VALID FOR 1 PERMIT ONLY U.N.O.REMARKS DRWN CHKD DATESCALE:
COPYRIGHT ENGINEERING EXPRESSC:\Users\colby\Engineering Express\Production - Documents\Projects\20-25436 Aluminum Louvered Roof\WP\Drawings & CAD\20-25436n Louvered Roof MPS.dwg07/23/2021 - 1:44pm colby INIT ISSUE (18-5654) RWN TSB 8/24/182018 IBC EPR RWN 5/11/20DETAIL UPDATES EPR RWN 7/22/202021 UPDATE CCB AEM 7/13/21- - - -PHOTOCOPIES NOT
TO BE USED6" TYP.DEPTH PERDESIGN SCHEDULE3KSI CONCRETE FOOTING PER FOOTING
SCHEDULE. POST MAY BE EMBEDDED DIRECTLY
INTO CONCRETE AS AN ALTERNATIVE TO
SURFACE MOUNTING. PROVIDE 18"
EMBEDMENT & A KEY HOLE FOR (1)#5 REBAR
12" LONG IN EACH DIRECTION, TYP.
EMBEDDED
POST, TYP
WIDTH PER
DESIGN SCHEDULE
POST EMBED DETAIL
NTS ELEVATION
SEE FOOTING SCHEDULE
ALUMINUM COLUMN &
CONNECTION PER SEPARATE
DETAIL. PLACE OVER MIDDLE 13 OF
FOOTING CLOSEST TO CENTER
SEE PAD FOOTING
DIMENSIONS ABOVE
PAVERS TO BE OVERLAID AFTER
PLACEMENT OF POST
(IF APPLICABLE)
REINFORCING STEEL
PER TABLE 12.2
VISIT ECALC.IO/FOOTING
FOR ENGINEER-CERTIFIED ORIGINALS, HELPFUL
TOOLS & RESOURCES & SITE-SPECIFIC ORDERING
VISIT ENGINEERINGEXPRESS.COM/STORE
FOR MORE MANUFACTURER MASTER PLANS
TO USE WITH THIS DOCUMENT
THIS DOCUMENT IS ONLY VALID WITH
ORIGINAL ENGINEER CERTIFICATION
FOOTING DETAILS: USE FOOTING PER # FOUND IN TABLE ABOVE
# WIDTH LENGTH DEPTH VOLUME WEIGHT REINFORCEMENT
1 24'' 24'' 18'' 6.0 CUFT 900 LBS 2
#4 TOP &
BOT EACH
WAY
-
2 30'' 30'' 18'' 9.4 CUFT 1406 LBS 4 -
3 30'' 30'' 24'' 12.5 CUFT 1875 LBS 4 & 5
#4
VERTICAL
TIES
4 36'' 36'' 24'' 18.0 CUFT 2700 LBS 4 & 6
5 36'' 36'' 30'' 22.5 CUFT 3375 LBS 4
#5 TOP &
BOT EACH
WAY
& 6
6 42'' 42'' 30'' 30.6 CUFT 4594 LBS 4 & 8
7 42'' 42'' 36'' 36.8 CUFT 5513 LBS 5 & 8
8 48'' 48'' 36'' 48.0 CUFT 7200 LBS 6 & 11
FOOTING TABLE NOTES:
1. F.S. AGAINST UPLIFT OF 33% HAS BEEN APPLIED
TO ALL LOADS.
2. AT 2000PSF SOIL BEARING PRESSURE, GRAVITY
DOES NOT GOVERN IN ANY CASE. ENSURE
PROPER COMPACTION & EMBEDMENT FOR FROST
& HEAVE REQUIREMENTS.
3. FOOTING WEIGHT CALCULATED PER 150 PCF
STANDARD WEIGHT CONCRETE
4. FOOTINGS OF ALTERNATE SIZE & EQUAL OR
GREATER VOLUME & WEIGHT
ACCEPTABLE WITH SEPARATE FOOTING
ENGINEERING
5. SITE SPECIFIC ENGINEERING REQUIRED FOR ANY
VALUES, SIZES, CONCRETE TYPES, OR SOIL
BEARING PRESSURES NOT COINCIDING WITH
LIMITS OF THIS MASTER PLAN.
TABLE 6.1 - FOOTING SELECTION
TABLE 6.2 - FOOTING DETAILS
FOOTER SCHEDULE NOTES:
1. FOOTERS SHALL BE 3000 PSI MINIMUM CONCRETE,
BEARING ON SOIL WITH A MINIMUM BEARING
CAPACITY OF 2000 PSF AS VERIFIED BY OTHERS.
2. IN LIEU OF THE FOOTERS DETAILED HEREIN, POSTS
MAY BE ANCHORED TO EXISTING CONCRETE SLABS
DESIGNED AND VERIFIED BY OTHERS TO SUPPORT THE
CANOPY SYSTEM AS DETAILED HEREIN.
3. FOOTERS SHALL HAVE THE MINIMUM REINFORCEMENT
INDICATED IN THE SCHEDULES HEREIN.
