HomeMy WebLinkAboutA121 REFLECTED CEILINGSN3 SNSNSNSNSN
SNSNSNSNSN ELNELN ELNELNSN3SNSNSNSNSNSN3 SN SNSNSN
SNSNSNSNSN ELNELN ELN ELNELN ELNSN3ELNSN SN SN SNSNSNREFLECTED
CEILING PLAN
A121
IN AREA TO BE EXPOSED TO DECK, REPLACE LOW PRESSURE SUPPLY BRANCH LINE DUCT AND WITH NEW RIGID SPIRAL DUCT AND
ROUND SUPPLY DIFFUSERS AS REQUIRED. CLEAN AND PREPARE FOR DRYFALL PAINT (PT_). AS SPECIFIED, PAINT EXISTING EXPOSED
CEILING DECK, EXPOSED DUCTWORK, SPRINKLER PIPING, JUNCTION BOXES, CONDUIT, STRUCTURAL BEAMS FIREPROOFING, ETC. IN
ACCORDANCE WITH NFPA 13 6.3.8.
TRANSITION FROM CEILING GRID TO EXPOSED CEILING TO BE A 5" WIDE DRYWALL BULKHEAD EXTENDING FROM 8'-0" AFF TO DECK AND
ALIGNING WITH ADJACENT WALLS AS SHOWN. TRANSITION TO BE A CLEAN VERTICAL BULKHEAD, FINISHED SUCH THAT CONTRASTING
PAINT COLORS CAN EASILY AND CLEANLY CUT AT WALL TO CEILING LINE. VERTICAL FACE OF DRYWALL TO BE PAINTED COLOR OF
ADJACENT WALL.
PROVIDE FLOATING DRYWALL CEILING AT 10'-0" AFF AT THIS LOCATION WITH 6" ARMSTRONG AXIOM TRIM AT EXPOSED EDGE. VERTICAL
FACE OF DRYWALL DOES NOT EXTEND TO DECK AT THIS LOCATION. EXTEND DRYFALL PAINT ON DECK ABOVE BEYOND EDGE OF
BULKHEAD AS FAR BACK AS REQUIRED SUCH THAT ALL VISIBLE DECK AND COMPONENTS FROM EYE-LEVEL AT ANY POINT IN THE SPACE
IS FINISHED WITH PT_. NOTE THAT SPRINKLERS MAY BE REQUIRED ABOVE AND BELOW CEILING IN THIS AREA.
CONTROL LINEAR LIGHT FIXTURES IN ENTRY 201 + CAFE 202 WITH SWITCH AT THIS LOCATION.
CONTROL OPEN OFFICE AND COPY LIGHTING WITH 3-WAY SWITCH AT THIS LOCATION. PROVIDE MULTIPLE SWITCHES AS REQUIRED.
PROVIDE NEW CEILING GRID AND TILE AS SHOWN TO MATCH AND ALIGN WITH EXISTING SUCH THAT NEW AND EXISTING CEILINGS
APPEAR CONTINUOUS.
PROVIDE SEPARATE PRICE FOR ADJUSTED CEILING LAYOUT IN THIS LOCATION. SEPARATE PRICE TO INCLUDE INSTALLATION OF (6)
80"X200" FRASCH VINE SUSPENDED ACOUSTIC CLOUD SYSTEMS (CLOUDS BY TENANT) WITH (5) 16' LED LINEARS AS SHOWN (LIGHTING
AND INSTALLATION BY GC). IF SEPARATE PRICE IS ACCEPTED, COORDINATE FINAL INSTALLATION HEIGHTS WITH SDI.
PROVIDE 4' WIDE DIRECT/INDIRECT SURFACE MOUNTED LED LINEAR LIGHT FIXTURE AT THIS LOCATION. FINAL HEIGHT TBD.
