E211 - BUILDING ELECTRICAL SCHEDULES & DETAILS
TYP. 2ND/3RD FLOOR UNIT 2189 SF @ 3 VA 6567 DRYER 5500 WASHER 1500 NOT USED 0 DISPOSAL 720 WATER HEATER (2) GWH-1 960 REFRIGERATOR 1500 RANGE 9600 CONDENSING UNIT 3494 FURNACE BLOWER 989 2 APPLIANCES @ 1500 EA. 3000 DISH WASHER 1200 TOTAL 35030 FOURTH FLOOR UNIT 3339 SF @ 3 VA 10017 DRYER 5500 WASHER 1500 NOT USED 0 DISPOSAL 720 WATER HEATER (2) GWH-1 960 REFRIGERATOR 1500 RANGE 9600 CONDENSING UNIT 3952 FURNACE BLOWER 1369 2 APPLIANCES @ 1500 EA. 3000 DISH WASHER 1200 TOTAL 39318 TYP. 2ND/3RD FLOOR UNIT 2189 SF @ 3 VA 6567 DRYER 5500 WASHER 1500 NOT USED 1600 DISPOSAL 720 WATER HEATER (2) GWH-1 960 REFRIGERATOR 1500 RANGE 9600 DISH WASHER 1200 2 APPLIANCE CKTS @ 1500 3000 TOTAL 32147 FIRST 10kVA AT 100% 10000 REMAINDER AT 40% 8859 100% OF COOLING EQUIP 4483 TOTAL VA 23342 23342VA / 208V = (AMPS) 112 125a Service FOURTH FLOOR UNIT 3339 SF @ 3 VA 10017 DRYER 5500 WASHER 1500 NOT USED 1600 DISPOSAL 720 WATER HEATER (2) GWH-1 960 REFRIGERATOR 1500 RANGE 9600 DISH WASHER 1200 2 APPLIANCE CKTS @ 1500 3000 TOTAL 35597 FIRST 10kVA AT 100% 10000 REMAINDER AT 40% 10239 100% OF COOLING EQUIP 5321 TOTAL VA 25560 25560VA / 208V = (AMPS) 123 150a Service 400A BUILDING SERVICE # DESCRIPTION W EA. SUBT. 4 TYP. 2ND/3RD UNITS 35030 140,120 1 FOURTH FL. UNIT 39318 39,318 5 TOTAL UNIT # 179,438 x DEMAND FACTOR 0.45 80,747 1 HOUSE PANEL 9895 9,895 1 ELEVATOR 44080 44,080 1 BLANK 0 0 1 BLANK 0 0 1 BLANK 0 0 1 BLANK 0 0 1 BLANK 0 0 1 BLANK 0 0 1 BLANK 0 0 TOTAL VA @ 208 V 134,723 TOTAL AMP DEMAND / (208 V *1.73)=374 A HP-1 (HOUSE PANEL) 4792 SF @ 0.5 VA 2396 EH-1 3016 GAS FURNACE 989 CONDENSER 3494 TOTAL 9895 9895VA / 208V = 48 100a PANEL DESIGNATION: HP-1 HOUSE PANEL 92/7$*(:0$,1$03$&,7<$0$,1/8*6 BRANCH CIRCUITS: PLUG-IN REMARKS: CKT DESCRIPTION VA TRIP CKT DESCRIPTION VA TRIP 1 LIGHTING/RECP 342 20A 2 LIGHTING/RECP 342 20A 3 LIGHTING/RECP 342 20A 4 LIGHTING/RECP 343 20A 5 LIGHTING/RECP 342 20A 6 LIGHTING/RECP 343 20A 7 LIGHTING/RECP 342 20A 8 GARAGE DOOR OPENER 500 20A 9 CONDENSER 3494 25A 10 GARAGE DOOR OPENER 500 20A 11 * 12 GARAGE DOOR OPENER 500 20A 13 FURNACE 989 15A 14 GARAGE DOOR OPENER 500 20A 15 16 GARAGE DOOR OPENER 500 20A 17 18 BOOSTER PUMP 2237 2P 19 20 30A 21 22 23 24 * AS REQ'D BY MFR. NOTE: EMERGENCY