HomeMy WebLinkAboutWillowHaven_ElectricalSchematicDoc_122120201. THE ELECTRICAL DRAWING INCLUDED HEREIN ARE SCHEMATIC DESIGN DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING ALL FINAL LOAD
CALCULATIONS, LIGHTING CALCULATIONS, SIZING OF ALL EQUIPMENT AND WIRING,
ETC BASED ON ACTUAL EQUIPMENT INSTALLED. CONTRACTOR SHALL ALSO BE
RESPONSIBLE FOR CONFIRMING ACTUAL EQUIPMENT SELECTED WILL PHYSICALLY
FIT WHILE MAINTAINING CODE AND MANUFACTURER REQUIRED CLEARANCES.
2. ALL ELECTRICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST
ADOPTED NATIONAL ELECTRICAL CODE AND ALL APPLICABLE FEDERAL, STATE, AND
LOCAL CODES.
3. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE
OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
4. ALL WIRE, CONDUIT, CONNECTORS, OUTLET BOXES, ETC. NECESSARY TO ACHIEVE A
COMPLETE ELECTRICAL INSTALLATION WHERE AN ELECTRICAL DEVICE IS REQUIRED
BY CODE BUT NOT SHOWN SHALL BE FURNISHED AND INSTALLED AS THOUGH FULLY
SHOWN AND SPECIFIED.
5. ALL CONDUIT, JUNCTION BOXES, ETC. ABOVE CEILINGS SHALL BE SUPPORTED FROM
THE BUILDING DECK, LIGHTING FIXTURES WHICH ARE INSTALLED IN SUSPENDED
CEILING SYSTEMS MUST BE MECHANICALLY FASTENED TO T-BAR SYSTEM AS PER
SPECIFICATIONS.
6. NO CUTTING OF BUILDING CONSTRUCTION SHALL BE DONE WHICH MAY IN ANYWAY
AFFECT THE BUILDING STRUCTURALLY OR ARCHITECTURALLY WITHOUT FIRST
SECURING THE OWNER'S CONSENT AND APPROVAL.
7. NO CONDUITS SHALL BE RUN THROUGH OR SUPPORTED FROM DUCTWORK.
8. ALL AREAS WHICH ARE DAMAGED BECAUSE OF THE ELECTRICAL WORK UNDER THIS
CONTRACT SHALL BE REPAIRED AND/OR REFINISHED. THE CONTRACTOR WILL BE
RESPONSIBLE FOR ALL CUTTING, PATCHING, PAINTING, AND REMOVING/REPLACING
CEILING TILES DAMAGED OR SOILED AS IS NECESSARY.
9. AFTER CONSTRUCTION IS COMPLETED, LABEL ALL CIRCUIT BREAKERS IN ALL
ELECTRICAL PANELS INVOLVED. SPARES SHALL BE MARKED AS SPARES.
10. ALL ELECTRICAL WORK, WIRING, CONNECTIONS, AND ASSOCIATED EQUIPMENT
WITHIN THE AREA OF WORK SHALL BE AS PER APPLICABLE ARTICLES OF THE
NATIONAL ELECTRICAL CODE. COORDINATE WITH SPECIFICATIONS FOR DEVICE
REQUIREMENTS.
11. THE ENTIRE INSTALLATION MUST BE GROUNDED IN COMPLIANCE WITH THE
NATIONAL ELECTRICAL CODE. ALL DEVICES, EQUIPMENT BOXES, ETC. MUST BE
CONNECTED TO A SOLID, INSULATED GREEN, COPPER GROUNDING CONDUCTOR.
THIS GROUNDING CONDUCTOR MUST BE CONTINUOUS WITHOUT SPLICES FROM
POINT OF ORIGIN IN PANELBOARD TO ALL BOXES AND EQUIPMENT ON EACH BRANCH
CIRCUIT. VERIFY GROUNDING VALUES AND SUBMIT A TYPEWRITTEN REPORT TO
THE ARCHITECT INDICATING TESTING RESULTS OF EACH CIRCUIT AT THE
COMPLETION OF THE PROJECT.
12. FOR SINGLE PHASE CIRCUITS, UNLESS NOTHER OTHERWISE, NEW WIRING
INDICATED SHALL BE (2) #12 & (1) #12 GROUND IN 3/4" CONDUIT. FOR CIRCUITS THAT
REQUIRE LONG TRAVEL DISTANCES, REFER TO VOLTAGE DROP NOTE BELOW.
