Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
To: Blue Raven Solar
1403 North Research Way, Building J
Orem, UT. 84097
Subject: Certification Letter
Richter Residence
13956 Four Seasons Way
Indianapolis, IN. 46074
To Whom It May Concern,
Design Criteria:
●Applicable Codes = 2014 Indiana State Building Code, ASCE 7‐10
●Roof Dead Load = 7 psf (MP1&2)
●Roof Live Load = 20 psf
●Wind Speed = 115 mph (Vult), Exposure C, Risk Category II
●
●
Sincerely,
John Calvert, P.E.
Project Engineer
June 4, 2021
The roof structures of (MP1&2) consist of composition shingle on roof plywood that is supported by pre‐manufactured trusses
that are spaced at @ 24"o.c.. The top chords, sloped at 40 degrees, are 2x4 sections, the bottom chords are 2x4 sections and the
web members are 2x4 sections. The truss members are connected by steel gusset plates. The max unsupported projected
horizontal top chord span is approximately 7'‐6''.
The existing roof framing systems of (MP1&2) are judged to be adequate to withstand the loading imposed by the installation of
the solar panels. No reinforcement is necessary.
Ground Snow Load = 20 psf ‐ Roof Snow Load = 14 psf
The spacing of the solar standoffs should be kept at 72" o.c. for landscape and 48" o.c. for portrait orientation, with a staggered
pattern to ensure proper distribution of loads.
A jobsite observation of the condition of the existing framing system was performed by an audit team of Blue Raven Solar as a
request from Domus Structural Engineering. All review is based on these observations and the design criteria listed below and
only deemed valid if provided information is true and accurate.
On the above referenced project, the roof structural framing has been reviewed for additional loading due to the installation of
the solar PV addition to the roof. The structural review only applies to the section of the roof that is directly supporting the solar
PV system and its supporting elements. The observed roof framing is described below. If field conditions differ, contractor to
notify engineer prior to starting construction.
The scope of this report is strictly limited to an evaluation of the fastener attachment, underlying framing and supporting
structure only. The attachment's to the existing structure are required to be in a staggered pattern to ensure proper distribution
of loading. All panels, racking and hardware shall be installed per manufacturer specifications and within specified design
limitations. All waterproofing shall be provided by the manufacturer. Domus Structural Engineering assumes no responsibility
for misuse or improper installation of the solar PV panels or racking.
Please contact me with any further questions or concerns regarding this project.
Note: Seismic check is not required since Ss<.4g and Seismic Design Category (SDC) < B
Attachment: 1 ‐ 5/16 dia. lag screw with 2.5 inch min. embedment
depth, at spacing shown above.
Richter Indianapolis IN.xlsm 1
____________________________________________________________________________________
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
20 psf
(ASCE7 - Eq 7-1)
1 (ASCE7 - Table 7-2)
1 (ASCE7 - Table 7-3)
1
14.0 psf
(ASCE7 - Eq 7-2)
1
14.0 psf
3.92 psf
3.0 psf
4.00 ft
5.50 ft
22.00 sft
66 lb
4.00
2.00
0.73
0.00 (Ceiling Not Vaulted)
0.27
7.0 psf
9.1 psf
Gravity Loading
PV System Weight
Weight of PV System (Per Blue Raven Solar)
X Standoff Spacing =
Y Standoff Spacing =
Note: PV standoffs are staggered to ensure proper distribution of loading
2x4 Top Chords @ 24"o.c.
I = Importance Factor =
Cs = Slope Factor =
Standoff Tributary Area =
ps = Cspf
ps = Sloped Roof Snow Load =
pf = Flat Roof Snow Load =
DL Adjusted to 40 Degree Slope
Roof Snow Load Calculations
pg = Ground Snow Load =
Ce = Exposure Factor =
pf = 0.7 Ce Ct I pg
Ct = Thermal Factor =
Roof Live Load = 20 psf
Roof Plywood
Roof Dead Load (MP1&2)
Composition Shingle
Note: Roof live load is removed in area's covered by PV array.