4. ALL REINFORCEMENT SHALL BE DEFORMED BARS OF
INTERMEDIATE GRADE NEW BILLET STEEL
CONFORMING TO CURRENT REQUIREMENTS OF ASTM
A615, GRADE 60 (U.O.N.), FREE FROM OIL, LOOSE
SCALE AND LOOSE RUST AND BENT, LAPPED, PLACED,
SUPPORTED AND FASTENED ACCORDING TO THE "ACI
DETAILING MANUAL" (SP-66) AND THE "BUILDING
CODE REQUIREMENTS FOR REINFORCED CONCRETE"
(ACI 318).
5. MINIMUM REINFORCING STEEL CLEAR COVERAGE
SHALL BE AS FOLLOWS. (PER ACI 318)
FOOTING: TOP, SIDES, BOTTOM = 1-1/2" MIN.
INSTALLED ON A SMOOTH LEVEL SURFACES ONLY.
MAINTAIN 3" IF NOT IN SMOOTH FORM.
6. ALLOW 3 DAYS CURE TIME BEFORE INSTALLING
ANCHORS INTO CONCRETE.
7. ALL CONCRETE WORK SHALL CONFORM TO ALL
REQUIREMENTS AND RECOMMENDATIONS OF ACI 318
"SPECIFICATION FOR STRUCTURAL CONCRETE FOR
BUILDINGS". A CERTIFICATE OF MANUFACTURER'S MIX
AND STRENGTH IS TO BE PROVIDED TO THE
INSPECTOR UPON REQUEST. NO WATER TO BE ADDED
AFTER TRUCK LEAVES PLANT WITHOUT APPROVAL OF
ENGINEER OR PLANT ENGINEER. PLANT CONTROL IS
REQUIRED. MAXIMUM MIX TIME AT POINT OF DEPOSIT
IS 90 MINUTES.
8. THESE TABLES REPRESENT EMPIRICAL UPLIFT
CALCULATIONS FOR FOOTING SIZES BASED ON
STANDARD WEIGHT (150PCF) CONCRETE. THEY
NEGLECT THE BENEFIT OF SKIN FRICTION AND OTHER
BENEFICIAL SURCHARGE LOADING. NO WARRANTY,
EXPRESSED OR IMPLIED, IS CONTAINED HEREIN AS TO
ANY INFORMATION OTHER THAN THAT WHICH IS
PUBLISHED HEREIN.
9. ALL FOOTINGS ARE TO BE INSTALLED LOWER THAN
CODE REQUIRED FROST LINE. GENERAL CONTRACTOR
IS RESPONSIBLE FOR ADHERENCE TO LOCAL FROST
LINE REQUIREMENTS. ADDITIONALLY, TOP OF
FOOTINGS ARE TO BE 8" MINIMUM BELOW GRADE IN
HVHZ (DADE & BROWARD COUNTIES, FL).
9 48'' 48'' 48'' 64.0 CUFT 9600 LBS 8 & 14
DESIGN UPLIFT
PRESSURE (-)
POST SUPPORT AREA
36 FT2 50 FT2 75 FT2 100 FT2 125 FT2 150 FT2 175 FT2 200 FT2 250 FT2
-10 PSF 1 1 2 3 3 4 4 5 6
-15 PSF 1 2 3 4 5 5 6 6 8
-20 PSF 2 3 4 5 6 6 7 8 9
-25 PSF 2 3 5 6 7 8 8 9 9
-30 PSF 3 4 5 6 8 8 9 9 N/A
-35 PSF 4 4 6 7 8 9 9 N/A N/A
-40 PSF 4 5 6 8 9 9 N/A N/A N/A
-45 PSF 4 5 7 8 9 N/A N/A N/A N/A
POST-BASE ATTACHMENT AND FOOTINGS
L =1/2 JOIST SPAN +JOIST OVERHANGCORNER POST
SUPPORT AREA
= W X L
W = 1/2 BEAM SPAN
+ BEAM OVERHANGL = JOIST SPANINTERNAL POST
SUPPORT AREA
= W X L
W = BEAM SPAN
EDGE POST
SUPPORT AREA
= W X L
W = 1/2 BEAM SPAN
+ BEAM OVERHANG
DECKING
NOT SHOWN
FOR CLARITY
NOTE: POST SUPPORT AREA MAY BE CALCULATED SEPARATELY FOR
EACH POST. EACH POST MAY UTILIZE DIFFERENT POST AND FOOTER
SELECTIONS FROM THE TABLES HEREIN BASED ON THE SITE DESIGN
CONDITIONS & ITS SUPPORT AREA
APPLICABLE FOR
HOST ATTACHED OR
FREESTANDING
POST SUPPORT AREA CALCULATION
NTS ELEVATION
TYP FOOTING INSTALLATION
NTS ELEVATION
CALL 811
BEFORE
YOU DIG
OR VISIT
WWW.CALL811.COM
USE POST SUPPORT AREA (CALCULATED FOR POST
SELECTION) TO DETERMINE FOOTING # TO DETERMINE
SIZE & REINFORCEMENT REQUIRED FOR EACH POST
VALID ONLY FOR ZIP CODE: 46033
VALID ONLY FOR: Cutting Edge
Hardscapes
FOR PERMIT USE WITHIN 14 DAYS
OF DIGITAL SEAL
PE10606888
09/13/21