13. ALL NEW CONDUITS INSTALLED UNDER THIS PROJECT MUST BE INSTALLED AS HIGH
AS POSSIBLE AND INSTALLED AROUND EXISTING BEAMS.
14. FIRESTOP ALL CONCEALED AND ACCESSIBLE CONDUITS WITHIN THE CONTRACT
WORK AREA. FIRESTOP ALL CONDUITS AS PART OF THE NEW CONSTRUCTION.
15. PROVIDE AND INSTALL APPROVED FIRE STOPPING AT ALL FLOOR SLAB/CEILING AND
WALL PENETRATIONS TO MAINTAIN THE FIRE RATED CONSTRUCTION.
16. RECEPTACLES SHALL BE PROVIDED WITH ARC-FAULT CIRCUIT INTERRUPTER
PROTECTION WHERE REQUIRED BY APPLICABLE CODES.
GENERAL ELECTRICAL NOTES:
VOLTAGE DROP NOTE:
THE FOLLOWING LIST APPLIES TO ALL NEW BRANCH WIRING PROVIDED UNDER
THIS CONTRACT. LISTS INDICATE THE NECESSARY GAUGE OF CONDUCTORS FOR
BRANCH CIRCUITS ONE WAY FROM PANEL TO LAST OUTLET OR LIGHTING FIXTURE
ON THE CIRCUIT.
120/240V CIRCUITS WIRE SIZE
· 0-100 FEET No. 12 AWG
· 101-250 FEET No. 10 AWG
· 250-400 FEET No. 8 AWG
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM SYSTEM AUDIO/VISUAL TYPE HORN W/ADA STROBE
FIRE ALARM SYSTEM SMOKE/CARBON DIOXIDE
COMBO DETECTOR - PHOTO-ELECTRIC
FIRE ALARM SYSTEM - FLOW SWITCH FOR SPRINKLER SYSTEM
INDIVIDUAL ADDRESSABLE MODULE
FIRE ALARM SYSTEM MANUAL PULL STATION
FIRE ALARM SYSTEM SMOKE DETECTOR -
PHOTO-ELECTRIC
FIRE ALARM SYSTEM STROBE
FIRE ALARM SYSTEM - SUPERVISED VALVE FOR SPRINKLER
SYSTEM
FIRE ALARM SYSTEM CONTROL PANEL
FIRE ALARM SYSTEM HEAT DETECTOR
FIRE ALARM SYSTEM - TAMPER SWITCH FOR SPRINKLER SYSTEM
FIRE ALARM SYSTEM LEGEND
BOLLARD
LIGHTING LEGEND
DOUBLE SPOT LIGHT
RECESSED MOUNTED DOWN LIGHT TYPE FIXTURE
FAN LIGHT
FLOOD LIGHT
FLOOD LIGHT FIXTURE
HID LIGHT FIXTURE - POST MOUNTED
PENDANT MOUNTED LIGHT FIXTURE - CEILING MOUNTED
SCONCE TYPE FIXTURE
SINGLE SPOT LIGHT
SINGLE SPOT LIGHT
SURFACE MOUNTED DOWN LIGHT TYPE FIXTURE
TRACK LIGHTING FIXTURE
BRACKET OR SCONCE TYPE FIXTURE
DOWN LIGHT WALL WASH TYPE FIXTURE
TIME CLOCK
LIGHTING CONTROLS LEGEND
CEILING MTD OCCUPANCY SENSOR
PHOTO CELL
POWER LEGEND
CONNECTION TO VARIABLE VOLUME BOX BY EC
CONNECTION TO AIR COOLED CONDENSING UNIT BY EC
BACK BOX
FINAL CONNECTION BY EC TO DISHWASHER - 120V-1Ø
COMBINATION DISCONNECT SWITCH AND STARTER
CONNECTION TO SOLENOID VALVE BY EC
FUSED DISCONNECT SWITCH
NON-FUSED DISCONNECT SWITCH
ELECTRIC THERMOSTAT BY OTHERS UNLESS NOTED
OTHERWISE AND WIRED BY EC
POWER ENCLOSED CIRCUIT BREAKER
AUTOMATIC TRANSFER SWITCH
FINAL CONNECTION BY EC TO EQUIPMENT
HAND DRYER, 48" ABOVE FINISHED FLOOR, UNLESS NOTED
OTHERWISE
HORIZONTAL UNIT HEATER - 1-60-120V - UNO
JUNCTION BOX
MOTOR
MOTOR OPERATED DAMPER
TRANSFORMER
