A002Carmel OverlookSTEMTREE LEARNING CENTER5790 E. Main StreetCarmel, IN 46033INSTRUCTIONS
GENERAL REQUIREMENTS -SUMMARY OF WORK
ALL SUBSTITUTION FOR SPECIFIED PRODUCTS SHALL BE BY WRITTEN APPROVAL OF THE ARCHITECT.
BIDDING PROCEDURE AND CONSIDERATION OF BIDS SHALL BE PROVIDED BY THE PROJECT MANAGER.
STUDIO 3 DESIGN TO PROVIDE ADDITIONAL INSTRUCTIONS.
THE PROJECT CONSISTS OF THE REMODEL OF A FORMER PIZZA HUT EXPRESS FOR USE BY ClusterTruck AS A KITCHEN FACILITY.
ARCHITECTURAL WORK IS LIMITED TO A SMALL PORTION OF NEW WALL AND SOME CEILING WORK AT THE FRONT AREA. ALL
EXISTING FINISHES ARE TO REMAIN .
CONSTRUCTION ACTIVITIES AND OPERATIONS SHALL BE LIMITED TO THE PROJECT AREA INDICATED ON THE DRAWINGS.
PORTIONS OF THE SITE BEYOND AREAS IN WHICH CONSTRUCTION OPERATIONS ARE INDICATED ARE NOT TO BE DISTURBED.
ACCESS TO SITE IS TO BE AVAILABLE TO PM/ARCHITECT AT ALL TIMES.
GENERAL CONSTRUCTION SPECIFICATIONS
THESE SPECIFICATIONS COVER CERTAIN PARTS OF THE GENERAL CONSTRUCTION PORTION OF THE PROJECT AS DESIGNED
BY STUDIO 3 DESIGN, 8604 ALLISONVILLE ROAD SUITE 330, INDIANAPOLIS, IN 46250.
INVITATION TO BID WILL BE PERFORMED BY THE PROJECT MANAGER.
CONTRACT REQUIREMENTS
THE CONTRACT DOCUMENTS INDICATE THE GENERAL ARRANGEMENT AND SCOPE AND IF ANY DEVIATIONS ARE NECESSARY,
SUCH DEVIATIONS SHALL BE MADE IN WRITING TO THE ARCHITECT FOR APPROVAL.
THE ARCHITECT RESERVES THE RIGHT TO MAKE MINOR CHANGES (MAX 10'-0") IN LOCATION OF DEVICE SYSTEMS OR EQUIPMENT.
ALL WORK MUST BE IN ACCORDANCE WITH ALL FEDERAL, STATE AND LOCAL LAWS, ORDINANCES, AND RULES DEALING WITH THE
WORK. ALL SUCH LAWS, ORDINANCES, AND RULES ARE HEREBY MADE A PART OF THIS SPECIFICATION BY REFERENCE.
CONSTRUCTION SCHEDULE
INFORMATION TO BE PROVIDED BY GENERAL CONTRACTOR IN TANDEM WITH STUDIO 3 DESIGN.
OPERATING AND MAINTENANCE MANUAL
FURNISH OPERATING AND MAINTENANCE MANUAL FOR ALL EQUIPMENT, MATERIALS, AND SYSTEMS INSTALLED IN A 3 RINGED
HARD BACK LOOSE LEAF BINDER.
CONTENTS
1. VENDORS AND LISTING INCLUDING NAMES, ADDRESSES AND PHONE
2. MANUFACTURERS PUBLISHED LITERATURE
3. LISTS AND LOCATIONS OF CIRCUITS, VALVES, DAMPERS, ETC.
4. INDEX
5. INSTRUCTIONS ON OPERATIONS AND MAINTENANCE
6. REPLACEMENT PART INFORMATION
7. GUARANTEES AND WARRANTIES ISSUED
8. SHOP DRAWINGS
SCHEDULE OF VALUES
INFORMATION TO BE PROVIDED BY CONTRACTOR.
