HomeMy WebLinkAboutNapleton Hyuandi - HVAC and Plumbing Symbols - MP001MP001 MECHANICAL SPECIFICATIONS GENERAL 1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE BID IN STRICT ACCORDANCE WITH DESIGN BASIS EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS OF DESIGN. SUBSTITUTE ITEMS WILL BE COMPARED AGAINST DESIGN BASIS DURING SUBMITTAL PROCESS. ENGINEER RESERVES THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS. 2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL ENERGY CONSUMING OR PRODUCING ITEMS AND FOR ALL DUCT ACCESSORIES, INSULATION, VAV BOXES, REGISTERS, GRILLES, DIFFUSERS AND LOUVERS. SUBMITTALS SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS, CONTRACTORS NAME, PROJECT NAME. CLEARLY INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE ITEM. 3. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL REQUIRED ELECTRICAL SUPPORT NEEDED FROM THE ELECTRICAL CONTRACTOR. ENSURE ALL SUBMITTALS FOR POWERED COMPONENTS AND CONTROLS ARE PROVIDED AND FULLY COORDINATED WITH ELECTRICAL CONTRACTORS. 4. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY WAY AFFECT THE EXECUTION OF HIS WORK. HE SHALL ALSO EXAMINE THE DRAWINGS AND SPECIFICATIONS FOR OTHER BRANCHES OF WORK MAKING REFERENCE TO THEM FOR DETAILS OF EXISTING BUILDING CONDITIONS. NO EXTRAS WILL BE ALLOWED FOR FAILURE TO INCLUDE ALL REQUIRED WORK IN THE BID. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIALS ENTERING INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE. 5. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE EXACT QUANTITIES, LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS SHOW GENERAL INTENT OF SYSTEMS. M.C. SHALL PROVIDE AND PAY FOR ALL REQUIRED PERMITS. 6. PRIOR TO WORK COORDINATE ALL OPENINGS AND INSTALLATIONS OF DUCT, PIPING, EQUIPMENT, CONTROLS, DIFFUSERS AND GRILLES WITH G.C. AND OTHER TRADES. PROVIDE INSTALLATIONS WITH PROPER MANUFACTURERS RECOMMENDED CLEARANCES. 7. UPON COMPLETION OF THE MECHANICAL INSTALLATION, DEMONSTRATE TO THE ENGINEER AND THE OWNER'S SATISFACTION THAT THE SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS AND APPLICABLE CODES. DEMONSTRATE THE DYNAMIC OPERATION OF EACH SYSTEM. VERIFY PROPER OPERATION OF EQUIPMENT, FILTERS ARE CLEAN AND COMPONENTS OF THE SYSTEM ARE INSTALLED AND ADJUSTED IN FULL ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS. 8. ALL WORK SHALL BE IN FULL ACCORDANCE WITH 2014 INDIANA MECHANICAL CODE (2012 INTERNATIONAL MECHANICAL CODE), INDIANA ENERGY CODE (ASHRAE 90.1-2007) PERTINENT STATE, COUNTY, CITY CODES AND ORDINANCES AND INDIANA AMENDMENTS. 