ELECTRICAL PLAN
E111
PROVIDE POWER AS REQUIRED AT HERCULITE DOOR FOR CARD
READER (CARD READER BY TENANT'S SECURITY VENDOR) AND
MAG-LOCK. COORDINATE WITH TENANT'S SECURITY
CONTRACTOR. SEE DOOR SCHEDULE FOR MORE DETAILS.
PROVIDE JUNCTION BOX AND DATA FOR TENANT'S FURNITURE
SYSTEM. COORDINATE EXACT LOCATION WITH TENANT'S
FURNITURE VENDOR.
PROVIDE POWER AND DATA FOR TENANT'S WALL MOUNTED
TELEVISION AT HEIGHT NOTED ON PLAN. COORDINATE EXACT
LOCATION WITH TENANT.
PROVIDE FLUSH MOUNT FLOOR CORE WITH POKE THRU DEVICE
FOR ELECTRICAL AND DATA WITH CONDUIT CONNECTION TO
WALL MOUNTED TV. COORDINATE WITH TENANTS FURNITURE
VENDOR ON EXACT LOCATION. PROVIDE POKE THRU DEVICE
SUBMITTAL TO TENANT FOR APPROVAL PRIOR TO ORDERING.
PROVIDE DEDICATED POWER OUTLET IN RECESSED BOX INSET
INTO CABINET/ WALL FOR TENANT'S MICROWAVE, CENTERED AT
24" AFF.
PROVIDE POWER AT THIS LOCATION FOR TENANT'S DISHWASHER.
ELECTRICAL OUTLET TO BE INSTALLED AT APPROXIMATELY 8" AFF IN
FRONT FACE OF BUILT-IN BENCH.
PLAN NOTES
ELECTRICAL PLAN
LEGEND
DESCRIPTIONDATE
ISSUE
07.07.21 REVIEW SET
07.12.21 PERMIT SET
REVISIONS
DESCRIPTIONMARK DATE DB
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700www.schottdesign.comPROJECT NUMBER
DRAWN BYPROJ. MGR REALYNCSUITE 250350 VETERANS WAY, CARMEL, IN 46032ASAS
2021.077
2ND FLOOR
N0 2' 4' 8' 16'
1. TENANT'S FURNITURE VENDOR IS RESPONSIBLE FOR INSTALLATION OF
FURNITURE AND FIELD VERIFICATION OF ALL CRITICAL DIMENSIONS.
2. ALL OUTLETS ARE TO INSTALLED 18" MIN. A.F.F. TO THE CENTER OF
THE DEVICE PER ADA GUIDELINES UNLESS NOTED OTHERWISE. ALL
EXISTING AND NEW DEVICES AND FACE PLATES TO BE WHITE.
3. REFER TO DOOR SCHEDULE AND COORDINATE WITH
TENANT/OWNER REGARDING POWER LOCATIONS TO
ACCOMMODATE ELECTRIC STRIKES, CARD READERS AND/OR
MAG-LOCKS. CARD READERS ARE TYPICALLY INSTALLED BY THE
TENANT'S SECURITY CONTRACTOR AND NOT SPECIFIED BY SDI.
4. CONTRACTOR TO PROVIDE GFCI OUTLET FOR WATER HEATER AND
AUTOMATIC SHUTOFF VALVES AS REQUIRED.
5. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED
TO ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES
AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE
EXISTING ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL
CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL
WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND
MUST COMPLY WITH ALL APPLICABLE CODES.
GENERAL NOTES
DED
POWER OUTLET, DUPLEX
NEW CONSTRUCTION EXISTING TO REMAIN
POWER OUTLET,
QUADRUPLEX
JUNCTION BOX
POWER OUTLET, DUPLEX
POWER OUTLET,
QUADRUPLEX
JUNCTION BOX
BOX, BLANK COVER PLATE
BOX, OPEN
BOX, BLANK COVER PLATE
BOX, OPEN
PROVIDE JUNCTION BOX
ABOVE CEILING FOR
POWER POLE
CONNECTION. POWER
POLE BY OTHERS.
POWER AND DATA POLE
FLOOR BOX WITH POWER
AND DATA, FLUSH
MOUNTED
FLOOR BOX WITH
JUNCTION BOX AND
DATA, FLUSH MOUNTED
FLOOR BOX WITH POWER
AND DATA, FLUSH
MOUNTED
FLOOR BOX WITH
JUNCTION BOX AND
DATA, FLUSH MOUNTED
DEDICATED CIRCUIT
DATA/COMMUNICATION
OUTLET (PROVIDE BOX
AND PULL STRING ONLY)
DATA/COMMUNICATION
OUTLET
GFCI GROUND FAULT CIRCUIT
INTERRUPT OUTLET
HEIGHT OF ELECTRICAL
OR DATA DEVICE
CEILING MOUNTED
JUNCTION BOX
CEILING MOUNTED
JUNCTION BOX
J
J
B
O
J
+42"
AREA NOT IN CONTRACT
AREA OF WORK