 68 GAUGE 12 GA97 10 GA118 SPECIAL INSPECTION AND TESTING IS REQUIRED IN ACCORDANCE WITH THE LATEST EDITION OF IBC, CHAPTER 17, FOR THE FOLLOWING PORTIONS OF CONSTRUCTION: SPECIAL INSPECTION AND TESTING: 1. 2. 3. THE GENERAL CONTRACTOR SHALL SUBMIT A COMPLETED "SPECIAL STRUCTURAL TESTING AND INSPECTION - PROGRAM SUMMARY SCHEDULE" TO THE BUILDING OFFICIAL, ARCHITECT AND ENGINEER PRIOR TO THE START OF CONSTRUCTION. THE TESTING/INSPECTION AGENCY SHALL SUBMIT A FINAL CERTIFIED REPORT AT SUBSTANTIAL COMPLETION INDICATING THAT ALL WORK REQUIRING SPECIAL INSPECTIONS AND TESTING HAS BEEN CONSTRUCTED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. A LIST OF ANY UNRESOLVED DEFICIENCIES SHALL BE INCLUDED IN THIS REPORT. CONCRETE SOILS: GEOTECHNICAL ENGINEER SHALL FIELD VERIFY SOIL BEARING CAPACITY AND COMPACTION PER THE REQUIREMENTS OF THE GEOTECHNICAL REPORT. SOILS: TESTING AGENCY SHALL FIELD VERIFY SOIL BEARING CAPACITY AND COMPACTION PER THE REQUIREMENTS OF THE GEOTECHNICAL ENGINEER. CAST-IN-PLACE ANCHORS IN CONCRETE POST-INSTALLED ANCHORS IN CONCRETE (PER PRODUCT ICC- ESR REQUIREMENTS) REINFORCING STEEL IN CONCRETE CAST-IN-PLACE ANCHORS IN MASONRY POST-INSTALLED ANCHORS IN MASONRY (PER PRODUCT ICC- ESR REQUIREMENTS) REINFORCING STEEL IN MASONRY - LEVEL B STRUCTURAL WELDING - VISUAL TESTING (UNO) HIGH STRENGTH BOLTING IF THE STRUCTURAL STEEL AND/OR JOIST FABRICATOR IS NOT AISC CERTIFIED, IN-SHOP SPECIAL INSPECTIONS ARE REQUIRED AND SHALL BE PAID FOR BY THE FABRICATOR. A. B. C. D. E. F. G. H. J. K. L. STRUCTURAL ABBREVIATIONS: & AND @ AT (CL TO CL SPACING) CL CENTERLINE Ø ROUND OR DIAMETER # POUND OR NUMBER AB ANCHOR BOLT AD AREA DRAIN ADD'L ADDITIONAL ADDM ADDENDUM ADJ ADJACENT AFF ABOVE FINISHED FLOOR ALT ALTERNATE APPROX APPROXIMATE ARCH ARCHITECTURAL/ITECT B/O BOTTOM OF BFE BOTTOM FOOTING ELEVATON BIT BITUMINOUS BLDG BUILDING BLK BLOCK BLKG BLOCKING BM BEAM BOT BOTTOM BRG BEARING BSMT BASEMENT BT BENT BTWN BETWEEN CANT CANTILEVER CFS COLD FORMED STEEL CIP CAST-IN-PLACE CJ CONTROL JOINT CL CENTERLINE CLR CLEAR CO CLEAN OUT COL COLUMN COMP COMPOSITE CONC CONCRETE CONN CONNECT/-ED/-ION CONST CONSTRUCT/-ION CONT CONTINUE/-OUS CONTR CONTRACT/-OR CMU CONCRETE MASONRY UNIT COORD COORDINATE CTR, CTRD CENTER, CENTERED CU FT CUBIC FEET CY CUBIC YARD DBL DOUBLE DBL TEE, TT DOUBLE TEE DEAD LD, DL DEAD LOAD DEPT DEPARTMENT DIA, Ø DIAMETER DIAG DIAGONAL DIM DIMENSION DN DOWN DO DITTO DP DEPTH OR DEEP DR DOOR DTL DETAIL DWG DRAWING DWLS DOWELS EA EACH EF EACH FACE EJ, EXP JT EXPANSION JOINT EL ELEVATION ELEC ELECTRICAL ELEV ELEVATOR EMBED EMBEDMENT, EMBEDDED EQ, = EQUAL EQUIP EQUIPMENT ERECT ERECTION EXIST EXISTING EXP EXPANSION EXT EXTERIOR EW EACH WAY FAB FABRICATE FD FLOOR DRAIN FDN FOUNDATION FFE FINISHED FLOOR ELEVATION FIN FINISH FLG FLANGE FLR FLOOR FP FIREPROOFING FRMG FRAMING FT, ' FOOT FTG FOOTING FV FIELD VERIFY GA GAUGE GALV GALVANIZED GC GENERAL CONTRACTOR GEN'L GENERAL GLU-LAM, GL GLUE LAMINATED WOOD GR BM GRADE BEAM H HIGH HD HEADED HDR HEADER HK HOOK HORIZ HORIZONTAL HT HEIGHT HVAC HEATING, VENTILATION AND AIR CONDITIONING I/F INSIDE FACE IE INVERT ELEVATION IN, " INCH INFO INFORMATION INSUL INSULATION INT INTERIOR INV INVERT JBE JOIST BEARING ELEVATION JST JOIST JT, JNT JOINT K KIPS KO KNOCK OUT KSI KIPS PER SQUARE INCH LB, # POUND LD LOAD LF LINEAL FOOT LG, LGT LENGTH, LONG LIVE LD, LL LIVE LOAD LLH LONG LEG HORIZONTAL LLV LONG LEG VERTICAL LOC LOCATION, LOCATE LONG LONGITUDINAL LSH LONG SIDE