9. MECHANICAL CONTRACTOR SHALL ENSURE EMPLOYEES ARE MEETING AND DOCUMENTING ALL OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS REQUIRED BY LAW AND BY CONTRACT. PERSONAL PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND UTILIZED AS REQUIRED. MECHANICAL CONTRACTOR SHALL PAY ALL FINES LEVIED BY OSHA FOR FAILURE TO COMPLY WITH OSHA REQUIREMENTS. 10. INSTALL ALL EQUIPMENT, DUCTWORK AND PIPING AS HIGH AS POSSIBLE. PRIOR TO ROUGH-IN COORDINATE ELEVATIONS WITH OTHER TRADES. WHERE VISIBLE, ORIENT PERPENDICULAR AND/OR PARALLEL TO STRUCTURE. EQUIPMENT 1. PROVIDE EQUIPMENT AS SHOWN ON EQUIPMENT SCHEDULES AND PLAN NOTES. SUBSTITUTIONS TO LISTED EQUIPMENT SHALL BE AT RISK OF CONTRACTOR. SUBSTITUTIONS SHALL ONLY BE ALLOWED IF ITEMS ARE EQUAL IN ALL ASPECTS. 2. PROVIDE SUBMITTALS TO ELECTRICIAN AS REQUIRED FOR COORDINATION OF ALL ELECTRICAL POWER WIRING. INCLUDE WIRING DIAGRAMS AND CABLING REQUIREMENTS FOR REFERENCE. COORDINATE ALL INTERLOCKS AS NEEDED. PROVIDE SINGLE POINT CONNECTION KITS AS NEEDED. 3. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND CLEARANCE REQUIREMENTS. PROVIDE ALL REQUIRED MOUNTING OR HOUSEKEEPING PADS. G.C. SHALL PROVIDE LEVEL GRADE FOR EXTERIOR MOUNTED EQUIPMENT. M.C. SHALL PROVIDE ALL HOISTING AND RIGGING NEEDED TO SET ALL HVAC EQUIPMENT. 4. ALL EQUIPMENT SHALL BE INSTALLED AS NEEDED TO PREVENT OBJECTIONABLE NOISE AND/OR VIBRATION. M.C. SHALL PROVIDE VIBRATION PADS, SPRING ISOLATORS, ATTENUATORS AND ACCESSORIES AS NEEDED. DUCTWORK 1. CONCEALED ROUND DUCTWORK SHALL BE CONSTRUCTED PER SMACNA LOW PRESSURE STANDARDS 1" PRESSURE CLASS, 5' MAXIMUM JOINT LENGTHS, SEAL CLASS B LONGITUDINAL SEAM SNAP LOCK PIPE AND ADJUSTABLE FITTINGS. 2. EXPOSED ROUND DUCTWORK (OR WHERE SPIRAL IS INDICATED ON THE PLANS) SHALL BE LINDAB OR EQUAL GALVANIZED STEEL CONFORMING TO ASTM STANDARDS A653 AND A924 GASKETED SPIRAL DUCTING WITH NO SEALER. EDPM RUBBER GASKET SHALL BE U.L. CLASSIFIED RATING OF FLAME SPREAD 0 AND SMOKE DEVELOPED 5 IN ACCORDANCE WITH ASTM STANDARD E84-91A SMACNA LEAKAGE CLASS 3. FITTINGS SHALL BE MANUFACTURED USING ONE OR MORE OF THE FOLLOWING CONSTRUCTION METHODS: OVERLAPPED EDGES STITCH WELDED ALONG THE ENTIRE LENGTH OF THE FITTING, STANDING SEAM GORE LOCKED AND INTERNALLY SEALED, BUTTON PUNCHED AND INTERNALLY SEALED. ELBOWS 3-INCH THROUGH 12-INCH DIAMETER WILL BE DIE STAMPED AND CONTINUOUSLY STITCH WELDED. 3. PROVIDE SHEET METAL 90 FOR ALL TURNS GREATER THAN 45 DEGREES. DO NOT USE FLEXIBLE DUCT FOR CHANGES IN DIRECTION GREATER THAN 45 DEGREES. 