RECEPTACLES LEGEND
COMBINATION DUPLEX RECEPTACLE/INFORMATION OUTLET
FLUSH MOUNTED IN FLOOR
DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - ABOVE COUNTER
DUPLEX RECEPTACLE - MOUNTED FLUSH IN FLOOR (SEE DETAIL)
DUPLEX RECEPTACLE - POKE-THRU (SEE DETAIL)
DUPLEX RECEPTACLE CONNECTED TO EMERGENCY POWER
SYSTEM
DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE
SINGLE RECEPTACLE
DUPLEX, TAMPER RESISTANT, GROUNDING TYPE RECEPTACLE
TELEVISION POWER OUTLET - 12" BELOW CEILING UNO
3-WAY SWITCH
SWITCH LEGEND
4-WAY SWITCH
LOWER CASE LETTER INDICATES FIXTURES CONTROLLED
IN SWITCH GROUP
IN WALL-TYPE DIMMER, RATING AS NOTED
DOUBLE POLE SWITCH
SINGLE PHASE MANUAL MOTOR SWITCH WITH OVERLOADS
OCCUPANCY SENSOR SWITCH
SWITCH WITH PILOT LIGHT (PILOT LIGHT IS ON WHEN SWITCH
IS IN OFF POSITION)
SINGLE POLE SWITCH
DATA OUTLET
TELECOMMUNICATIONS LEGEND
COMMUNICATION OUTLET
DATA/TELEPHONE OUTLET MOUNTED FLUSH IN FLOOR
TELEPHONE OUTLET - MOUNTED 18" ABOVE FINISHED FLOOR,
UNLESS OTHERWISE NOTED
WALL TELEPHONE OUTLET
TELEVISION OUTLET - MOUNTED 12" BELOW FINISHED
CEILING, UNLESS OTHERWISE NOTED
CT
ANN
F
F S
F FS
IAM
F
F
F SV
FACP
F H
F TS
F L
P
OS
3
4
a
D
2
OS
M
PL
VVB
ACCU
ADO
BB
DW
SV
CB
ATS
HD
M HUH
J
M
M FCU
M MOD
T
AUTOMATIC DOOR OPERATOR
FAN COIL UNIT - 1-60-120V - UNO
F
P
SPECIAL PURPOSE RECEPTACLE
DUPLEX GROUND FAULT INTERRUPTER RECEPTACLE ABOVE
COUNTER
2
AB
GFI
TR
TV
AB
GFI
W
VT
WAP WIRELESS ACCESS POINT DATA OUTLET
TYPICAL FLUORESCENT PENDANT MOUNTED FIXTURE
TYPICAL FLUORESCENT RECESSED FIXTURE
TYPICAL FLUORESCENT SURFACE MOUNTED FIXTURE
TYPICAL FLUORESCENT WALL MOUNTED FIXTURE
MISCELLANEOUS ELECTRICAL LEGEND
INDICATES NOTES ELSEWHERE
PHASE
SWITCH LEG
BRANCH CIRCUIT
SWITCHED CIRCUIT
HOMERUN TO PANEL BOARD - 3 #12-3/4"C UNO
ELECTRICAL PANEL BOARD - SURFACE MOUNTED
Ø
F S
DOUBLE FACE EXIT SIGN
SINGLE FACE EXIT SIGN
TYPICAL FLUORESCENT RECESSED EMERGENCY FIXTURE
DUAL HEAD EMERGENCY LIGHT
1
ELECTRICAL PANEL BOARD - RECESSED
CO2
DUPLEX RECEPTACLE W/ TWO INTEGRAL USB PORTSUSB
DUPLEX GFCI TYPE RECEPTACLE MOUNTED IN WEATHERPROOF
"WHILE-IN-USE" COVER
WPGFI
FINAL CONNECTION BY EC TO ELECTRIC FIREPLACE -
120V-1ØFP
FINAL CONNECTION BY EC TO GARBAGE DISPOSAL -
120V-1ØGD
FINAL CONNECTION BY EC TO UNDERCOUNTER ICE
MACHINE - 120V-1ØICE
FINAL CONNECTION BY EC TO ELECTRIC WALL
HEATER - 208V-1Ø
EWH
SCALE:
PROJECT NUMBER: PLOT DATE: 757 FREDERICK ROAD
SUITE 202
CATONSVILLE, MD 21228
(410)461-7763
JSRASSOCIATES.NET
JANE@JSRASSOCIATES.NET
STATUS:
REVISION LOG
REV # DATE DESCRIPTION
DRAWN BY:
SHEET NO.
