Review Set
7062 N. TUXEDO STREETINDIANAPOLIS, IN 46220PH: 317-508-4516 FAX: 317-820-3405e-mail: morwalsoplad1@gmail.comJACK P. MORGANAIA CSI - ARCHITECTMECHANICAL PLANM1.102/07/21
MECHANICAL PLAN - BUILDING VIEW
SCALE: 1/8" = 1'-0"
MECHANICAL PLAN - OFFICE VIEW
SCALE: 1/4" = 1'-0"
sagging of lines. Pitch auxiliary drain pans and cooling coils slightly
in direction of condensate flow.
drain. Slope to positive drain with straps at 48" o.c. to avoid
coil. Provide 3/4" condensate drain separated from cooling coil
requirements of all units with the Electrical Contractor to
Ductwork shall be insulated. See Ductwork General Notes.
with slope to positive drainage outside of building. Provide sheet
The Mechanical Contractor to provide 3/4" PVC condensate drains
All Exhaust Fans and Ventilators shall have back draft dampers.
metal auxiliary drain pan, at attic units, 2" deep under each cooling
assure final correct locations of the unit's disconnects.
Units provided and installed by the Mechanical Contractor, power
and wiring by the Electrical Contractor.
All equipment to be provided with internal fuse protection,
per N.E.C., State and local Codes.
Mechanical equipment shall be base bid as 3Ø power supply.
power supply prior to ordering and installing equipment.
control devices and Low Voltage Wiring. Thermostats to be
Mechanical contractor shall be responsible for verifying available
The Mechanical Contractor to provide and install specified
Fresh / Outside Air shall conform to ASHRAE 62 "Ventilation
for Acceptable Indoor Air Quality" and all State and Local Codes.
D.O.E. Test procedure and A.R.I. Standard 210-79.
S.E.E.R. / E.E.R. - as rated in accordance with U.S. Government
A.F.U.E. - Annual Fuel Utilization Efficiency as established by
U.S. Government Standard D.O.E. Test.
to final occupancy.
The Mechanical Contractor shall provide Balancing Report prior
lock for all thermostats.
Fully Programmable 7 Day. Provide "tamperproof" Covers with
The Mechanical Contractor shall coordinate all electrical
The Mechanical Contractor shall be responsible for pouring
The Mechanical Contractor is to coordinate gas piping with
The heating, air conditioning equipment and installation shall
The Mechanical Contractor shall coordinate supply air and
may be installed at the proper locations, as not to affect the
conform to all current National, State and Local Codes.
of the units, and piping servicing the units. Piping in attic, to be
structural system of the building.
served using 1" stencil or engraved plastic.
concrete pad for units. Units to be 30" clear of building or
Plumbing Contractor to assure correct size and final locations
The Mechanical Contractor to clearly label each unit by area
return air ducts with General Contractor so duct encasements
suspended from trusses a minimum of 12" above insulation for
proper leak test and future service and inspection. The M.C.
at manufacturer's recommendations, which ever is greater.
to verify all aspects of gas service with local utility.
The Mechanical Contractor shall install fire dampers in all ducts
passing through Fire Rated Walls and Ceilings (denoted as "F.D."
on these Drawings) and all other locations specified by the State
Fire Marshall or Authority Having Jurisdiction.
These drawings indicate duct for size and approximate location. Ducts
may need to be moved slightly to insure no obstruction in installation.
to unit.
faced insulation.
acoustical lining.
of insulation.
- OR -
finished areas shall be painted flat black.
SMACNA Duct Manual and NFPA 90-A.
Coordinate all duct penetrations with Structural Drawings.
exhaust grilles, ductwork, etc. with lighting layout, reflected ceiling plan
Coordinate exact locations of all ceiling diffusers, registers and
Supply and return ducts shall be sheet metal with 1" thick internal
Wrap all supply and return ductwork with 2" thick, 3/4 lb. density foil
Flexible ductwork not to exceed 6'. When longer runs occur, use 28 Ga.
All ductwork shall be fabricated and installed in accordance with
OR SPECIFICATIONS.
