HomeMy WebLinkAboutA002 - 100_BID AND PERMIT (08-27-20)STANDARD SYSTEMS
SHAFTWALL SYSTEMS
NOTE: * = AT FRAMING EXCEEDING 12'-0" HEIGHT, PROVIDE BRACINGFRAMING1 5/8"
2-1/2"
2-1/2"
2-1/2"
3-5/8"
3-5/8"
3-5/8"
6"
6"
6"
2-1/2"
C-H STUDS
2-1/2"
C-H STUDS
2-1/2"
C-H STUDS
4"
C-H STUDS
4"
C-H STUDS
6" DBL
E STUDS
6" DBL
E STUDS
</= 6'-0"
> 6'-0" - </= 8'-0"
> 8'-0" - </= 10'-0"DEPTHAT MID HEIGHT LOCATION, BUT NOT TO EXCEED 12'-0" MAX.
SPAN
25--(0.0179")
25--(0.0179")
22--(0.0270")
20--(0.0329")
25--(0.0179")
22--(0.0270")
20--(0.0329")
25--(0.0179")
22--(0.0270")
20--(0.0329")
25--(0.0199")
22--(0.0294")
20--(0.0341")
25--(0.0199")
20--(0.0341")
25--(0.0199")
20--(0.0341")FRAMINGGAUGESTUD 16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
24"
24"
24"
24"
24"
24"
24"
2-4"X16GA. METAL CEE STUDS
2-6"X18GA. METAL CEE STUDS
2-6"X16GA. METAL CEE STUDSSPACINGALLOWABLEL/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
LINTEL SIZEDEFLECTIONFURRING2 HOUR1 LAYER8'-3"
7'-3"
11'-0"
9'-9"
12'-0"
10'-6"
13'-0"
11'-6"
14'-6"
12'-9"
16'-0"
14'-0"
17'-3"
15'-0"
20'-0"
15'-0"
25'-3"
22'-0"
26'-6"
23'-3"RATED12'-1"
14'-11"
15'-3"
16'-11"
18'-2"
26'-3"
28'-0"ONE SIDE*PARTITION1 HOUR1 LAYER9'-6"
8'-3"
12'-6"
10'-9"
13'-0"
11'-6"
14'-0"
12'-3"
16'-0"
13'-6"
17'-3"
15'-0"
18'-3"
16'-0"
20'-0"
15'-0"
26'-0"
22'-9"
27'-6"
24'-0"RATED11'-8"
13'-7"
14'-0"
15'-10"
17'-6"
25'-3"
28'-0"EACH SIDEPARTITION2 LAYERS10'-6"
8'-9"
13'-6"
11'-3"
14'-0"
12'-3"
14'-9"
13'-0"
16'-9"
13'-6"
18'-0"
15'-9"
19'-0"
16'-6"
20'-0"
15'-0"
23'-9"
20'-9"
25'-6"
22'-3"EACH SIDEINTERIOR WALL LIMITING HEIGHTS
LINTEL SCHEDULE U.N.O.
REFER FLOOR PLAN FOR
PARTITION TYPE
CUT GYPSUM WALLBOARD TO FIT
DECK FLUTES DEFLECTION TRACK
ATTACHED WITH ANCHORS
AT 2'-0" O.C.DO NOT ATTACH GYPSUM
WALLBOARD TO TOP TRACK
STRUCTURAL FLOOR OR ROOF
ASSEMBLY
FILL GAP WITH ACOUSTICAL
SEALANT
GYPSUM PARTITION AT STRUCTURE
REFER FLOOR PLAN FOR
PARTITION TYPE
HB PTA SERIES PARTITION TOP
ANCHOR OR OTHER APPROVED
LATERAL SUPPORT METHOD
STRUCTURAL FLOOR OR ROOF
ASSEMBLY
CMU PARTITION AT STRUCTURE
BOND BEAM - REF
STRUCTURAL
COMPRESSIBLE FILLER IN
JOINT AND FLOOR/ROOF1"FILL CAVITY WITH
ACOUSTICAL INSULATION
REFER FLOOR PLAN FOR
PARTITION TYPE
FIRECODE COMPOUND BOTH
SIDES. 1/2" @ 1 HR; 1" @ 2HR DEFLECTION TRACK
ATTACHED WITH ANCHORS
AT 2'-0" O.C.