PROJECT CLOSE OUT
WHEN THE CONTRACTOR CONSIDERS THE WORK SUBSTANTIALLY COMPLETE, THEY SHALL SEND STUDIO 3 DESIGN AND THE
OWNER NOTICE OF SUBSTANTIAL COMPLETION. ATTACH TO THE NOTICE THE CONTRACTOR PUNCH LIST. UPON RECEIPT THE
ARCHITECT SHALL SCHEDULE A PRELIMINARY INSPECTION. AFTER UNACCEPTABLE OF INCOMPLETE WORK HAS BEEN CORRECTED
CONTRACTOR SHALL NOTIFY ARCHITECT WHO WILL SCHEDULE A FINAL INSPECTION. SHOULD THE ARCHITECT DETERMINE THE
WORK IS SUBSTANTIALLY COMPLETE A CERTIFICATE OF SUBSTANTIAL COMPLETION. THE OWNER MAY ASSUME OCCUPANCY UPON
RECEIPT OF CERTIFICATE OF SUBSTANTIAL COMPLETION.
CUTTING AND PATCHING
PROVIDE LABOR AND MATERIAL TO CUT AND PATCH AS SHOWN OR IMPLIED ON DRAWINGS. OPENINGS MADE IN EXISTING
CONCRETE CONSTRUCTION FLOOR INSTALLATIONS OF NEW PIPING, ETC, SHALL BE DIAMOND CUT. RESTORE WORK WHICH HAS
BEEN CUT OR REMOVED AND INSTALL NEW PRODUCTS TO PROVIDE COMPLETED WORK. REFINISH ENTIRE SURFACES AS
NECESSARY TO PROVIDE EVEN FINISH.
CLEANING
PROVIDE ALL REQUIRED PERSONNEL EQUIPMENT AND MATERIAL NECESSARY TO MAINTAIN THE SPECIFIED STANDARD OF
CLEANLINESS, WEEKLY, AND MORE OFTEN IF NECESSARY INSPECT AND PICK UP SCRAP, DEBRIS, AND WASTE MATERIAL. DUST
CONTROLS MUST BE MAINTAINED THROUGHOUT CONSTRUCTION. SWEEP ALL INTERIOR SPACES. CLEAN IMMEDIATELY PRIOR TO
THE DATE SET FOR THE ARCHITECT'S PRELIMINARY INSPECTION. REMOVE ALL DEBRIS, VACUUM ALL FLOORS AND LEAVE OTHER
SURFACES DUST FREE AND CLEAN. FINAL CLEANING, CONTRACTOR SHALL PROVIDE A LEVEL OF CLEANLINESS GENERAL
PROVIDED BY COMMERCIAL BUILDING MAINTENANCE SUBCONTRACTORS.
CAST-IN-PLACE CONCRETE
CONCRETE WORK SHALL CONFORM TO THE FOLLOWING CODES, SPECIFICATIONS AND STANDARDS.
ACI 301 "Specifications for Structural Concrete".
ACI 318 "Building Code Requirements for Structural Concrete".
Concrete Reinforcing Steel Institute (CRSI), "Manual of Standard Practice".
ACI 311 "Standard Specifications for Tolerances for Concrete Construction and Materials".
Portland Cement Association "Positioning Welded Wire Fabric".
ASTM C1116, Type III "Standard Specifications for Fiber Reinforced Concrete and Shotcrete".
THE FOLLOWING ITEMS ARE ADDITIONS AND/OR MODIFICATIONS TO THE CODES, SPECIFICATIONS AND STANDARDS NOTED
ABOVE.
CONCRETE FOR SLABS TO BE 3500 PSI, FOUNDATIONS AND OTHER WORK SHALL BE MINIMUM 3,000 PSI AT 28 DAY TEST WITH 4
INCH MAXIMUM SLUMP. CONCRETE FOR EXTERIOR WALLS AND FLAT WORK SHALL BE MINIMUM 4,000 PSI AT 28 DAY TEST WITH 4
INCH MAXIMUM SLUMP AND 6% AIR-ENTRAINMENT, PLUS OR MINUS 1% CEMENT FOR ALL CONCRETE SHALL BE TYPE I, MAXIMUM
COURSE AGGREGATE SIZE SHALL BE 1 INCH. EXCEPT FOR AIR-ENTRAINMENT, ADMIXTURES SHALL NOT BE USED.
