HomeMy WebLinkAboutA121 Reflected Ceiling PlanSNSNSNSNSNSNDSNSNSNSN4SN4SN4ELNELN ELNELNSN10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 9'-0" 9'-0" 9'-0" 9'-0" 10'-0" 9'-0" REFLECTED CEILING PLAN A121 CONTROL ENTRY/COLLABORATION 201, CAFE 209 AND OPEN OFFICE 210 LIGHTING WITH 4-WAY SWITCH AT THIS LOCATION. PROVIDE MULTIPLE SWITCHES AS REQUIRED. IN AREA TO REMAIN EXPOSED TO DECK, CLEAN ALL EXPOSED SURFACES AND PREPARE FOR DRYFALL PAINT (PT5) AS NOTED ON PLAN PER MANUFACTURER'S RECOMMENDATIONS. PAINT EXISTING EXPOSED CEILING DECK, EXPOSED DUCTWORK, SPRINKLER PIPING, JUNCTION BOXES, CONDUIT, STRUCTURAL BEAMS AND FIREPROOFING IN ACCORDANCE WITH NFPA 13 6.3.8. PROVIDE RIGID SPIRAL DUCT AND RECTANGULAR SUPPLY DIFFUSERS AS REQUIRED IN THIS AREA. TRANSITION FROM CEILING GRID TO EXPOSED CEILING TO BE A 5" WIDE DRYWALL BULKHEAD EXTENDING FROM 8'-11" AFF TO DECK. TRANSITION TO BE A CLEAN VERTICAL BULKHEAD, FINISHED SUCH THAT CONTRASTING PAINT COLORS CAN EASILY AND CLEANLY CUT AT WALL TO CEILING LINE. VERTICAL FACE OF DRYWALL TO BE PAINTED COLOR OF ADJACENT WALL. EDGE OF BULKHEAD TO ALIGN WITH CORNER OF WALL AS SHOWN. PROVIDE DRYWALL BULKHEAD AT 8'-0" AFF AT THIS LOCATION. ALIGN EDGES WITH CORNERS OF WALLS AS SHOWN. ALL FACES OF BULKHEAD TO BE PAINTED (PT_). PLAN NOTES LIGHT CIRCUIT LIGHT SWITCH, DIMMER LIGHT SWITCH, 3-WAY LIGHT SWITCH ND N N3 BUILDING STANDARD EXIT LIGHT FIXTURE RECESSED LIGHT FIXTURE LIGHT FIXTURE, 2'x2', LED METALUX CRUZ RELOCATED DIFFUSER, LAY-IN, 4"x4' RELOCATED DIFFUSER, LAY-IN, 1'x4' RELOCATED DIFFUSER, LAY-IN, 2'x2' CEILING GRID, SUSPENDED, 2'x2' NEW OR RELOCATED LINEAR SUSPENDED LED: FOCAL POINT, VERVE IV, FL40, 3500K, FINISH: MATTE SATIN WHITE, LENGTHS VARY (SEE PLAN); BOTTOM OF FIXTURES MOUNTED AT 9'-0" AFF TRACK LIGHT: CONTECH LIGHTING TL1 SERIES, COLOR: WHITE TRACK HEADS: CTL905 SERIES, COLOR: WHITE (ACTUAL NUMBER OF TRACK HEADS TBD; COORDINATE WITH SPECIFIED LIGHTING) TRACK MOUNTED AT 9'-0" AFF GYPSUM BOARD CEILING LEGEND REFLECTED CEILING PLAN DESCRIPTIONDATE ISSUE 07.07.21 REVIEW SET 07.12.21 PERMIT SET REVISIONS DESCRIPTIONMARK DATE DB THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700www.schottdesign.comPROJECT NUMBER DRAWN BYPROJ. MGR REALYNCSUITE 250350 VETERANS WAY, CARMEL, IN 46032ASAS 2021.077 2ND FLOOR N0 2' 4' 8' 16' BUILDING STANDARD EMERGENCY LIGHT FIXTURE MECHANICAL DIFFUSER RELOCATION A121 1 *REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION EXISTING VAV BOXES OR HEAT PUMP AND MAIN SUPPLY DUCTS TO REMAIN RELOCATE DIFFUSERS & FLEXDUCT IF REQUIRED VAV / HEAT PUMP EXHAUST FAN, 2'x2' EXPOSED TO DECK A121 1SWITCH, EXHAUST FANNE 1. WHERE NEW CEILING GRID IS SHOWN, PROVIDE BUILDING STANDARD 2X2 GRID AND TILE AT HEIGHT SHOWN ON PLAN. 2. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS, CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE. 3. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1, CONTRACTOR MUST NOTIFY SDI. OVER 50% OF THE LIGHTING WILL BE REPLACED WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL NEED TO BE MET. 4. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS, PROVIDE COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH A ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF INCLUDED AREA IS DETECTED. PROVIDE CEILING MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED. 5. ALL EXISTING AND NEW DEVICES AND FACE PLATES TO BE WHITE. WHERE POSSIBLE, GANG MULTIPLE SWITCHES TO ACCOMMODATE MULTI-SWITCH PLATE WHEN SWITCHES ARE SHOWN ADJACENT ON PLAN. 6. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH ALL APPLICABLE CODES. GENERAL NOTES 1. MECHANICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE DRAWINGS. NO NEW MAIN MECHANICAL APPLIANCES OR MAIN EQUIPMENT ARE BEING PROVIDED. ALL MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND FLEX DUCT PER NEW WALL LAYOUT. NO NEW HARD DUCTWORK OR EQUIPMENT IS BEING ADDED;  MECHANICAL CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH THE INDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES. MECHANICAL NOTES AREA NOT IN CONTRACT AREA OF WORK 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 12'-0" 8'-0" 8'-0" A A B A CERNO, GAVIOTA PENDANT DIAMETER: 4-0" SUSPENSION: ANGLED CABLE RING WALLS: 001 WALNUT SEAM PLATE: 049 TEXTURED BLACK POWDER COAT LIGHT DIRECTION: DIRECT LAMP: 3500K LED BOTTOM OF FIXTURE MOUNTED AT 7'-0" AFF B CERNO, PURA PENDANT DIAMETER: 30" WOOD BODY: WALNUT (CM-001) SHADE: FROSTED POLYMER (CM-051) LAMP: 3500K LED FIXTURE MOUNTING HEIGHT TO BE DETERMINED IN FIELD 08/13/21