HomeMy WebLinkAboutP-601 - PLUMBING DETAILS40" MIN.36" MIN.
DOOR MIN. 30"
WATER HEATER PAN
WATER HEATER
FAN COIL UNIT
PLENUM
CLEARANCE
RACK REFRIGERANT
LINE SETS ON SIDE
WALL OF MECH ROOM
RETURN GRILLE,
SEE PLANS
CONDENSATE DRAIN;
ROUTE TO HUB DRAIN
MAIN SHUT-OFF
WATER HEATER PAN
SLEEVE
FLEX
CONN.
DUCTFIRE DAMPER
W/ACCESS PANEL
FAN
COIL
UNIT
WATER HEATER
HW CW VALVE (TYP.)
SIDE VIEW
TOP VIEW
NOTE: TYPICAL CONDITION SHOWN, REFER TO HVAC AND
PLUMBING FLOOR PLANS FOR ADDITIONAL REQUIREMENTS.
CEILING
RADIATION
DAMPER
PLENUM BOX OR
ELBOW, R/D=1.5
MIN. 20"9'-0" REFER TO PLANSSEE HVACPLANSSEE HVAC PLANS12"MIN.NOM.36"FIRE PARTITION BY
CONTRACTOR;
WITH FOAM SEAL.4"NOTES:
1. ROUTE CONDENSATE PIPING (SIZE PER
MANUFACTURER) TO HUB DRAIN.
2. REFER TO REFRIGERANT PIPING DETAIL
ON HVAC DETAIL SHEET FOR
ASSOCIATED REQUIREMENTS.
3. REFER TO STRUCTURAL UNIT PLAN
DRAWINGS FOR ACTUAL CONDITION AT
EACH CLOSET. HARD DUCT MAIN ALWAYS
ROUTES PARALLEL TO JOINTS.
4. COORDINATE HARD DUCT ELEVATION AT
JOIST SPACE WITH FIRE AND PLUMBING
PIPING PRIOR TO INSTALLATION.
5. FIRESTOP ALL PENETRATIONS AT
CEILING, FLOOR AND THROUGH FCU
SUPPORT.
NOM. 30"
T&P VALVE, ROUTE
DRAIN LINE TO HUB
DRAIN
4" HUB DRAIN
2" WASTE
TRAP SHALL NOT BE INSTALLED
BELOW FLOOR BUT SHALL
BE ROUGHED IN NOT LESS
THAN 6" AND NOT MORE
THAN 18" ABOVE FLOOR
NO STANDPIPE RECEPTOR SHALL
EXTEND MORE THAN 30" NOR
LESS THEN 18" ABOVE ITS TRAP
1 1/2" VENT
1/2"CW
1/2"HW
SHUTOFF VALVE WITH THREADED
HOSE CONNECTION
2" WASTE
P-TRAP WITH UNION
CONNECTIONS
FLOOR LINE
CLOTHES WASHER RECESSED
WALL BOX WITH FACE PLATE;
EQUAL TO GUY GRAY SERIES
RECESSED WALL BOXES
SINK
SHUT-OFF VALVE
REDUCER
GARBAGE
DISPOSAL
5/8" DRAIN
HOSE
1 1/2" VENT
2" SAN
DISHWASHER
1/2" HW
CW SUPPLY
HW SUPPLY
CODE APPROVED
AIR ADMITTANCE
VALVE (AAV)
COUNTERTOP
INSTALL AS HIGH AS
POSSIBLE UNDER
THE COUNTERTOP
4" MIN.
SLOPE
RISER PIPE SAME
AS SEWER
18"x18"x8" THICK
CONCRETE PAD
ROUND FLANGED HOUSING
W/ HEAVY DUTY CAST IRON
COVER LIKE J.R. SMITH 4251
CLEANOUT PLUGFINISH GRADE
2-WAY FITTING
SYSTEM RISER
CAST IRON FLANGE
AND SPIGOT PIECE
CAST IRON BELL
AND SPIGOT PIPE
THRUST BLOCKING
RODS
FIRE SERVICE
MAIN
RESTRAINT
BUILDING SLAB
AT REFRIGERATORS = 12" AFF.
AT ICE MACHINES = 12" AFF.