SHEET NAME
BUILDER:
E001
H.F. LENZ
COMPANY
Engineering
1407 Scalp Avenue
Johnstown, PA 15904
P: 814.269.9300
www.hflenz.com
Headquarters:
2020-0450.01
12/21/2020 1/8" = 1'-0"
ELECTRICAL NOTES,
SYMBOLS, &
ABBREVIATIONS
WSP
PERMITJames Miles2080 W 106th Street, Carmel, IN 46032Willow Haven Senior Homes08/09/21
F
F
F FF F
F
F
F F
F
F F
F
F F
F
F
F
FACP PANEL LP,
240/120-1Ø-3W
PANEL EM, 240/120-1Ø-3W,
GENERAC, 24 POLE,
TRANSFER SWITCH & LOAD
CENTER
FS
FS
ABGFI ABGFI
ABGFI AB GFI ABGFIABGFI
ABGFI
ABGFI
ABGFI
ABGFI
ABGFIABGFI
RP-1 RP-1
RP-1RP-1 RP-1 RP-2
RP-2
RP-2
RP-2 RP-1
HOME
OFFICE
LAUNDRY
FLEX
SPACE
PWDR
RM
LIBRARY
MECH
PANTRY
SRR
HK
SLEEPING
ROOM
VT
TVTV
V T
VT
TV
VT
TV
V T
TV
V T
TV
V T
TV
V T
TV
V T
TV
VT
TV
F
F FF F
F F
F
F
30A
GFI
30A
GFI
AFF
GFI
44"
USB
USB USB
USB
USB USB USB USB USB
USB
USB
V T TV
DW DW
FP
VT
TV
F
F
IAM
IAM
FIRE ALARM SYSTEM
SUPERVISED VALVES
G
GENERAC, 19.5 kW, NATURAL GAS
GENERATOR LOCATED UNDER DECK.
CONTRACTOR SHALL CONFIRM WITH
AHJ AND GENERATOR MANUFACTURER
THAT LOCATION IS ACCEPTABLE AND
THAT ALL REQUIRED CLEARANCES ARE
MET.
WPGFI
F
F
F
F
F
F
F
F
WPGFI
WPGFIWPGFI
1
2
3
KITCHEN
BATHBATH BATH
BATH
BATH BATH BATH BATH BATH BATH
REF REF
ICE
ABGFI
ABGFI
ABGFIABGFI
AB AB
WPGFI
10-POLE CONTACTOR
BEF-1
EWH-1
EWH-1
AHU-1
AHU-2
AHU-3ACCU-1
ACCU-2
ACCU-3
WP
WP
WP
ELECTRIC WALL
HEATER (TYP)
5
108
SLEEPING
ROOM
111
SLEEPING
ROOM
109
SLEEPING
ROOM
107
SLEEPING
ROOM
106
SLEEPING
ROOM
105
SLEEPING
ROOM
104
SLEEPING
ROOM
103
SLEEPING
ROOM
102
SLEEPING
ROOM
101
LIVING
ROOM
DINING
ROOM
ACTIVITY
AREA ENTRY
EWH-1
CABLE TV AND WIFI HEAD END EQUIPMENT SHALL BE LOCATED ON WALL
WITHIN ROOM. COORDINATE EXACT LOCATION WITH OWNER.
KEYNOTES ELSEWHERE THIS DRAWING:
1
2
3
COORDINATE FINAL SINK AND ICE MAKER LOCATIONS W/ SHOP DRAWINGS.
COORDINATE FINAL LOCATION AND MOUNTING HEIGHT OF RECEPTACLES
FOR MICROWAVE AND WALL OVEN W/ SHOP DRAWINGS.