HORIZONTAL LSL LAMINATED STRAND LUMBER LSV LONG SIDE VERTICAL LT WT LIGHT WEIGHT LVL LAMINATED VENEER LUMBER MAN MANUAL MAS MASONRY MAT'L MATERIAL MAX MAXIMUM MECH MECHANICAL MEMB MEMBRANE MEZZ MEZZANINE MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MO MECHANICAL OPENING MTL MATERIAL #, NO. NUMBER NA, N/A NOT APPLICABLE NIC NOT IN CONTRACT NOM NOMINAL NTS NOT TO SCALE O/F OUTSIDE FACE O.C. ON CENTER OD OVERFLOW DRAIN OH DR OVERHEAD DOOR OPNG OPENING OPP OPPOSITE P&J PAN AND JOIST P/C PRECAST CONCRETE PAF POWDER ACTUATED FASTENER PART PARTITION PL PLATE PLBG PLUMBING PLF POUNDS PER LINEAR FOOT PNL PANEL PRELIM PRELIMINARY PREP PREPARATION PROJ PROJECT/-ION PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PT POST TENSION QUAN, QTY QUANTITY R RADIUS RD ROOF DRAIN REC RECESSED, RECOMMEND REF REFERENCE REINF REINFORCE/-ING/-ED REQ'D REQUIRED RET RETAINING REV REVISION RO ROUGH OPENING SCHED SCHEDULE SEC, SECT SECTION SF, SQ FT SQUARE FOOT SHT SHEET SIM SIMILAR SJI STEEL JOIST INSTITUTE SL SNOW LOAD SPA SPACES/-ING SPEC SPECIFICATIONS SQ SQUARE SQ YD SQUARE YARD STD STANDARD STIFF STIFFENER/-S STIR STIRRUPS STL STEEL STL JST STEEL JOIST STOR STORAGE STR, STRT STRAIGHT STRUC(T) STRUCTURAL SYM SYMMETRICAL T&B TOP AND BOTTOM T&G TONGUE AND GROOVE T/O TOP OF TBE TOP OF BEAM ELEVATION TDE TOP OF DECK ELEVATION TFE TOP OF FOOTING ELEVATION TGE TOP OF GIRDER ELEVATION THRU THROUGH TPE TOP OF PLANK ELEVATION TRANS(V) TRANSVERSE TRTD TREATED TSE TOP OF SLAB ELEVATION TYP TYPICAL TWE TOP OF WALL ELEVATION UNFIN UNFINISHED UNO UNLESS NOTED OTHERWISE VERT VERTICAL W WIDE/WIDE FLANGE W/ WITH W/O WITHOUT WD WOOD WDW WINDOW WP WORK POINT WT WEIGHT WWF WELDED WIRE FABRIC A B C D E F G H I J K L M N O P Q R S T U V W Phone: 763.425.9960 Fax: 763.425.9958 5279 Kyler Avenue NE Albertville, MN 55301 SOLUTIONS, P.A. STRUCTURAL INNOVATIVE Email: isspa@isseng.com Web: www.isseng.comISSISSISSPAISSPAPAPA REVISIONS: DRAWN BY DATE ISSUED CHECKED BY Scope Drawings These drawings indicate the general scope of the project in terms of architectural design concept, the dimensions of the building, the major architectural elements and the type of structural, mechanical and electrical systems. The drawings do not necessarily indicate or describe all work required for full performance and completion of the requirements of the contract. On the basis of the general scope indicated or described, the trade contractors shall furnish all items required for the proper execution and completion of work. PROJECT NUMBER: 618 East Market Street Indianapolis, Indiana 46202 phone 317/264.8162 a x i s a r c h . c o m CLIENT 8-27-2020 JMW MJV 08/27/2020 S001 GENERAL STRUCTURAL NOTES 86220CARMELExtra Space Storage155 CARMEL DRIVE, CARMEL, INWeihe Engineers 10505 N. College Avenue Brad Schoeff - Sr. Project Manager PH: 317-846-6611 Innovative Structural Solutions, P.A. 5279 Kyler Avenue, NE PH: 763-425-9960 Gooderum & Associates Engineering 874 Cheltenham Way PH: 317-506-8151 Indianapolis, IN 46280 Albertville, MN 55301 Avon, IN 46123 Extra Space Storage 9000 Keystone Crossing, Ste. 660 Jim Adams Indianapolis, IN 46240 PH: 317-663-8648 CIVIL ENGINEER STRUCTURAL ENGINEER MEP ENGINEER STRUCTURAL DRAWING SHEET INDEX S001 GENERAL STRUCTURAL NOTES S101 FOUNDATION PLAN S102 SECOND FLOOR FRAMING PLAN S103 THIRD FLOOR FRAMING PLAN S104 ROOF FRAMING PLAN S201 SECTIONS AND DETAILS S202 SECTIONS AND DETAILS S203 SECTIONS AND DETAILS # DESCRIPTION DATE 07/14/21