AT COUNTERS = 1" ABOVE COUNTER BACK SPLASH,
FOR COFFEE MAKER SUPPLY
VARIESREFRIGERATOR ICE MAKER
RECESSED WALL BOX WITH
FACE PLATE; EQUAL TO OATEY
SERIES RECESSED WALL BOXES
ANGLE STOP VALVE WITH
THREADED CONNECTION
FOR ICE MAKER TUBING
1/2"CW
FLOOR LINE
SLOPE
RISER PIPE SAME AS SEWER
FINISH FLOOR
CLEANOUT BOX WITH RECESSED
SOLID COVER
BRONZE PLUG
MAXIMUM MOUNTINGHEIGHT OF 5'-0"ABOVE FLOORWALL SLEEVE
(TYPICAL)
4"CW INCOMING SERVICE WITH
JOINT HARNESS REACTION ANCHORS
PROVIDE REMOTE WATER
METER READ OUTS, SEE
FLOOR PLANS FOR LOCATION
REDUCED PRESSURE BACKFLOW
PREVENTER
4"CW TO
BUILDING SERVICE
1. ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH UTILITY COMPANY'S
REQUIREMENTS. WATER METER FURNISHED BY LOCAL UTILITY, CONTRACTOR INSTALLED.
NOTE:
NEEDLE VALVE
PRESSURE GAUGE
COUPLING ADAPTOR (TYP)
METER
METER
GATE VALVE (TYP)
SEE SPECIFICATIONS
FOR PIPE SUPPORT
REQUIREMENTS
TYPICAL DRAIN FUNNEL WITH AIR
GAP, TERMINATE DRAIN LINE
OVER NEAREST FLOOR DRAIN
BFP-1
BFP-2
4"CW
4"CW
STRAINER
(TYP)
THREADED
CLEANOUT PLUG
TEST TEE ACCESS COVER AND FRAME
FINISHED WALL SURFACE
PIPE
DOUBLE SUPPORT NUT
LOCKING NUT
HANGER ROD HANGER ROD
LOCKING NUT
SUPPORT NUTCLEVIS HANGER
14 GAUGE ZINC COATED
SHEET STEEL SADDLE
AT LEAST 12" LONG
PIPE
INSULATION
INSULATION
PREFORMED PIPE SUPPORT INSERT,
SAME THICKNESS AS INSULATION
MANUFACTURED FOR THIS PURPOSE
ROOF DECK
STEEL ANGLE
FRAME SUPPORT
24"x24" SUMP RECEIVER
INSULATION
1 1/2"x1 1/2" UNI-STRUT FRAME
UNDER DECK CLAMP
CAST IRON DOME
WITH TWIST LOCK
RIGID INSULATION
MEMBRANE ROOFING
ADJUSTABLE
EXTENSION
ROOF DECK
STEEL ANGLE
FRAME SUPPORT
24"x24" SUMP RECEIVER
INSULATION
1 1/2"x1 1/2" UNI-STRUT FRAME
UNDER DECK CLAMP
CAST IRON DOME
WITH TWIST LOCK
RIGID INSULATION
MEMBRANE ROOFINGADJUSTABLE
EXTENSION
2" HIGH WATER DAM
INSULATION
BLOCKING
UNI-STRUT TRAPEZE SUPPORT
STRUT PIPE CLAMP
PIPE INSULATION MATERIAL
(REFER TO SPECIFICATIONS)
SYSTEM PIPE (REFER TO
DRAWINGS FOR TYPE OF
SYSTEM AND PIPE SIZE)
OR CUSHION STRIP
NEOPRENE ISOLATOR
THREADED
STEEL HANGER
ROD
STEEL ROD
COUPLING
48" A.F.F. IN MECH CLOSETSRECESSED WALL VALVE BOX WITH
FACE PLATE; EQUAL TO ACUDOR
ARVB RECESSED WALL VALVE BOXES
BALL
VALVE
FLOOR LINE
3/4"CW, SEE ENLARGED
FLOOR PLANS
3/4"CW, SEE ENLARGED
FLOOR PLANS12"PENETRATION BOOT & FLASHING TO
MEMBRANE ROOFING BY ROOFING
CONTRACTOR BASED ON CARLISLE U-8-A.
REFER TO MANUFACTURER'S
RECOMMENDATIONS FOR INSTALLATION
PROVIDE STAINLESS STEEL
CLAMPING BAND
SURE SEAL WATER CUT-OFF MASTIC
ROOF DECK - SEE ARCHITECTURAL
DRAWINGS FOR CONSTRUCTION
OPENING IN DECK BY PLUMBING
CONTRACTOR
SEE DRAWINGS FOR SIZE
INCREASER AS REQUIRED
PIPE SIZE PER DRAWINGS
CARRIER PIPE
WATER STOP AND
ANCHOR COLLAR
WALL
WALL SLEEVE
MECHANICAL INTERLOCKING
RUBBER LINKS TYPE WALL
PENETRATION SEAL
CONTROL PANEL
AND VFD'S
HYDROPNEUMATIC TANK
TYPICAL
PUMP TYPICAL FLEXIBLE
CONNECTOR
FLOOR
CONCRETE HOUSEKEEPING PAD
NORMALLY CLOSED
FULL LINE SIZE BY-PASS
PRESSURE REGULATING
VALVE AND CHECK VALVE
TYPICAL SHUT OFF VALVE
TYPICAL CHECK VALVE
CW TO
BUILDING
SERVICE
CW FROM BFP'S, AND
WATER METERS
NOTE: REFER TO SCHEDULE AND SPECIFICATIONS FOR ACTUAL QUANTITY OF PUMPS.