4 SOLATUBE. NO POWER REQUIRED.
5 COORDINATE FINAL LOCATION AND MOUNTING HEIGHT OF RECEPTACLE
FOR INDUCTION COOKTOP W/ SHOP DRAWINGS.
HOME
OFFICE
LAUNDRY
GREETING
RM
MECH
PANTRY
SRR
HK
KITCHEN
BATHBATHBATH
BATH
BATH BATH BATH BATH BATH BATH
LF-7LF-7LF-7
LF-5
LF-4 LF-6 LF-4 LF-6
LF-5 LF-5
LF-4 LF-6 LF-4 LF-6
LF-5
LF-6
LF-5LF-5
LF-6
LF-2LF-2
LF-2LF-2 LF-2
LF-1
LF-2
LF-7LF-7
LF-7
LF-1 LF-1
LF-1LF-1
LF-2
LF-1 LF-1
LF-1 LF-1
LF-2
LF-5
LF-4 LF-6 LF-4 LF-6
LF-5
S LF-5 SS
LF-5
LF-13 OSLF-13
LF-13
SPANEL LP,
240/120-1Ø-3W
PANEL EM, 240/120-1Ø-3W,
GENERAC, 24 POLE,
TRANSFER SWITCH & LOAD
CENTER
LF-13SSLF-6
LF-4
LF-6
LF-4
LF-1
LF-2
LF-2
LF-2A
LF-1
LF-1
LF-1
LF-1
LF-1 LF-2A
LF-1
LF-1
LF-9 LF-1 LF-10
LF-1
LF-1
LF-1
LF-8 LF-810-POLE
CONTACTOR
LF-6A
LF-6A
LF-6B
S
LF-1A LF-1A
LF-1A LF-1A
LF-1A
OS OS
LF-1LF-1
LF-1 LF-1 SLF-1 LF-1
LF-1 LF-1
LF-11
LF-11
CT
LF-1
LF-10
LF-10
LF-1
LF-1 LF-1
LF-1 LF-1
LF-1
LF-1
LF-9
LF-1 LF-1 LF-1
LF-1 LF-1 LF-1 LF-1 LF-1
LF-1
LF-1LF-1 LF-1
LF-1 LF-1 LF-1 LF-1
LF-9
LF-1 LF-1 LF-1
LF-2A
LF-1LF-1 LF-1
LF-1 LF-1
LF-1
LF-1A LF-1A
LF-1A LF-1ALF-1ALF-1A LF-1A
LF-1A LF-1A LF-1A
LF-4LF-4 LF-1
LF-1
LF-1 LF-1 LF-1
LF-1 LF-1
LF-1 LF-1 LF-1
LF-1 LF-1 LF-1 LF-1
LF-1 LF-1
LF-1
LF-1 LF-1
LF-1 LF-1
LF-1 LF-1
LF-1
LF-1
LF-1 LF-1
LF-1 LF-1
LF-1 LF-1
LF-18
LF-18
LF-18 LF-18 LF-18 LF-18
LF-18 LF-18 LF-18
LF-11 LF-11
4
4
4 4 4
LF-3
LF-3
LF-3 LF-3
LF-3LF-8LF-8LF-8 LF-8L
F
-
8 LF-8
LF-8LF-8FLEX
SPACE
LIVING
ROOM
DINING
ROOM
ACTIVITY
AREA
ENTRY
SLEEPING
ROOM
106
SLEEPING
ROOM
105
SLEEPING
ROOM
104
SLEEPING
ROOM
103
SLEEPING
ROOM
102
SLEEPING
ROOM
101
SLEEPING
ROOM
108
SLEEPING
ROOM
107
SLEEPING
ROOM
111
SLEEPING
ROOM
109 LF-14
LF-14
SLEEPING
ROOM
LF-7
LF-1LF-1
LF-1
LF-1
LF-2 SSTO RESIDENT
BATH LTG CKT
TO 20A-1P-CB IN PNL LP
OR NEXT RESIDENT RM
LF-818"
SEE FULL PLAN FOR
ALL LOCATIONS
FIXTURE PROVIDED
W/ ON / OFF MOTION
SENSOR.