DL Adjusted to 40 Degree Slope
Point Loads of Standoffs
Miscellaneous
Vaulted Ceiling
Total Roof DL (MP1&2)
PV Dead Load = 3 psf (Per Blue Raven Solar)
Richter Indianapolis IN.xlsm 2
___________________________________________________________________________________________
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
115 mph
C
Hip/Gable
40 degrees
20 ft
19.3 ft
(Eq. 30.3-1)
0.9 (Table 30.3-1)
1 (Fig. 26.8-1)
0.85 (Table 26.6-1)
115 mph (Fig. 26.5-1A)
II (Table 1.5-1)
qh = 25.90
15.54
Zone 1 Zone 2 Zone 3 Positive
GCp = -0.94 -1.15 -1.15 0.84 (Fig. 30.4-1)
Uplift Pressure = -14.67 psf -17.91 psf -17.91 psf 21.7 psf
X Standoff Spacing = 4.00 4.00 2.67
Y Standoff Spacing = 5.50 2.75 2.75
Tributary Area = 22.00 11.00 7.33
Dead Load on Attachment= 66.00 33.00 22.00
Footing Uplift (0.6D+0.6W)= -283 lb -177 lb -118 lb
Zone 1 Zone 2 Zone 3 Positive
GCp = -0.94 -1.15 -1.15 0.84 (Fig. 30.4-1)
Uplift Pressure = -14.67 psf -17.91 psf -17.91 psf 10.0 psf (Minimum)
X Standoff Spacing = 6.00 6.00 4.00
Y Standoff Spacing = 3.50 1.75 1.75
Tributary Area = 21.00 10.50 7.00
Dead Load on Attachment= 63.00 31.50 21.00
Footing Uplift (0.6D+0.6W) = -270 lb -169 lb -113 lb
-283 lb
450 lb
Therefore, OK
Fastener =1 - 5/16" dia. lag
Number of Fasteners = 1
Embedment Depth = 2.5
Pullout Capacity Per Inch = 250 lb
Fastener Capacity = 625 lb
w/ F.S. of 1.5 & DOL of 1.6= 667 lb
Therefore, OK
Wind Calculations
Maximum Design Uplift =
Standoff Uplift Capacity =
450 lb capacity > 283 lb demand
Fastener Capacity Check
Standoff Uplift Check
Kz (Exposure Coefficient) =
Kzt (topographic factor) =
Kd (Wind Directionality Factor) =
V (Design Wind Speed) =
Risk Category =
qh = 0.00256 * Kz * Kzt * Kd * V^2
Wind Pressure P = qh*G*Cn
Exposure Category
Per ASCE 7‐10 Components and Cladding
Mean Roof Height
Roof Slope
667.2 lb capacity > 283 lb demand
0.6 * qh =
Standoff Uplift Calculations-Landscape
Input Variables
Wind Speed
Effective Wind Area
Design Wind Pressure Calculations
Roof Shape
Standoff Uplift Calculations-Portrait
Richter Indianapolis IN.xlsm 3
___________________________________________________________________________________________
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
(MP1&2)PASS
Dead Load 9.1 psf
PV Load 3.9 psf
Snow Load 14.0 psf
Governing Load Combo = DL + LL
Total Load 33.1 psf
Fb (psi) = f'b x Cd x Cf x Cr (NDS Table 4.3.1)
900 x 1.25 x 1.5 x 1.15
Allowed Bending Stress = 1940.6 psi
(wL^2) / 8
= 464.8229 ft#
= 5577.875 in#
Actual Bending Stress = (Maximum Moment) / S
= 1821.4 psi
L/180 (E = 1600000 psi Per NDS)
= 0.5 in
Deflection Criteria Based on =
(w*L^4) / (185*E*I)
=
= L/395 > L/180 Therefore OK
Allowed Deflection (Live Load) =L/240
0.375 in
(w*L^4) / (185*E*I)
L/653 > L/240 Therefore OK
Member Area = Fv (psi) = 180 psi (NDS Table 4A)
Allowed Shear = Fv * A = Max Shear (V) = w * L / 2 = 248 lb
Framing Check
5.3 in^2
Check Shear
w = 66 plf
2x4 Top Chords @ 24"o.c.
Member Span = 7' - 6"
945 lb
Allowed > Actual -- 26.3% Stressed -- Therefore, OK
DF#2
Member Spacing
@ 24"o.c.
Maximum Moment =
Check Deflection
I (in^4)
5.36
Lumber Sp/Gr
Actual Deflection (Live Load) =
Allowed Deflection (Total Load) =
Actual Deflection (Total Load) =
Allowed > Actual -- 93.9% Stressed -- Therefore, OK
Member Properties
Member Size
2x4
S (in^3)
3.06
0.138 in
Continuous Span
0.228 in
Check Bending Stress
(True Dimensions)
Richter Indianapolis IN.xlsm 4