HomeMy WebLinkAboutP500 - PLUMBING DETAILS - DWVFOR INSULATED PIPING)
TO STRUCTURE
1/2" HANGER ROD
WHERE REQUIRED
FIBERGLAS
ONLY
INSULATED PIPE
METAL SHIELD FOR
20 GAUGE SHEET
BARRIER (TYPICAL
CONTINUOUS VAPOR
NUT (TYPICAL)
HANGER
PIPING
STRAP
THRU BOLT
NOTES:
REFER TO RELATED SECTIONS OF THE SPECIFICATIONS FOR INFORMATION REGARDING FLASHING MEMBRANE AND FIRESTOP
SEALANT
FINISH FLOOR
LC
PROVIDE NEW CONCRETE TO MATCH
EXISTING FLOOR
FLASHING MEMBRANE
REMOVE EXISTING CONCRETE
TO RECIEVE FLASHING CLAMP
FIRESTOP SEALANT
CORE HOLE TO RECIEVE
DRAIN BODY
FLOOR DRAIN BODY
EXISTING SLAB
FLOOR DRAIN GRATE
TRAP SEAL
TO GRADE DETAIL
AT END OF LINECLEANOUT OCCURS
1/8 BEND IF
WASTE LINE
LENGTH TO SUIT
WASTE LINE
1/8 BEND
FINISHED GRADE HEAD
WITH COUNTER SUNK
BRASS CLEANOUT PLUGFLOOR LINE
SAME AS CLEANOUT
BALANCE OF PIPE
1/8 BEND
AREASFOR CARPETEDCARPET MARKER
OF FLOORTO BE FLUSH WITH TOP
COVER. TOP OF COVERCLEANOUT AND ACCESS
CLEANOUT TO GRADEFLOOR CLEANOUT
NOTE: LOCATE PIPING 1 1 /2"
MIN. CLEARANCE OF GYPSUM
BOARD
CAULK AIRTIGHT
WITH ACOUSTICAL
OR FIRE-RATED
SEALANT
FLOOR CONSTRUCTION
SAFING BATT INSULATION
BACKER ROD
PIPE RISER CLAMP
STEEL SHIM (OPTIONAL)
3/4" NEOPRENE PAD
0.2500
NOTE:
FIRE SEALANTS AND PIPE
PENETRATION SHALL HAVE AN
F-RATING AND NO LESS THAN
THE REQUIRED FIRE RESISTANCE
RATING OF THE WALL
PENETRATED.
SANITARY, DRAINAGE
OR WATER PIPE
NON-SECURE SPACESECURE SPACE
PVC PIPE SLEEVE
RATED CAULK.
1/4" BEAD OF FIRE
DISHWASHER
LOOPED HIGH AND SECURELY
FASTENED TO COUNTER OR WALL
2"
FOOD-WASTE
GRINDER
1/2" TO FOOD
WASTE GRINDER INLET
SUMP RECEIVER
COLUMN
CLAMP TO WALL OR COLUMN
OFFSET (IF REQUIRED
BY JOB CONDITION)
ROOF DRAIN
INSULATION
UNDERDECK
CLAMP
PLUGGED SLEEVE
NOTE:
1 . PROVIDE RISER CLAMP AT ALL OTHER FLOOR PENETRATIONS.
2. HOLD HORIZONTAL PIPING AT DESIGN SLOPE (1 /4" PER
FOOT FOR 2" AND 3" PIPE, 1 /8" PER FOOT FOR LARGER PIPE)
TO ALLOW MAXIMUM UTILIZATION OF AVAILABLE PIPE SPACE IN
BUILDING.
TRAPEZE HANGER (3/4" PIPE FOR
PIPING UP TO 5", 1 " PIPE FOR
LARGER PIPING.)
ALL THREAD ROD (3/8" FOR PIPING UP TO 6",
1 /2" FOR LARGER PIPING)
CONCRETE INSERT
HOLD BELL OF HUB TIGHT
TO BOTTOM OF FLOOR
CONSTRUCTION
EXTEND SLEEVE 2" ABOVE
FINISHED SLAB
EXTEND SLEEVE 2"
ABOVE LOCATIONS WHERE
TOPPING SLAB EXISTS
PIPE SLEEVE
FLOOR SLAB
TOPPING SLAB (REFER
TO ARCHITECTURAL DRAWINGS
FOR LOCATIONS)
FOR PENETRATIONS IN FIRE RATED FLOORS,
FILL VOID OR CAVITY WITH MATERIALS
CLASSIFIED BY UNDERWRITERS LABORATORIES INC.
FOR USE IN THROUGH-PENETRATION FIRESTOP
SYSTEM OR U.L. CLASSIFIED THROUGH-PENETRATION
FIRESTOP DEVICE
NO SCALE
A A
REFER TO SPECIFICATIONS FOR ADDITIONAL SLEEVE REQUIREMENTS
1 8 GAUGE CONTINUOUS SHEET METAL
ENCLOSURE FOR PENETRATIONS WITH
FIRE-STOP MATERIAL. ENCLOSURE
SHALL NOT BE ATTACHED TO PIPE OR
INSULATION.
SECTION A-A
NO SCALE
TOPPING SLAB (REFER TO THE ARCHITECTURAL
DRAWINGS FOR LOCATIONS)
FOR PENETRATIONS IN FIRE-RATED FLOORS, FILL VOID, OR
CAVITY WITH MATERIALS CLASSIFIED BY UNDERWRITERS
LABORATORIES INC. FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEM OR U.L. CLASSIFIED
THROUGH-PENETRATION FIRESTOP DEVICE
1 /4" TO 3/8" GAP BETWEEN PIPE AND CORE
PIPE AND/OR CONDUIT
1" TYP
OUTSIDE SURFACE
OF PIPE (OR
INSULATION)
1 /4" TO 3/8" GAP BETWEEN
EDGE OF
ENCLOSURE AND
PIPE
SLEEVE
UNDERSIDE PLAN VIEW
OR 3 FT. ABOVE STRUCTURE.
1 0 FT. (MIN.) FROM ANY WALL
VENT STACK OUTLET TO BE
NOTE:
ROOFING CONSTRUCTIONROOF
FLASHING SLEEVE
VENT STACK
VENT STACK EXTENSIONHOLE IN WALL
FINISH BY OTHERS
WOOD OR STEEL
FRAMING STUD
SCREW MOUNTING
BRACKET TO STUD
WASH MACHINE SERVICE
CONNECTION BOX
OVERFLOW TRAY
2" WASTE OUTLET 1/2" CW SUPPLY
TOP OF BOX
TOP OF MACHINE
3-1/2"
XX" TO FL.
SHOCK ABSORBER
TYPICAL SERVICE STOP RI
G EEIS
PE60860351
No.REENIGNELANOISSEFORPDOUGLAS.RMOO
RET R
NNDIA A
STATE OF DEMOORE ENGINEERING
SERVICES, INC.
6340 LaPas Trail
Indianapolis, IN 46268
Phone (317) 291-1052
FAX (317) 298-2729 ARCHITECTCLIENT PROJECT DRAWING TITLE SHEET PROJECT INFO REVISIONS20022
# DESCRIPTION DATEMAGNOLIACONDOMINIUMS126TH & RANGELINERD CARMEL, IN100% Contract Set GC/CM SEAL 10/07/2020
P500 PLUMBING DETAILS -DWV09/22/21