3/4"HW
3/4"CW
BALL VALVE
CHECK VALVE
THERMAL EXPANSION
TANK ET-1
SUPPORT FROM
STRUCTURE
VACUUM RELIEF
VALVE
ASME APPROVED TEMP. &
PRESSURE RELIEF VALVE.
TERMINATE RELIEF DRAIN LINE OVER
MOP BASIN OR NEAREST FLOOR
DRAIN WITH MINIMUM 4" AIR GAP
PAN ASSEMBLY DRAIN,
TERMINATE OVER MOP BASIN
OR NEAREST FLOOR DRAIN
WITH MINIMUM 4" AIR GAP
ELECTRIC
WATER
HEATER
DWH-3
TANK
DRAIN
SUPPORT PLATFORM ASSEMBLY
WITH DRAIN PAN AND SUPPORT
BRACKETS. EQUAL TO HOLDRITE
#50-SWHP-M. INSTALL PER
MANUFACTURER'S REQUIREMENTS
ALL-THREAD
SUPPORT
RODS
UNION
(TYPICAL)
THERMOMETER
CW
HW
FINISH HEIGHT OF
ROOF HYDRANT TO BE
MIN OF 3'-0" A.F.R.
ROOF MEMBRANE
1/8" N.P.T. DRAIN HOLE
CONNECT TO 1/2" DRAIN PIPE
AND TERMINATE OVER FLOOR
DRAIN 3/4" COLD WATER
PENETRATION BOOT & FLASHING TO
MEMBRANE ROOFING BY ROOFING
CONTRACTOR. REFER TO MANUFACTURER'S
RECOMMENDATIONS FOR INSTALLATION
PROVIDE STAINLESS STEEL
CLAMPING BAND
SURE SEAL WATER CUT-OFF MASTIC
ROOF DECK -SEE ARCHITECTURAL
DRAWINGS FOR CONSTRUCTION
OPENING IN DECK BY PLUMBING
CONTRACTOR
HEAD CASTING
DUAL CHECK
VALVE
3/4" HOSE CONNECTION
HANDLE
WATER TIGHT SEAL
UNDER DECK FLANGE
MOUNTING BOLTS (4)MIN OF 10"11700201
No.
STATE OFJOSEPHR.BO
L
Y
ARDPROFES
S
IONA L E N G INEERDATE SIGNED 08/31/21
R E G I S T ER
E
D
I
ND I A N A
18166
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION
DOCUMENTS
GRJK800 West Monon Green Blvd.P-601
PLUMBING DETAILS
08/31/202108/31/2021
NOT TO SCALE
APT. WATER HEATER & FAN COIL UNIT DETAILA
NOT TO SCALE
CLOTHES WASHER BOX PIPING DETAILB
NOT TO SCALE
DISHWASHER/DISPOSAL DETAILC
NOT TO SCALE
EXTERIOR CLEANOUT DETAILD
NOT TO SCALE
FIRE SERVICE CONNECTIONE
NOT TO SCALE
RECESSED WATER VALVE BOX DETAILF
NOT TO SCALE
INTERIOR CLEANOUT DETAILG
NOT TO SCALE
MULTIPLE WATER METER PIPING DETAILH
NOT TO SCALE
NO HUB CLEANOUT W/ ACCESS DOOR DETAILI
NOT TO SCALE
PIPE HANGER DETAILJ
NOT TO SCALE
ROOF DRAIN DETAIL (W/ EXTENSION)K
NOT TO SCALE
ROOF OVERFLOW DRAIN DETAIL (W/ EXTENSION)L
NOT TO SCALE
TRAPEZE DETAILM
NOT TO SCALE
UNIT RECESSED WALL VALVE BOX DETAILN
NOT TO SCALE
VENT THRU ROOF DETAILO
NOT TO SCALE
WALL/FLOOR SLEEVE DETAILP
NOT TO SCALE
WATER BOOSTER PUMP PIPING DETAILQ
NOT TO SCALE
SUSPENDED WATER HEATER PIPING DETAILR
NOT TO SCALE
ROOF HYDRANT DETAILS