PLAN NOTES
LIGHT CIRCUIT
LIGHT SWITCH, 3-WAY
LIGHT SWITCH, DIMMERN
N3 3
EXIT LIGHT FIXTURE
LIGHT FIXTURE,
PENDANT. ASSUME
$1,000 MATERIAL COST
TOTAL FOR ALL
PENDANTS
RECESSED LIGHT
FIXTURE
LIGHT FIXTURE, 2'x2', LED,
COLUMBIA LIGHTING CCL
LIGHT FIXTURE, 2'x4', LED
COLUMBIA LIGHTING CCL
RELOCATED DIFFUSER,
LAY-IN, 4"x4'
RELOCATED DIFFUSER,
LAY-IN, 1'x4'
RELOCATED DIFFUSER,
LAY-IN, 2'x2'
CEILING GRID,
SUSPENDED, 2'x2'
NIGHT LIGHT
NEW OR RELOCATED EXISTING TO REMAIN
EXIT LIGHT FIXTURE
LIGHT CIRCUIT
LIGHT SWITCH, 3-WAY
LIGHT SWITCH
CEILING GRID,
SUSPENDED, 2'x2'
DIFFUSER,
LAY-IN, 4"x4'
DIFFUSER,
LAY-IN, 1'x4'
DIFFUSER,
LAY-IN, 2'x2'
GYPSUM BOARD CEILING
LIGHT FIXTURE, 2'x2',
FLUORESCENT, PARABOLIC
LIGHT FIXTURE, 2'x4',
FLUORESCENT, PARABOLIC
LEGEND
REFLECTED CEILING PLAN - BASE BID
DESCRIPTIONDATE
ISSUE
08.13.21 REVIEW SET
08.18.21 PERMIT SET
REVISIONS
DESCRIPTIONMARK DATE DB
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700www.schottdesign.comPROJECT NUMBER
DRAWN BYPROJ. MGR BASTIAN SOLUTIONSONE MERIDIAN PLAZA | SUITE 20010585 N. MERIDIAN ST, INDIANAPOLIS, IN 46290EHEH
2021.130
2ND FLOOR
N
0 2'4'8'16'
EMERGENCY LIGHT FIXTURE EMERGENCY LIGHT FIXTURE
MECHANICAL DIFFUSER RELOCATION
A121
1
*REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION
EXISTING VAV BOXES OR
HEAT PUMP AND MAIN SUPPLY
DUCTS TO REMAIN
RELOCATE DIFFUSERS &
FLEXDUCT IF REQUIRED
VAV /
HEAT PUMP
EXHAUST FAN, 2'x2' EXHAUST FAN,
2'x2'
GYPSUM BOARD CEILING
EXPOSED TO DECK
A121
1
1. REUSE EXISTING CEILING GRID UNLESS OTHERWISE NOTED; PROVIDE
NEW TO MATCH EXISTING AND REPAINT ALL GRID IN SHERWIN
WILLIAMS CEILING BRIGHT WHITE WITH PAINT SPECIFICATION
APPROPRIATE FOR SUBSTRATE. EXISTING GRID IS 2x2 AT 8'-4" A.F.F.
PROVIDE NEW 2x2 ACOUSTICAL LAY IN TILES THROUGHOUT;
CONFIRM SPECIFICATION WITH TENANT. REPAIR ANY DAMAGED
GRID AND REPLACE ANY DAMAGED TILES WITH NEW TO MATCH
EXISTING.
2. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN
SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI
OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT
IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT
INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1,
CONTRACTOR MUST NOTIFY SDI. OVER 50% OF THE LIGHTING WILL BE
REPLACED WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL
NEED TO BE MET.
4. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS; PROVIDE COMBO
UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH A
ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE
LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF
INCLUDED AREA IS DETECTED. PROVIDE CEILING MOUNTED
OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED.
5. ALL DEVICES AND FACE PLATES TO BE WHITE; REPLACE EXISTING AS
REQUIRED. WHERE POSSIBLE, GANG MULTIPLE SWITCHES TO
ACCOMMODATE MULTI-SWITCH PLATE WHEN SWITCHES ARE SHOWN
ADJACENT ON PLAN.
6. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO
ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND
LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING
ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS
TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED
SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH
ALL APPLICABLE CODES.
GENERAL NOTES
1. MECHANICAL WORK IS LIMITED TO A DESIGN-BUILD
SCOPE AND IS OUTLINED IN THESE DRAWINGS. NO
NEW MAIN MECHANICAL APPLIANCES OR MAIN
EQUIPMENT ARE BEING PROVIDED. ALL
MECHANICAL WORK IS LIMITED TO RELOCATION OF
DIFFUSERS AND FLEX DUCT PER NEW WALL LAYOUT.
IF IN GOOD CONDITION, EXISTING H.V.A.C.
DIFFUSERS SALVAGED FROM DECONSTRUCTION
MAY BE SUBSTITUTED FOR NEW. NO NEW HARD
DUCTWORK OR EQUIPMENT IS BEING ADDED;
MECHANICAL CONTRACTOR IS TO NOTIFY
APPLICABLE PARTIES IF ADDITIONAL WORK IS
REQUIRED SO THAT ADDITIONAL PLANS CAN BE
FILED AND MUST COMPLY WITH THE INDIANA
MECHANICAL CODE AND ALL OTHER APPLICABLE
CODES.
MECHANICAL NOTES
AREA NOT IN CONTRACT
AREA OF WORK
0 2' 4' 8' 16'
REFLECTED CEILING PLAN - ALTERNATIVE LAYOUT
0 2' 4' 8' 16'
LIGHT FIXTURE, LINEAR LED,
FINELITE HP-4 ID; LENGTHS
NOTED ON PLANS
09/16/21