DO NOT ATTACH GYPSUM
WALLBOARD TO TOP TRACK
STRUCTURAL FLOOR OR ROOF
ASSEMBLY
FIRE RATED GYPSUM PARTITION AT STRUCTURE
REFER FLOOR PLAN FOR
PARTITION TYPE
HB PTA SERIES PARTITION TOP
ANCHOR OR OTHER APPROVED
LATERAL SUPPORT METHOD
STRUCTURAL FLOOR OR ROOF
ASSEMBLY
FIRE RATED CMU PARTITION AT STRUCTURE
BOND BEAM - REF
STRUCTURAL1"FILL CAVITY WITH
THERMAFIBER SAFING
INSULATION
J-MOLD
FIRECODE COMPOUND BOTH
SIDES. 1/2" @ 1 HR; 1" @ 2HR
FILL CAVITY WITH THERMAFIBER
SAFING INSULATION
1/4" JOINT
#093 ZINC CONTROL
JOINT
GYPSUM WALLBOARD PER
PARTITION TYPE
GYPSUM PARTITION CONTROL JOINT
CMU CONTROL JOINT
BACKER ROD AND SEALANT
JOINT EA. SIDE OF WALL
FLANGED NEOPRENE
CONTROL JOINT CONT.
STOP HORIZ. BARS AT
EACH SIDE OF JOINT
VERTICAL REINFORCING
PER STRUCTURAL
SASH BLOCK CMU
3/8"
ADDITIONAL STUD AS
REQ'D
1/4" JOINT
#093X ZINC CONTROL
JOINT - FIRE RATED
GYPSUM WALLBOARD PER
PARTITION TYPE
GYPSUM PARTITION CONTROL JOINT
FIRE-RATED
ADDITIONAL STUD AS
REQ'D
THERMAFIBER INSULATION
CMU CONTROL JOINT FIRE RATED
BACKER ROD AND SEALANT
JOINT EA. SIDE OF WALL
CERAMIC FIBER BLANKET WERE
REQUIRED FOR FIRE RATING
STOP HORIZ. BARS AT
EACH SIDE OF JOINT
VERTICAL REINFORCING
PER STRUCTURAL
SASH BLOCK CMU
1/2"
STRUCTURAL FLOOR OR ROOF
ASSEMBLY
WALL HEIGHT C = EXTEND TO BOTTOM OF CEILINGWALL HEIGHT A = EXTEND WALL TO 6" ABOVE CEILINGWALL HEIGHT S = EXTEND WALL TO BOTTOM OF STRUCTURAL DECKBRACE TO STRUCTURE AT
4'-0" O.C. AT PARTIAL HEIGHT
WALLS
METAL STUDS. PROVIDE WIDTH
PER WALL TYPE AND GAGE AS
REQUIRED FOR HEIGHT
5/8" GYPSUM WALLBOARD
TYP. BOTH SIDES (USE TYPE X
FOR RATED ASSEMBLIES)
SOUND ATTENUATION
INSULATION AS SPECIFIED PER
WALL TYPE
CONTINUOUS METAL
RUNNER TRACK
ACOUSTICAL SEALANT
AT ALL JOINTS 45.00°
ACOUSTICAL SEALANT
AT ALL JOINTS
DEFLECTION TRACK AT
STRUCTURE
TYPICAL WALL NOTES
CEILING WHERE OCCURS
FIRE RATING
(AS OCCURS)
HEIGHT ATTRIBUTE
S - CONSTRUCT TO STRUCTURE ABOVE
A - CONSTRUCT WALL TO 6" ABOVE CEILING
C - CONSTRUCT WALL TO CEILING
**IF NO ATTRIBUTE - CONSTRUCT
WALL TO STRUCTURE.
1 HR
W1A.S
LOW WALL HEIGHT
AS OCCURS
1 HR
W1A.S
4' - 0"
WALL TYPE - REFER
SCHEDULE ON A002
WALL TYPE SYMBOL
TYPICAL WALL NOTES
A. VERIFY ALL RATED WALLS WITH LIFE SAFETY COMPLIANCE PLAN.
B. ALL RATED WALL ASSEMBLY CONSTRUCTION SHALL BE SEALED WITH FIRE/SMOKE
RATED SEALANT @ ALL JOINTS AND PENETRATIONS. PROVIDE SMOKE DAMPERS AT
ALL DUCT PENETRATIONS THROUGH RATED WALLS.
C. ALL ACOUSTICAL WALL ASSEMBLY CONSTRUCTION SHALL BE SEALED WITH
ACOUSTICAL SEALANT AT ALL JOINTS AND PENETRATIONS. REFER TO TYPICAL
ACOUSTICAL DETAILS.
D. WATER RESISTANT GYPSUM WALLBOARD SHALL BE USED IN LIEU OF TYPE 'X'
GYPSUM WALLBOARD IN ALL LOCATIONS WHERE CERAMIC AND PORCELAIN
TILE FINISH IS USED; AS WELL AS ALL RESTROOMS, KITCHEN, MECHANICAL
ROOMS, AND JANITOR CLOSETS.
E. GAGE OF ALL INTERIOR METAL STUD FRAMING TO BE DESIGNED FOR 5 PSF
WIND LOADS, STUD HEIGHT AND ADDITIONAL LOADING SUCH AS MILLWORK
OR SUSPENDED ITEMS WITH DEFLECTION LIMITED TO L/240.
