HomeMy WebLinkAboutGarden Table Carmel - Boaz Construction - Permit Responses
Boaz Construction – 4201 Millersville #200, Indianapolis IN 46240
www.buildboaz.com
Ph: 317-790-7333
July 28, 2021
ATTN: Carmel Fire Department
RE: The Garden Table
350 Monon Blvd
Carmel IN, 46032
Dear Reviewer,
Please find responses to comments related to the review of the permit application for the referenced
project:
1) Building Fire Alarm System Notification and initiating devices shall be installed through out space
as required by NFPA 72 and the 2014 Indiana Fire Code. Fire Alarm Test/Inspection
documentation and device certification installation letter shall be submitted to CFD Code
Enforcement system at the time of Final Inspection request.
RESPONSE – See attached letter response from Spencer Engineering.
2) All required exit doors shall not be provided with a lock or latch unless it is panic or fire exit
hardware as required by section 1008.1.10 of the Indiana Fire Code. Interior and patio required
exit doors.
REPSONSE – See attached letter response from One10 Studios.
3) Fire sprinkler system coverage shall be installed in the entire space as required by the Indiana
Fire Code and NFPA 13.
RESPONSE – Frontier Fire Suppression will be the fire suppression contractor responsible
for reworking existing shell coverage to coordinate with new walls and ceilings. Frontier
Fire Suppression will apply for a separate State CDR for fire suppression work, and that
will be uploaded to Project Dox site once received.
4) Emergency Lighting shall be installed in outdoor patio area as required by section 1006.3 of the
Indiana Fire Code.
RESPONSE – See attached letter response from Spencer Engineering.
5) Kitchen hood system and fire sprinkler plans and state CDR's shall be submitted to CFD via
project dox when ready for review.
RESPONSE – Zesco is the contractor responsible for kitchen hood installation, will submit
finalized plans & State CDR when we receive them.
Thank you,
Ben Summers
Project Manager
317-556-2074
200 S MERIDIAN STREET, SUITE 301, INDIANAPOLIS, INDIANA 46225 | ONE10STUDIO.COM
July 27, 2021
Attn: Carmel Fire Department
RE: The Garden Table
350 Monon Blvd.
Carmel, IN
Permit Application: B-2021-00999
Dear Reviewer,
Please find responses to comments related to the review of the permit
application for the referenced project. All comments are addressed in the
order they appeared on the review.
• Doors exiting interior and south patio space to be furnished with
required panic hardware or locks and signage in compliance with
Section 1008.1.9.3 Item 2.
Sincerely,
Daniel Toner, AIA
404.245.2117 tel
dtoner@one10studio.com
1533 East Northfield Dr, Suite 400 Brownsburg, In 46112 ph:317.858.9970
Mechanical, Electrical, & Plumbing Engineering Firm
www.spencermep.com
July 27, 2021
Carmel Fire Department
Carmel, IN
Re: The Garden Table
350 Monon Blvd.
Carmel, IN
Permit Application: B-2021-00999
Dear Reviewer,
This letter is in response to the review of the subject space. All comments applicable to the comments
have been addressed in the order they appeared on the review. Any changes made based on each
comment are listed by sheet.
• Fire alarm notification devices shall be tied into existing building fire alarm control panel. Duct
mounted smoke detectors are not required due to system being below 2000 cfm.
• Contractor shall connect three (3) type A3 light fixtures on patio to emergency lighting invertor.
• Exit sign installed at patio exit door entering garage shall be rotated 90 degrees to be visible from
table area.
It is our intention to have responded properly to all of your concerns and we hope you find the above
acceptable and are able to approve the submission with the above explanations and information. Thanks
in advance for your time and consideration.
Signed,
Donald E. Spencer, P.E.