4. PROVIDE MANUAL BALANCING DAMPERS FOR ALL SUPPLY AIR RUNS. ROUND DAMPERS SHALL BE SECURED ON BOTH SIDES OF DUCT AND SHALL CONTAIN LOCKING HANDLE. SPIRAL DUCTS SHALL USE SPIRAL STYLE DAMPERS WITH FULL WIDTH SHAFTS AND NYLON BEARINGS AT EACH END. RECTANGULAR DUCTS SHALL USE MULTI OR SINGLE BLADE WELDED FRAMED DAMPERS WITH JACK SHAFTS AND LOCKING HANDLE. INSTALL NYLON RIBBON ON ALL DAMPER HANDLES LOCATED IN INSULATED DUCTING. DO NOT INSTALL DAMPERS IN NON ACCESSIBLE LOCATIONS. PROVIDE INTEGRAL DAMPERS WITH DIFFUSER IN NECK IF NO ACCESSIBLE LOCATION IS POSSIBLE. ALL SUPPLY AIR RUNS SHALL HAVE MEANS OF BALANCE. RETURN AND EXHAUST AIR RUNS SHALL CONTAIN DAMPERS WHERE SHOWN ON PLANS. 5. INSULATED FLEXIBLE DUCTING SHALL NOT EXCEED 25 FEET. ALL FLEX SHALL BE LISTED FLEXIBLE DUCT, FLEXIBLE CONNECTORS ARE NOT ACCEPTABLE. FLEXIBLE DUCT EQUAL TO FLEXIBLE DUCT CLASS 1 AIR DUCT, DOUBLE LAMINATED POLYESTER FILM ON STEEL WIRE REINFORCING, INSULATED WITH SCRIM REINFORCED METALIZED POLYESTER OUTER FIRE RETARDANT JACKET. R-4.2 FOR CONDITIONED SPACES AND R-6.0 FOR ANY SPACES OUTSIDE BUILDING THERMAL ENVELOPE. FLEX DUCTS SHALL NOT BE RUN THROUGH WALLS OR FLOORS. PROVIDE HARD DUCTED SLEEVES AS NEEDED. 6. RECTANGULAR DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH SMACNA LOW PRESSURE DUCT STANDARDS, +/- 1.0" W.C. FROM ASTM A 653/A 653M G-90 COATED GALVANIZED SHEET STEEL. SEAMS SHALL BE PITTSBURGH CONSTRUCTION, NO BUTTON PUNCH OR SNAP LOCK SEAMS ARE ACCEPTABLE. SEAL ALL TRANSVERSE AND LONGITUDINAL SEAMS WITH WATER BASED DUCT SEALER, SEAL CLASS B. GAUGE AND JOINT CLASSIFICATIONS ACCEPTABLE ARE AS FOLLOWS, ALL SECTION LENGTHS ARE 48" MAXIMUM, REFER TO SMACNA RIGIDITY TABLES FOR GAUGES ON LONGER SECTIONS IF REQUIRED: < 12" 26 GAUGE, FLAT S AND DRIVE 12"-24" 24 GAUGE, FLAT S AND DRIVE 25"-34" 22 GAUGE, STANDING S AND FLAT DRIVE 34"-40" 22 GAUGE, STANDING S AND STANDING DRIVE >40" REFER TO SMACNA FOR STANDARDS. 2. DUCT HANGERS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," CHAPTER 5, "HANGERS AND SUPPORTS." PROVIDE GALVANIZED MINIMUM 22 GAUGE 1" WIDE STRAP TO HANG RECTANGULAR DUCTWORK SMALLER THAN 30" WIDE. DUCT HANGERS FOR RECTANGULAR SHEET METAL DUCTS 30" AND LARGER SHALL BE TRAPEZE STYLE USING UNI-STRUT AND 3/8" OR 1/2" ROD. PROVIDE GRIPPLE, DURODYNE OR EQUAL CABLE HANGERS FOR HANGING ROUND DUCTWORK. SUPPORT ALL HANGERS FROM STRUCTURE PER SMACNA STANDARDS.HANGERS FOR SPIRAL DUCTS GREATER THAN 28" IN DIAMETER SHALL BE HUNG WITH ROD AND DUCT CLAMP. FLEXIBLE DUCTING SHALL BE SUPPORTED USING MINIMUM 2" WIDE NYLON STRAP. ALL INTERVALS ARE PER SMACNA. 3. FOR ALL RETURN AIR, PROVIDE OPENINGS, PATHWAYS, TRANSFERS, COORDINATE UNDERCUTS, ETC. AS REQUIRED TO RETURN AIR SUPPLIED TO SPACES BACK TO AIR HANDLING UNIT. DUCT ACCESSORIES 1. COORDINATE WITH ARCHITECTURAL DRAWINGS AND PROVIDE FIRE AND FIRE AND SMOKE DAMPERS AT FIRE RATED ASSEMBLY PENETRATIONS IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE AND WHERE SHOWN ON PLANS. 