BATH
LF-5
LF-4 LF-6
SSSOS S
TO RESIDENT RM
LTG CKT (TYP)
SHOWER
LT SW
NIGHTLIGHT SW
ROOM LT SW
FAN SW HEATER SW
S
SCALE:
PROJECT NUMBER:PLOT DATE: 757 FREDERICK ROAD
SUITE 202
CATONSVILLE, MD 21228
(410)461-7763
JSRASSOCIATES.NET
JANE@JSRASSOCIATES.NET
STATUS:
REVISION LOG
REV # DATE DESCRIPTION
DRAWN BY:
SHEET NO.
SHEET NAME
BUILDER:
E101
H.F. LENZ
COMPANY
Engineering
1407 Scalp Avenue
Johnstown, PA 15904
P: 814.269.9300
www.hflenz.com
Headquarters:
2020-0450.01
12/21/2020 1/8" = 1'-0"
FIRST FLOOR POWER PLAN
WSP
PERMIT
2
ELECTRICAL - FIRST FLOOR PLAN - POWER & SIGNAL
Scale: 1/8" = 1'-0"4' 8' 16'0
1
ELECTRICAL - FIRST FLOOR REFLECTED CEILING PLAN - LIGHTING
Scale: 1/8" = 1'-0"4' 8' 16'0
3
TYPICAL BATH LTG FLOOR PLAN
Scale: 1/4" = 1'-0"
4
TYPICAL SLEEPING RM LTG FLOOR PLAN
Scale: 1/4" = 1'-0" 0 2' 4' 8'
0 2' 4' 8' James Miles2080 W 106th Street, Carmel, IN 46032Willow Haven Senior Homes08/09/21
LINE VOLTAGE CEILING SENSOR
(DUAL TECH)5
NOT TO SCALE
W/ DUAL TECHNOLOGY
CEILING SENSOR
LINE VOLTAGE
WHITE
SWITCH
BLACK
LOAD
H N
BLACK
LINE VOLTAGE WALL SWITCH
SENSOR (DUAL TECH) 4
NOT TO SCALE
WALL SWITCH SENSOR
GREEN
BLACK LOAD
BLACK H
N
W/ DUAL TECHNOLOGY
TYPICAL FIRE ALARM RISER DIAGRAM 1 NOT TO SCALE
TYPICAL FIRE ALARM DEVICE MOUNTING DETAIL2 NOT TO SCALE
FIRE FIRE
FIRE ALARM
PULL DOWN
4"
WALL MOUNTED
SMOKE/HEAT
DETECTOR
NEVER HERE
12" MAX
CEILING MOUNTED
SMOKE/HEAT
DETECTOR
24" TO TOP OF LENS. MIN
DISTANCE HANDICAP
BEDROOM STROBE
SYNCHRONIZE
MORE THAN TWO
APPLIANCES IN ANY
FIELD OF VIEW
80" (ADA)80" (MIN NFPA)AUDIO/VISUAL (A/V) AND
VOICE ONLY (V/O)
DEVICES
MANUAL
PULL
STATION
48" MAX (ADA)42" MIN/54" MAX(NFPA)FINISHED
FLOOR
SIDE
WALL
96" MAX
(NFPA)
AFF
FIREMANS
PHONE
JACK
CEILING
MAGNETIC
DOOR
HOLDER
6"
DOOR
WIDTH
LESS 3"
TO EXIT DOOR
5' MAX
FINISHED
WALL
3' MIN
4"
A/C SUPPLY
OR RETURN
DIFFUSER
ACCEPTED HERE
NOTE:
MEASUREMENTS SHOWN ARE
TO THE CLOSEST EDGE OF
THE DETECTOR
80" MIN (IBC)96" MAX (IBC)NOTE:
REFER TO THE PROPER DEVICE
INSTALLATION INSTRUCTIONS FOR
BACKBOX MOUNTING HEIGHT.
NUMBER OF CONDUCTORS
AS REQ'D BY EQUIPMENT
MANUFACTURER
(NORMAL-EMERGENCY)
120V CIRCUIT
ADDRESSIBLE INPUT MODULE (IAM)
1 #18 (TWISTED/SHIELDED PAIR)-1/2"C
2 #12 (THHN)-1/2"CB
IAM
A
B
A F F S IAM
F FS FSV
IAM
B F
A A A A
C C
A
1 #18 (TWISTED/SHEILDED PAIR)X
AND 2 #14 (THHN)-1/2"C
C
MAIN FIRE
ALARM CONTROL
PANEL
END OF LINE RESISTOR
ANN X
C
F
F S
FIRE ALARM CONTROL PANEL
PROVIDE AT LOCATION OF MAIN
TO LOCAL INITIATION CIRCUIT.A
1. PULL STATIONS, SMOKE DETECTORS, HEAT
DETECTORS SHALL BE ADDRESSIBLE.
