HomeMy WebLinkAboutInspection CF-2021-0000518.pdfFinal Fire Inspection for Occupancy
Carmel Fire Department
10701 N. College Ave.
Indianapolis, IN 46280
317-571-2600
cfdinspections@carmel.in.gov
Final Inspection Inspection Result
Status
Completed with failures
Inspected by
Lucas Ray
Completed at
07/13/2021 15:16
Business Address Suite City State Zip
101 4TH AVE SE -- CARMEL IN 46032
Business Name Building Type
CARMEL ELEMENTARY
SCHOOL
EXEMPT
Re-Inspection Scheduled for Will Call
Item Result Remarks
PERMIT NUMBER Fail
Hydraulic Tag shall be posted. Add Horn
Strobe to Mezzanine outside roof area. FDC
lowered, turned, painted red and add address
numerics Add RISER ROOM to outside of
doors to the right of the system Label FACP
door as well Label risers zone 1,2,3
respectfully
Fail
Code
INDIANA_IFC2014 - 901.5.1 - Occupancy. - It shall be unlawful to occupy any portion of a building or structure until
the required fire detection, alarm and suppression systems have been tested and approved.
CF-2021-0000518 1 / 3
Item Result Remarks
Remove lock from mezzanine mechanical
door. Add Exit signs on front patio. All mag
lock systems shall be tested prior to final C of
O. Finish all drives and sidewalks Egress
lighting must be installed in North vestibule
Fail
Code
INDIANA_IFC2014 - 1001.1 - General. - Buildings or portions thereof shall be provided with a means of egress system
as required by this chapter. The provisions of this chapter shall control the design, construction and arrangement of
means of egress components required to provide an approved means of egress from structures and portions thereof.
Sections 1003 through 1029 shall apply to new construction. Section 1030 shall apply to existing buildings. Exception:
Detached oneand two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories
above grade plane in height with a separate means of egress and their accessory structures shall comply with the
International Residential Code.
All ceiling tiles must be installed throughout
the building All sprinkler caps must be
removed All construction materials must be
cleared out of building
Fail
All hood systems must still be tested and
approved prior to C of O
Fail
Code
INDIANA_IFC2014 - 901.4.1 - Required fire protection systems. - Fire protection systems required by this code or the
International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code.
Notes
Permit # 20010091
CF-2021-0000518 2 / 3
All Violations are cited from Indiana Fire Code (675 IAC 22-2.4), the Indiana
Code, NFPA, and Carmel City Code unless otherwise noted.
Notice of Fire and/or Safety Violations:
You are hereby notified that a Fire Inspection of your premises has been made. Any violations to Fire
Code have been noted by the inspector above.
Order to Comply:
The violation(s) listed above could be peril to the life and safety of the occupants and/or property.
You are hereby notified to have the violation(s) eliminated 30 days from inspection, unless otherwise
noted as some violations will need to be corrected immediately.
Compliance:
Please send email notification to the Carmel Fire Department Prevention Division at
CFDInspections@carmel.in.gov with evidence of corrected violation(s). If violations CANNOT be
corrected before the (30) day compliance expires, you must contact the Carmel Fire Prevention
Bureau via email or phone. The Carmel Fire Prevention Bureau reserves the right to perform re-
inspections to assure quality control of this program.
Right of Appeal:
You have specific rights including: (1.) The right to file a written petition for review of violation(s) or
order(s) issued within eighteen (18) working days of the date you receive notification, to the State
Fire Marshal, Department of Building Services, 402 W. Washington St., Suite E241, Indianapolis, IN
46204 (2.) The right to request an informal discussion of the violation(s) prior to filing a petition for
review
Failure to Comply with Order(s):
Failure to comply with this order by the time set may result in the following: (1.) Institution of a
mandatory and injunctive relief in the enforcement of Indiana Code Chapter 22-14. (2.) Revocation or
denial of a permit to operate your business.
Inspection Signatures
Occupancy Contact Signature
Brad Judy
bjudy@skillman.com
Inspector Signature
Lucas Ray
Fire Marshal
lray@carmel.in.gov
Powered by TCPDF (www.tcpdf.org)
CF-2021-0000518 3 / 3