2. PROVIDE FLASHING MATERIALS AND OR SLEEVES AS REQUIRED FOR ALL DUCT PENETRATIONS OF NON RATED ELEMENTS. EXPOSED PENETRATIONS SHALL BE FLASHED WITH SHEET METAL TIGHT TO WALLS. 3. PROVIDE HIGH EFFICIENCY TAKE OFFS, PEAL AND STICK STYLE ATTACHED TO RECTANGULAR DUCTING WITH SHEET METAL SCREWS FOR ALL ROUND SUPPLY AIR TAKE OFFS AND SADDLES. 4. REGISTERS, GRILLES AND DIFFUSERS SHALL BE EQUIVALENT TO SCHEDULED PRODUCTS. SUBSTITUTION OF RESIDENTIAL STAMPED STYLE PRODUCTS FOR COMMERCIAL PRODUCTS WILL NOT BE ACCEPTED. DUCT INSULATION 1. ALL DUCT INSULATION MATERIALS SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS (ON THE FLAME SPREAD TEST SCALE) AND SMOKE DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST SCALE) OR AS DEFINED BY NFPA 255 STANDARD METHOD OF TESTING OF SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS, LOCAL CODES AND LOCAL AUTHORITIES HAVING JURISDICTION. DUCT WRAP SHALL BE FIBERGLASS MATERIAL PER ASTM C-411,ASTM C-1104,ASTM C665, ASTM C-1338, ASTM E-84, UL723, NFPA 90A,CAN/ULC S102-1188,ASTM C1290, ASTM C553, ASTM C1136. 2. INSULATION: INSTALL ALL INSULATION IN STRICT ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO SAGGING, FRAYED OR TORN INSULATION WILL BE EXCEPTED. UNLESS OTHERWISE NOTED ON PLANS DUCTWORK SHALL BE INSULATED AS FOLLOWS: SA- 1-1/2" FIBERGLASS DUCT WRAP WITH FSK FACING, 75 #/FT3 MINIMUM APPLIED R-3.5. RA NONE REQUIRED UNLESS NOTED ON PLANS. SA/RA IN UNCONDITIONED OR ATTIC SPACES OUTSIDE THE BUILDING INSULATION ENVELOPE; 2" MINIMUM 75 #/FT3, R-6 AS APPLIED FSK DUCT WRAP. SA/RA- IN RETURN AIR PLENUMS OR CONDITIONED SPACES WHERE NOT CONCEALED BY DRYWALL CEILING OR BULKHEAD CONSTRUCTION WITHIN THE BUILDING INSULATION LINE NONE REQUIRED. PIPING 1. PIPING SLEEVES; INTERIOR OR EXTERIOR ABOVE GRADE; GALVANIZED-STEEL-PIPE SLEEVES OR PVC-PIPE SLEEVES. VERIFY, WITH FIRE AUTHORITIES HAVING JURISDICTION, THAT PVC MATERIALS ARE ALLOWED FOR SLEEVES. BELOW GRADE; ALL; MECHANICAL GALVANIZED-STEEL PIPE SLEEVE SYSTEM LIKE LINK-SEAL. ALL SLEEVES SHALL BE FIRE STOPPED OR CAULKED. EXTERIOR SLEEVES SHALL PROVIDE WATER/AIR TIGHT PENETRATION SYSTEM. FIRE STOPPING. 1. FIRE STOPPING SYSTEMS SHALL BE IN FULL COMPLIANCE WITH SECTIONS 714 AND 717 OF THE IBC AND SECTION 607 OF THE IMC. 2. CONTRACTOR SHALL MAKE REFERENCE TO ARCHITECTURAL PLANS AND PROVIDE ALL REQUIRED FIRE STOPPING. 3. CONTRACTOR SHALL PROVIDE AHJ WITH FULL SUBMITTAL INDICATING METHODS OF CONSTRUCTION AND UL LISTINGS FOR EACH PENETRATION SYSTEM USED. 4. DUCTS AND AIR TRANSFER OPENING PENETRATIONS OF ASSEMBLIES REQUIRED TO BE PROTECTED AND IN NON FIRE-RESISTANCE-RATED FLOORS SHALL COMPLY WITH SECTIONS 717. 5. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND CEILING RADIATION DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 607 OF THE IMC. AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND LISTING. 6. ACCESS DOORS SHALL BE PERMITTED IN CEILINGS OF FIRE-RESISTANCE-RATED FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES PROVIDED SUCH DOORS ARE TESTED IN ACCORDANCE WITH ASTM E 119 OR UL 263 AS HORIZONTAL ASSEMBLIES AND LABELED BY AN APPROVED AGENCY FOR SUCH PURPOSE. ALL ACCESS DOORS SHALL BE PROVIDED BY TRADE MAKING PENETRATIONS. CHECK TEST AND START UP REQUIREMENTS 1. ALL HVAC EQUIPMENT INSTALLATIONS SHALL BE VERIFIED AND STARTED UP PER MANUFACTURERS RECOMMENDATIONS. VERIFY ALL MODES OF OPERATION. CONFIGURE ALL CONTROLS AND PROGRAM OCCUPANCIES PER OWNER PROVIDED SCHEDULES. 2. PROVIDE AIR BALANCE BY CONTRACTOR. CONTRACTOR SHALL BALANCE SUPPLY, RETURN, OUTSIDE, RELIEF AND EXHAUST AIR SYSTEMS IN ACCORDANCE WITH CURRENT SMACNA, NEEB OR AABC STANDARDS TO DESIGN VALUES AND PROVIDE WRITTEN REPORT TO ARCHITECT. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL DEVICES, DRIVES, SHEAVES, MOTOR CHANGES AND REWORK AS REQUIRED TO MEET DESIGN REQUIREMENTS. 3. TEMPERATURE CONTROL WORK SHALL BE THE RESPONSIBILITY OF THE HVAC CONTRACTOR. PROVIDE ALL COMPONENTS INCLUDING T/S, T/S WIRE (PLENUM RATED IN RA PLENUMS), SWITCHES, ACTUATORS ETC. AS REQUIRED FOR A COMPLETE SYSTEM. PRIOR TO ROUGH-IN COORDINATE FINAL LOCATION FOR ALL CONTROLS WITH OWNERS REPRESENTATIVE. 4. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION AND MAINTENANCE MANUALS, AIR BALANCE REPORT AND AS BUILT DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER SELECTED PERSONNEL AS REQUESTED AND PROVIDE WARRANTY INFORMATION FOR ALL MANUFACTURERS WARRANTED EQUIPMENT. ABBREVIATIONSSYMBOLS AFF ABOVE FINISHED FLOOR ACCU AIR COOLED CONDENSING UNIT AHU AIR HANDLING UNIT AWH ARCHITECTURAL WALL HEATER BDD BACK DRAFT DAMPER BOD BOTTOM OF DUCT BOB BOTTOM OF BEAM BTUH BRITISH THERMAL UNIT PER HOUR CFM CUBIC FEET PER MINUTE CWH COMMERCIAL WALL HEATER DEG F DEGREES FARENHEIT DB DRY BULB Ø ROUND DUCT EA EACH OR EXHAUST AIR EG EXHAUST GRILLE EADB ENTERING AIR DRY BULB EAWB ENTERING AIR WET BULB EC ELECTRICAL CONTRACTOR ECH ELECTRIC CEILING HEATER EF EXHAUST FAN ESP EXTERNAL STATIC PRESSURE " W.C. EUH ELECTRIC UNIT HEATER EWH ELECTRIC WALL HEATER F FURNACE FC FAN COIL FD FIRE DAMPER FD/SD FIRE AND SMOKE DAMPER FPM FEET PER MINUTE FPVAV FAN POWERED VAV FT FEET FSK FOIL SCRIM VAPOR BARRIER GC GENERAL CONTRACTOR GPM GALLONS PER MINUTE GUH GAS UNIT HEATER HD HOOD HP HEAT PUMP OR HORSE POWER IN INCHES IR INFRA RED LAT LEAVING AIR TEMPERATURE LS LINEAR SLOT