Loading...
HomeMy WebLinkAboutplan_design_release04292005_modifiedELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm. This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans. Use Internet Browser to View this report, other browsers are not compatible to view this report Page 1/2 CONSTRUCTION DESIGN RELEASE State Form 41191 (R9/5-98) Report Printed on:June 2, 2021 Project number Release date 423094 06/02/21 Construction type Occupancy classification Scope of release SPK, II-B B, REM Type of release Project name Street address City County ARCH ELEC MECH PLUM Standard Element Three 571 Monon Blvd 1st Floor CARMEL HAMILTON To: Owner / Architect / Engineer Design Point Architects George F Small AR19600042 4676 St. John Circle Zionsville IN 46077 Note :(A1A & A1B): In accordance with the affidavit sworn under penalties of perjury in the application for construction design release the plans and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety Commission. Providing false information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a fine up to $10,000. The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions listed below. THIS IS NOT A BUILDING PERMIT. All required local permits and licenses must be obtained prior to beginning construction work. All construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications must be filed with and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and void, if the work authorized is not commenced within one (1) year from the above date. CONDITIONS: ACDS 4G0412AE 14B1600 14W1104A AREL This project has been reviewed under the 2014 Indiana Building Code, 2014 Indiana Fire Code, 2009 Indiana Electrical Code, 2012 Indiana Plumbing Code, 2014 Indiana Mechanical Code, 2014 Indiana Fuel Gas Code, 2010 Indiana Accessibility Chapter 11 (ICC A117.1 2009), and the 2010 Indiana Energy Conservation Code (ASHRAE 90.1 2007) The proposed building, addition, or remodel shall not put the existing building in noncompliance or into further noncompliance in accordance with 675 IAC 12-4-12. Buildings, or portions thereof, shall be designed and constructed to sustain all dead, live, and environmental loads in accordance with Chapter 16, IBC (675 IAC 13-2.6). Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building, in accordance with Section 1104, IFC (675 IAC 22-2.5). NOTE: Flexible air ducts, both metallic and nonmetallic, shall comply with Sections 603.6.1, 603.6.1.1, 603.6.3 and 603.6.4, IMC. Flexible air connectors, both metallic and nonmetallic, shall comply with Sections 603.6.2 through 603.6.4, IMC, in accordance with Section 603.6, IMC. Pursuant to 675 IAC 12-6-21, the issuance of a design release does not relieve the owner from required compliance with all applicable rules of the commission, even if noncompliant conditions appear in the plans and specifications that have been filed with the division. The owner is responsible for correcting any and all areas of noncompliance even if they are discovered subsequent to the issuing of this design release. Indiana Department of Homeland Security DIVISION OF FIRE & BUILDING SAFETY PLAN REVIEW DIVISION 402 W. Washington St., Room E245 Indianapolis, IN 46204 Fax & e-mail: SUPPORT HOOSIER SAFETY Available At Your Local Licence Branch In accordance with Section 19 of the General Administrative Rules (675 IAC 12-6-19) a complete set of plans and specifications that conform exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a copy of the design release. 0000000000, gsmall@designpointarchitects.com ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm. This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans. Use Internet Browser to View this report, other browsers are not compatible to view this report Page 2/2 This order is effective upon service. If you would like to request informal review of this order, please complete the informal review form located at https://www.in.gov/dhs/4149.htm. Following receipt of this form, the Department may modify or reverse the order, however, a request for an informal review does not extend the deadline for filing a petition for review with the Fire Prevention and Building Safety Commission (Commission). Additionally, if you have any questions regarding this order, you may contact that Department at (317) 232-2222. If you desire a formal administrative review of this order by the Commission, you must comply with the requirements of Indiana Code § 4-21.5-3-7 and file a written petition for review within 15 days of the date this order was served, however, this period is extended to 18 days if service is made by mail. Your petition for review must state facts demonstrating that you are: (1) a person to whom the order is specifically directed; (2) aggrieved or adversely affected by the order; or (3) entitled to review under any law. You may submit your petition by the following methods: U.S. MAIL OR PERSONAL SERVICE ONLINE Fire Prevention and Building Safety Commission By completing the form at c/o Legal Counsel https://www.in.gov/dhs/4148.htm 302 W. Washington Street, Rm. E208 Indianapolis, IN 46204 For additional information about the administrative review process and applicable templates that may be used for filings, visit the following link https://www.in.gov/dhs/appeals.htm. Code review official Address (name,title of local official,street,city,state and ZIP code DESHAWN JORMAN JIM BLANCHARD ONE CIVIC SQUARE CARMEL,IN 46032 DEPT OF COMMUNITY SERVICE Fax & e-mail: 3175712499, jblanchard@carmel.in.gov Indiana State Building Commissioner DJorman@dhs.IN.gov