2. PROVIDED GALVANIZED INTERLOCKING STEEL STRIP
(RED STRIPED) TYPE MC CABLE FOR ALL FIRE ALARM
CIRCUITS. CABLE ASSEMBLY SHALL BE UL LISTED
FOR FIRE ALARM CIRCUIT APPLICATIONS.
3. CABLE SIZE AND QUANTITY SHOWN FOR
DIAGRAMMATICAL PURPOSES ONLY, PROVIDE ONLY
MANUFACTURERS RECEMMENDED CABLING.
F S F S
TO ADDITIONAL DEVICES. CONSULT
MANUFACTURER ON NUMBER OF
CIRCUITS REQUIRED.
TO ADDITIONAL DEVICES. CONSULT
MANUFACTURER ON NUMBER OF
CIRCUITS REQUIRED.
TYPICAL BATHROOM SWITCH FACEPLATE LAYOUT 3 NOT TO SCALE
NIGHTLIGHTOVERHEAD/
MIRROR
FAN
OCCUPANCY SENSOR
CONTACT WIRING DIAGRAM 6 NOT TO SCALE
J RP-2
SLEEPING RM
J RP-1
SLEEPING RM
J RP-2
SLEEPING RM
J RP-2
SLEEPING RM
J RP-1
SLEEPING RM
J RP-2
SLEEPING RM
J RP-1
J RP-1
J RP-1
J RP-1
SPARE
SPARE
RELAY
DIGITAL
TIME CLOCK
TORK (NSI INDUSTRIES)
CAT. No. DGM100A
120V-1Ø
HOT
NEUTRAL
10-POLE CONTACTOR
EATON, CAT No. ECC04C1AAA
ELECTRICALLY OPERATED/
MECHANICALLY HELD
240V-1Ø, BRANCH
CIRCUITS CONTROLLED
BY CONTACTOR
SLEEPING RM
SLEEPING RM
SLEEPING RM
SLEEPING RM
SCALE:
PROJECT NUMBER:PLOT DATE: 757 FREDERICK ROAD
SUITE 202
CATONSVILLE, MD 21228
(410)461-7763
JSRASSOCIATES.NET
JANE@JSRASSOCIATES.NET
STATUS:
REVISION LOG
REV # DATE DESCRIPTION
DRAWN BY:
SHEET NO.
SHEET NAME
BUILDER:
E501
H.F. LENZ
COMPANY
Engineering
1407 Scalp Avenue
Johnstown, PA 15904
P: 814.269.9300
www.hflenz.com
Headquarters:
2020-0450.01
12/21/2020 1/8" = 1'-0"
ELECTRICAL DETAILS
WSP
PERMITJames Miles2080 W 106th Street, Carmel, IN 46032Willow Haven Senior Homes08/09/21
LIGHTING NOTES:
1. WALA LAMPS SHALL BE CONTROLLED THROUGH ONLINE APP.
2. CONTRACTOR SHALL PERFORM LIGHTING CALCULATIONS TO CONFIRM ALL LIGHTING LEVELS ARE AS REQUIRED BY
THE ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA) AND ALL APPLICABLE CODES.
SCALE:
PROJECT NUMBER: PLOT DATE: 757 FREDERICK ROAD
SUITE 202
CATONSVILLE, MD 21228
(410)461-7763
JSRASSOCIATES.NET
JANE@JSRASSOCIATES.NET
STATUS:
REVISION LOG
REV # DATE DESCRIPTION
DRAWN BY:
SHEET NO.
SHEET NAME
BUILDER:
E601
H.F. LENZ
COMPANY
Engineering
1407 Scalp Avenue
Johnstown, PA 15904
P: 814.269.9300
www.hflenz.com
Headquarters:
2020-0450.01
12/21/2020 1/8" = 1'-0"
ELECTRICAL
SCHEDULES &
DIAGRAMS
WSP
PERMITJames Miles2080 W 106th Street, Carmel, IN 46032Willow Haven Senior Homes08/09/21