F. ALL WALL FRAMING THAT EXTENDS ABOVE FINISH CEILING TO BE BRACED TO
STRUCTURE ABOVE AT 4'-0" O.C. ALTERNATING DIRECTIONS AS LIMITING HEIGHTS
REQUIRE.
G. ALL WALL FRAMING NOTED TO EXTEND TO CEILING OR 6" ABOVE CEILING TO
BE BRACED TO STRUCTURE AT 4'-0" O.C. ALTERNATING DIRECTIONS.
H. REFER TO REFLECTED CEILING PLAN FOR CEILING MATERIALS AND HEIGHTS;
REFER ROOM FINISH SCHEDULE FOR APPLIED FINISHES AND SPECIAL
INSTRUCTION.
J. PROVIDE METAL TRIM OR ZIP-STRIPS AT THE EDGES OF ALL GYPSUM WALLBOARD
WHERE IT ABUTS ANOTHER MATERIAL AND WHERE EDGES ARE EXPOSED TO VIEW.
K. DIVIDE ALL GYPSUM WALLBOARD AREAS WITH CONTROL JOINTS NOT EXCEEDING
30 FEET IN EITHER DIRECTION OR AS SHOWN OTHERWISE. PROVIDE RATED
CONTROL JOINTS IN FIRE RATED PARTITIONS. COORDINATE LOCATION OF
CONTROL JOINTS WITH ARCHITECT PRIOR TO INSTALLATION.
L. PROVIDE HIGH-IMPACT GYPSUM WALLBOARD IN ALL CORRIDORS, STAIRCASES
AND OTHER SPACES AS NOTED ON PLANS.
M. PROVIDE HORIZONTAL JOINT REINFORCEMENT AT 16" O.C. AT MASONRY WALLS.
PROVIDE VERTICAL REINFORCEMENT PER STRUCTURAL DRAWINGS AND
SPECIFICATIONS.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M4A - - - - -
DESCRIPTION: 4" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.3 5/8"5 5/8" 7 5/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M6A - - - - -
DESCRIPTION: 6" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M6B 1 HR UL U906 - -
DESCRIPTION: 6" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M8A - - - - -
DESCRIPTION: 8" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M8B 1 HR UL U905 - -
DESCRIPTION: 8" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.5 5/8" 7 5/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M6C 2 HR UL U906 - -
DESCRIPTION: 6" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.5 5/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M8C 2 HR UL U905 - -
DESCRIPTION: 8" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.7 5/8" 7 5/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M8D 3 HR UL U904 - -
DESCRIPTION: 8" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.9 5/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M10A - - - - -
DESCRIPTION: 10" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.11 5/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.M12A - - - - -
DESCRIPTION: 12" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically.
Refer to structural for vertical reinforcement.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. S2A - - - - -
INTERIOR FURRED WALL:One layer 5/8" X
gypsum
board applied vertically to one of 1-5/8" steel
studs
16" o.c.2 1/4"FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. S3A - - - - -
INTERIOR FURRED WALL: One layer 5/8" X
gypsum
board applied vertically to one of 2-1/2" steel
studs
16" o.c.3 1/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. S4C - - - - -
INTERIOR WALL: One layer 5/8" X gypsum board
applied vertically to each side of 3-5/8" steel studs
16" o.c.4 7/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.S4A - - - - -
INTERIOR FURRED WALL:One layer 5/8" X
gypsum
board applied vertically to one of 3-5/8" steel
studs
16" o.c.4 1/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.S4E 1 HR UL U419 - -
INTERIOR WALL: One layer 5/8" X gypsum board
applied vertically to each side of 3-5/8" steel studs
16" o.c. Fill stud cavities with 3" fiberglass batt
insulation.4 7/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.S4B - - - - -
INTERIOR FURRED WALL: One layer 5/8" X
gypsum
board applied vertically to one of 3-5/8" steel
studs
16" o.c. Fill stud cavities with 3" fiberglass batt
insulation.4 1/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.S4D - - - - -
INTERIOR WALL: One layer 5/8" X gypsum board
applied vertically to each side of 3-5/8" steel studs
16" o.c. Fill stud cavities with 3" fiberglass batt
insulation.4 7/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.S4F 2 HR UL U419 - -
INTERIOR WALL: Two layers of 1/2" X gypsum
board
applied vertically to each side of 3-5/8" steel studs
16" o.c. Fill stud cavities with 3" fiberglass batt
insulation.5 5/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. S6C - - - - -
INTERIOR WALL: One layer 5/8" X gypsum board
applied vertically to each side of 6" steel studs
16" o.c.7 1/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.S6A - - - - -
INTERIOR FURRED WALL:One layer 5/8" X
gypsum
board applied vertically to one of 6" steel studs
16" o.c.6 5/8"FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. S6E 1 HR UL U419 - -
INTERIOR WALL: One layer 5/8" X gypsum board
applied vertically to each side of 6" steel studs
16" o.c. Fill stud cavities with 5-1/2" fiberglass batt
insulation.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. S6B - - - - -
INTERIOR FURRED WALL: One layer 5/8" X
gypsum
board applied vertically to one of 6" steel studs
16" o.c. Fill stud cavities with 5-1/2" fiberglass batt
insulation.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. S6D - - - - -
INTERIOR WALL: One layer 5/8" X gypsum board
applied vertically to each side of 6" steel studs
16" o.c. Fill stud cavities with 5-1/2" fiberglass batt
insulation.
FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.S6F 2 HR UL U419 - -
INTERIOR WALL: Two layers of 1/2" X gypsum
board
applied vertically to each side of 6" steel studs
16" o.c. Fill stud cavities with 5-1/2" fiberglass batt
insulation.8" 6 5/8"7 1/4" 7 1/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. W4A - - - - -
INTERIOR FURRED WALL:One layer 5/8" X
gypsum
board applied vertically to one side of 2x4" wood
studs
16" o.c.4 1/8"FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. W4B - - - - -
INTERIOR WALL: One layer 5/8" X gypsum
board applied vertically to both sides of 2x4" wood
studs 16" o.c.4 3/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.W4C - - - 33 RAL-TL11-086
INTERIOR WALL: One layer 5/8" X gypsum
board applied vertically to both sides of 2x4" wood
studs 16" o.c. Fill stud cavities with 3-1/2"
fiberglass
batt insulation.4 3/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. W4D 1 HR UL U305 - -
INTERIOR WALL: One layer 5/8" X gypsum
board applied vertically to both sides of 2x4" wood
studs 16" o.c. Fill stud cavities with 3-1/2"
fiberglass batt
insulation.4 3/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. W6A - - - - -
INTERIOR FURRED WALL:One layer 5/8" X
gypsum
board applied vertically to one side of 2x6" wood
studs
16" o.c.6 1/8" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. W6B - - - - -
INTERIOR WALL: One layer 5/8" X gypsum
board applied vertically to both sides of 2x6" wood
studs 16" o.c.6 3/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.W6C - - - 33 RAL-TL11-086
INTERIOR WALL: One layer 5/8" X gypsum
board applied vertically to both sides of 2x6" wood
studs 16" o.c. Fill stud cavities with 5-1/2"
fiberglass batt
insulation.6 3/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No. W6D 1 HR UL U305 - -
INTERIOR WALL: One layer 5/8" X gypsum
board applied vertically to both sides of 2x4" wood
studs 16" o.c. Fill stud cavities with 5-1/2"
fiberglass batt
insulation.6 3/4" FIRE
RATING
REF. DESIGN
No.
STC
RATING
TEST No.W6E 1 HR UL U311 - -
INTERIOR WALL: One layer 5/8" X gypsum
board applied vertically to both sides of 2x4" wood
studs 16" o.c. Fill stud cavities with 5-1/2"
fiberglass batt
insulation.7 1/4" DANDR ID GE DRE
W
WHITEHI T
AR-19400087
ARC TEC
STATE OF
No.
DND
I NAA AII
R EG I STERE
DNDI NA AI
HI TARC TECDANDRID GE DRE
W
WHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in terms of
architectural design concept, the dimensions of the building, the major
architectural elements and the type of structural, mechanical and
electrical systems. The drawings do not necessarily indicate or describe
all work required for full performance and completion of the requirements
of the contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items required for the
proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
CLIENT
GSD
DDW
08/17/2020
A002
INTERIOR WALL TYPES AND
DETAILS
19045CARMELExtra Space Storage155 CARMEL DRIVE, CARMEL, INWeihe Engineers
10505 N. College Avenue
Brad Schoeff - Sr. Project Manager
PH: 317-846-6611
Innovative Structural Solutions, P.A.
5279 Kyler Avenue, NE
PH: 763-425-9960
Gooderum & Associates Engineering
874 Cheltenham Way
PH: 317-506-8151
Indianapolis, IN 46280
Albertville, MN 55301
Avon, IN 46123
Extra Space Storage
9000 Keystone Crossing, Ste. 660
Jim Adams
Indianapolis, IN 46240
PH: 317-663-8648
CIVIL ENGINEER
STRUCTURAL ENGINEER
MEP ENGINEER
SCALE: 1 1/2" = 1'-0"02 TYPICAL INTERIOR WALL DETAILS
SCALE: 1 1/2" = 1'-0"01 TYPICAL INTERIOR WALL SECTION
SCALE: 3/4" = 1'-0"
INTERIOR WALL TYPES LEGEND
# DESCRIPTION DATE
07/14/21