DIFFUSER MAN MANUAL MBH 1000 BTUH MC MECHANICAL CONTRACTOR MCC MOTOR CONTROL CENTER MFR MANUFACTURER MUA MAKE UP AIR OA OUTSIDE AIR PC PLUMBING CONTRACTOR DHU DEHUMIDIFICATION UNIT PRV PRESSURE RELIEF VALVE PSI POUNDS PER SQUARE INCH PTAC PACKAGED TERMINAL AIR CONDITIONER RA RETURN AIR RJ ROOF JACK RPM REVOLUTIONS PER MINUTE RTU ROOF TOP UNIT SA SUPPLY AIR TCC TEMPERATURE CONTROL CONTRACTOR TSP TOTAL STATIC PRESSURE UON UNLESS OTHERWISE NOTED VAV VARIABLE AIR VOLUME WC WALL CAP WIC WALK IN COOLER WIF WALK IN FREEZER AIR COOLED CONDENSING UNIT MANUAL VOLUME DAMPER LOCKING WITH SHAFT FIRE DAMPER ROUND MOTORIZED DAMPER M COMBINATION FIRE/SMOKE DAMPER THERMOSTAT EXHAUST GRILLE ROOF EXHAUST FAN TURNING VANES DOUBLE THICKNESS XXX X-# FD FD SD ROOF TOP UNIT W/D W/D HORIZONTAL FURNACE OR FC WITH SECONDARY DRAIN PAN HORIZONTAL AIR COOLED CONDENSING UNIT WALL MOUNTED EXHAUST FAN SUPPLY AIR DIFFUSER RETURN AIR REGISTER OR GRILLE ROUND DIFFUSER LINEAR OR SLOT DIFFUSER CEILING MOUNTED EXHAUST FAN ACCU FC F AC DIRECT DUCT MOUNTED REGISTER DIFFUSER TAG EWHELECTRIC WALL HEATER SQUARE TO ROUND TRANSITION SHEET METAL DUCT WIDTH BY DEPTH LINED SHEET METAL DUCT FREE AREA WIDTH BY DEPTH. ACCESS DOOR SQUARE SHEET METAL 90 PROVIDE WITH DOUBLE THICKNESS TURNING VANES. RADIUS SHEET METAL 90, R=1.5*D ROUND BRANCH DUCT SADDLE ON ROUND DUCT. 45 DEG BRANCH DUCT TAKE OFF ON RECTANGULAR. STRAIGHT ROUND TAP BRANCH DUCT TAKE OFF. M RECTANGULAR MOTORIZED DAMPER BOOT MOUNTED REGISTER MARK CFM T HPOR AIR COOLED HEAT PUMP EF VERTICAL FURNACE OR FC RADIANT FIRE DAMPER RFD THERMOSTAT IN LOCK BOX SENSORS, TEMPERATURE, HUMIDITY CARBON MONOXIDE SENSOR CARBON DIOXIDE SENSOR NITROGEN OXIDE SENSOR NO CO2 CO S T DUCT SMOKE DETECTOR SD H MOTOR CONTROL CENTER MCC ACCESS DOOR HVAC AND PLUMBING ABBREVIATIONS, SYMBOLS, SPECIFICATIONS, & SCHEDULES DRAWING ISSUE HISTORY BID / PERMIT ISSUE: CONSTRUCTION SET: COPYRIGHT 2021 210519 JP JP AS NOTED PROJECT NO: DRAWING DATE: DRAWN BY: CHECKED BY: DRAWING SCALE: HYUNDAI OF CARMELOFFICE REMODEL4200 E 96th STREETCARMEL, INDIANAA u t o m o t i v e G r o u pN MEP Consulting Engineers262 Tradewinds DriveSanta Rosa BeachFlorida 32459317.506.8151dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP:E:874 Cheltenham DriveAvon IN, 46123South OfficeNorth Office07-09-2021JEFFREY M. PE R KEY07-09-2021 07-09-2021 1. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL ENERGY CONSUMING OR PRODUCING ITEMS AND FOR ALL PLUMBING FIXTURES, VALVES, DRAINS, CLEAN OUTS, PIPING, PIPING ACCESSORIES, INSULATION AND PIPING HANGERS. SUBMITTALS SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS, CONTRACTORS NAME, PROJECT NAME. CLEARLY INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF FORMAT.ENGINEER RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE ITEM. 2. PLUMBING WORK SHALL BE COMPLETE IN EVERY DETAIL AND ALL MISCELLANEOUS ITEMS OF MATERIAL AND LABOR NECESSARY TO COMPLETE THE WORK DESCRIBED, SHOWN OR REASONABLY IMPLIED ON DRAWINGS OR SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACT. CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS TO THE WORK WHERE REQUIRED, WHEN SUCH ADJUSTMENTS ARE NECESSARY FOR PROPER OPERATION AND WITHIN THE INTENT OF THE CONTRACT. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIALS ENTERING INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE. 3. ALL WORK SHALL BE IN FULL ACCORDANCE WITH 2012 INDIANA PLUMBING CODE (2006 INTERNATIONAL PLUMBING CODE W/ INDIANA AMENDMENTS), 2007 ASHRAE 90.1 INDIANA ENERGY CODE 2010, PERTINENT STATE, COUNTY, CITY CODES AND ORDINANCES WITH INDIANA AMENDMENTS. 4. PLUMBING CONTRACTOR SHALL VISIT THE SITE AND VIEW ALL EXISTING CONDITIONS BEFORE SUBMITTING A PROPOSAL FOR THE WORK AS DESCRIBED AND SHOWN. NO EXTRAS WILL BE ENTERTAINED FOR FAILURE TO MAKE THIS VISIT. 5. PLUMBING CONTRACTOR SHALL ACCEPT SOLE AND COMPLETE RESPONSIBILITY FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. 6. PLUMBING CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL PLUMBING ROUGH-INS, 7. PIPING TYPES UNLESS OTHERWISE NOTED ON PLANS: WATER WATER TUBING SHALL BE TYPE A PEX WIRSBO, ZURN, NIBCO, OR UPONOR CONFORMING TO ASTM F876, F877, E84, E814, ANSI/UL 263 AND NSF14/61. 100 PSIG AT 180 DEG. BLUE FOR COLD AND RED FOR HOT AND RE-CIRCULATION WHITE FOR GENERIC. FITTINGS SHALL BE PER ASTM F1960 LIKE UPONOR ProPEX COLD EXPANSION, PRESS FIT MECHANICAL JOINTS PER ASTM F2854 OR COPPER CRIMP WITH BRASS OR ENGINEERED PLASTIC FITTINGS. MANIFOLDS WHERE USED SHALL BE LIKE UPONOR ProPEX TYPE L TO ASTM F877 WITH BRASS OR EP BALL VALVES. SEWER/VENT POLYVINYL CHLORIDE SEWER PIPE (PVC): ASTM D2665, ASTM F 1866 SCHEDULE 40 SOLID CORE DRAIN WASTE AND VENT WITH PVC SOCKET WELDED FITTINGS DESIGNED TO FIT PIPING DIAMETERS. ALL PIPING IN RETURN AIR PLENUMS SHALL CONFORM TO REQUIREMENTS FOR PLENUM MATERIALS. 8. DIELECTRIC UNIONS SHALL BE USED TO CONNECT DISSIMILAR METALS OR METAL PIPING SHALL HAVE METAL CONNECTIONS ON EACH END THREADED TO MATCH THE ADJACENT PIPING. METAL COMPONENTS SHALL BE SEPARATED BY A NYLON INSULATOR TO PREVENT CURRENT FLOW BETWEEN DISSIMILAR METALS. UNIONS SHALL BE SUITABLE FOR THE SYSTEM OPERATING PRESSURES AND TEMPERATURE WELD TYPE: ASTM A-234 9. UNLESS OTHERWISE NOTED, ROUTE ALL PIPING AS HIGH AS POSSIBLE AND ROUTE PERPENDICULAR AND/OR PARALLEL TO BUILDING STRUCTURE. PLUMBING SPECIFICATIONS 08/18/21