LIGHTS INCLUDED IN CKT 1. WIRE EMERGENCY LIGHTS BEFORE ANY SWITCHES PER NEC 700.10 TOTAL VA 11616 PANEL DESIGNATION: TYP. 2ND/3RD FLOOR UNITS 92/7$*(:0$,1$03$&,7<$0$,1/8*6 BRANCH CIRCUITS: PLUG-IN REMARKS: CKT DESCRIPTION VA TRIP CKT DESCRIPTION VA TRIP 1 WASHER 1500 20A 2 LAUNDRY/HALL 1067 20A 3 REFRIGERATOR 1500 20A 4 DRYER 5500 2P 5 DISPOSAL 720 15A 6 * 7 KITCHEN 1500 20A 8 GWH-1 480 15A 9 KITCHEN 1500 20A 10 GWH-1 480 15A 11 LIVING RM/DINING 1500 20A 12 CONDENSING UNIT 3494 2P 13 MASTER BED/OTHER 1500 20A 14 * 15 BATHROOM 500 20A 16 FURNACE BLOWER 989 2P 17 DISHWASHER 1200 20A 18 * 19 BATHROOM 500 20A 20 RANGE 9600 2P 21 BEDROOM 1000 20A 22 50A 23 OUTDOOR LIVING 500 20A 24 SPACE 15A * AS REQ'D BY MFR. + ACTUAL VA VARIES BY UNIT TYPE;TOTAL VA 35030 PANEL DESIGNATION: FOURTH FLOOR UNIT 92/7$*(:0$,1$03$&,7<$0$,1/8*6 BRANCH CIRCUITS: PLUG-IN REMARKS: CKT DESCRIPTION VA TRIP CKT DESCRIPTION VA TRIP 1 WASHER 1500 20A 2 LAUNDRY/HALL 1500 20A 3 REFRIGERATOR 1500 20A 4 DRYER 5500 2P 5 DISPOSAL 720 15A 6 * 7 KITCHEN 1500 20A 8 GWH-1 480 15A 9 KITCHEN 1500 20A 10 GWH-1 480 15A 11 LIVING RM/STUDY 1750 20A 12 CONDENSING UNIT 3952 2P 13 MASTER BED/PATIO 1750 20A 14 * 15 BATHROOM 500 20A 16 FURNACE BLOWER 1369 2P 17 DISHWASHER 1200 20A 18 * 19 BATHROOM 500 20A 20 RANGE 9600 2P 21 BEDROOM 1500 20A 22 50A 23 OUTDOOR/DINING 1000 20A 24 BEDROOM 1517 20A * AS REQ'D BY MFR. + ACTUAL VA VARIES BY UNIT TYPE;TOTAL VA 39318 F.F. 16" 40" 48" 54" 80" 88" 96" FINISH CEILING POWER/ COMMUNICATIONS DEVICES & SYSTEMS FURNITURE OUTS CATV OUTLET DEVICES & MOUNTING BRACKETS ABOVE COUNTER DEVICES COORDINATE w/ ARCH. ELEVATIONS & CABINETRY SHOP DWGSPULL STATION WALL-MOUNTED OPERABLE DEVICES WALL-MOUNTED DEVICE w/ SIDE ACCESSIBILITY STROBE CEILING-MOUNTED HORN OR HORN/ STROBE 4"4"MAX. 12"CEILING-MOUNTED DETECTOR DO NOT PLACE DETECTOR IN THIS AREA WALL-MOUNTED DETECTOR HORN HORN/ STROBE ARCHITECTCLIENT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20022 JANUARY 15, 2021 # DESCRIPTION DATEMAGNOLIACONDOMINIUMSCARMEL, INCONSTRUCTION SET GC/CM BUILDING ELECTRICALSCHEDULES & DETAILSE211 SCALE: ELECTRICAL LOAD CALCULATIONS E211 1 NA SCALE: ELECTRICAL ONE-LINE DIAGRAM E211 2 NA SCALE: ELECTRICAL PANEL SCHEDULES E211 3 NA SCALE: ELECTRICAL MOUNTING DETAIL E211 4 NA 09/22/21