Duct dimensions are shown as clear inside dimensions. Where internal
Portions of ducts visible through diffusers, grilles and registers in
insulation is called for, dimensions shall be increased by the thickness
Provide flexible connection where supply and return air ducts connect
round ductwork to obtain required lengths.
and owner's layout, so they will remain unobstructed.
Ductwork openings shall be coordinated with MBM for installation by this
Contractor. The M.C. to provide ductwork for exterior, insulated and
weather-protected and install return air ductwork as required.
Where applicable, Owens Corning 1" fiberglass duct board.
- OR -
THESE NOTES SHALL APPLY UNLESS OTHERWISE INDICATED BY DRAWINGS
1/2
NOTES:
1. DUCTS TO BE TIED TO MAIN EXHAUST FOR SINGLE WALL PENETRATION
2. TIE ACTIVATION OF FAN INTO LIGHT SWITCH FOR SIMULATENOUS
OPERATION OF FAN AND LIGHTS
BROAN 6"Ø .250 3.0 1000 1151/8 1 1; 2
ALL FIXTURES, LISTED ABOVE, MAY BE BID WITH A PRE-APPROVED EQUAL.NOTE:
100 - 550
950 - 1,725PRICE: 80 CORE (EGG CRATE)RAG SQ/RECT
PRICE: SCD SERIESSAD 1 SQUARE
RETURN GRILLE/FLUSH MOUNT300 - 400 < 20 NECK AS PER PLANS STL
LAY-IN/NECK AS PER PLANS
SUPPLY AIR DIFFUSER/T-BAR500 - 800 < 20 STL WHITE O.B.D.
WHITE
671 120
100 - 550 PRICE: 510 SERIES SAR RECT MOUNT DIRECTLY TO DUCT
SUPPLY AIR REGISTERS500 - 800 < 20 STL STEEL O.B.D.
NOT ALL APPLY
NOT ALL APPLY
912SD36060 E14 800 20 % 0.75 .75 T-A (2) 2
FU 1 BRYANT
NOTE:NOTES:
1. ALL UNITS SHALL BE SET IN DRIP PAN W/ DRAIN LINE TO EXTERIOR OF BUILDING.
2. ALL UNITS SHALL BE COMPLETE WITH 7-DAY ELECTRONIC FULLY PROGRAMMABLE THERMOSTAT w/ LOCKABLE COVER
GAS 60,000
80 67 24 18 90 67 24 1.5 13.0 3.5 17
115 8 2.0 20520 1
R410A / 14
REF
LBS
95
BA13NA024BNG CU 1 BRYANT 208 17 2.0 225251
SPECIFIC CHART VALUES ARE FOR REFERENCE ONLY ALL PERFORMANCE SHALL BE VERIFIED AGAINST
SUBMITTAL SHEETS FORM SUPPLIER. MFG FOR SPECIFIC OF PERFORMANCE AND EQUIPMENT DESCRIPTIONS.
STRAP
HANGERS (TYP.)
SUPPORT
DIFFUSER
INSULATION
O.B. DAMPER
10'-0"
MAXIMUM ALLOWABLE
LENGTH OF FLEX. DUCT
VOLUME DAMPER
BRANCH
DUCT
SUSPENDED ACOUSTICAL
CEILING PANEL
FLEX DUCT
NOT TO SCALE:
PDP 400UH 1/2 MODAL 400,000
UH-1 UH-2
400,000 400,000
CU-1
2T FU-1
800
RAG
24X24
SAD
170
SAD
180
SAD
60 SAD
200
SAD
110
SAR
40
SAR
40
EF-1
80
EF-2
80
6"Ø EXHAUST DUCT
WC-6 WALL HOOD
12"Ø 14"Ø14"ØRAG
14X14
10"Ø
8"Ø FLEX DUCT-TYP.
SPIRAL DUCT
-TYP.
4"Ø FURNACE
FLUE TO WALL
OUTLET
LINE SETS TO
CONDENSER
UNIT
UNIT HEATER FLUES
UP AND OUT THRU
ROOF
T
09/14/21