PROVIDE THE MINIMUM THICKNESS OF COMPACTED GRANULAR FILL SHOWN ON THE DRAWINGS UNDER ALL INTERIOR FLOOR
SLABS PLACED ON GRADE. FILL SHALL BE COMPACTED TO 95% OF ITS MAXIMUM DENSITY AT OPTIMUM MOISTURE CONTENT, AS
DETERMINED BY THE MODIFIED PROCTOR TEST, ASTM D-1557. ALL GRANULAR FILL MATERIAL PLACED UNDER FLOOR SLABS SHALL
BE GOOD, CLEAN MATERIAL WITH LESS THAN 5% PASSING A 200 SIEVE . A 6 MIL POLYETHYLENE VAPOR BARRIER SHALL BE
PLACED ON TOP OF THE GRANULAR FILL IN ALL INTERIOR SLAB AREAS. LAPS SHALL BE A MINIMUM OF 6 INCHES. TURN UP VAPOR
BARRIER AT ALL VERTICAL SURFACES. ELECTRICAL CONDUITS OR OTHER UNDERFLOOR PIPES, DUCTS OR RACEWAYS SHALL BE
PLACED WITHIN THE GRANULAR FILL SUCH THAT A MINIMUM 2 INCH DEEP COVER IS PROVIDED.
REINFORCING STEEL SHALL CONFORM TO ASTM A-615, GRADE 60. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 1064 AND
SHALL BE PLACED IN ALL SLABS, EXTENDING THROUGH ALL CONSTRUCTION AND CONTROL JOINTS UNLESS OTHERWISE SHOWN.
NYCON IS AN APPROVED EQUIVALENT.
EXPANSION MATERIALS SHALL BE NON-EXTRUDING TYPE FOR ALL INTERIOR AND EXTERIOR WORK, 1/2 INCH THICK X WIDTH
REQUIRED, AGAINST ALL VERTICAL SURFACES AND WHERE OTHERWISE SHOWN.
CONSTRUCTION JOINTS IN SLABS SHALL BE OF 24 GAUGE GALVANIZED STEEL WITH KEY WAY, INSTALLED FOR PERMANENT
INSTALLATION. AN EQUIVALENT TO A FORMED KEY WAY SHALL BE # 4 SMOOTH DOWELS, 12" LONG, AT 24' ON CENTER. CONTROL JOINTS
IN SLABS SHALL BE A CONTINUOUS 1/8 INCH WIDE X 1 INCH DEEP CONTINUOUS SAW CUT. THICKEN SLABS AT ALL CONTROL JOINTS.
INTERIOR AND EXTERIOR FLAT WORK SHALL BE CURED USING A COMPOUND EQUAL TO SONNEBORN "KURE-N-SEAL", COMPATIBLE WITH
FINISH MATERIALS APPLIED TO FINISHED FLOOR SLABS. APPLY CURING COMPOUND IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS AND RECOMMENDATIONS. INTERIOR FLAT WORK SHALL RECEIVE STEEL TROWEL FINISH, EXTERIOR FLAT WORK SHALL
RECEIVE A LIGHT BROOM FINISH.
METAL SCREW TYPE STUDS FOR INTERIOR WALLS SHALL BE AS SHOWN ON PLANS X 25 GAUGE STUDS AT 16 OR 24 INCHES ON CENTER,
AS SHOWN. STANDARD FLOOR AND CEILING TRACKS SHALL BE USED. WALLS SHALL BE BRACED AS REQUIRED OR SHOWN TO MAINTAIN
STRAIGHTNESS.
PROVIDE ALL MISCELLANEOUS STEEL SHOWN ON THE DRAWINGS FOR INJECTOR SUPPORT. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS AND ALL APPLICABLE CODES.
METALS
CONSTRUCTION LUMBER SHALL BE EQUAL TO DOUGLAS FIR, OR #2 HEM FIR KILN DRIED TO A MOISTURE CONTENT OF 19% OR LESS,
DRESSED LUMBER SHALL BE RED OAK, POPLAR, CLEAR WHITE PINE OR BIRCH, KILN DRIED TO A MOISTURE CONTENT OF 15% OR LESS
AND FIRE TREATED.
LUMBAR USED FOR BLOCKING, CURBS, CANTS, ETC., SHALL BE FIRE TREATED OR WHERE IN CONTACT WITH THE ELEMENTS SHALL BE
EQUAL TO #2 SOUTHERN PINE (15% MOISTURE CONTENT) PRESERVATIVE TREATED.
PLYWOOD FOR BLOCKING SHALL BE FIRE RETARDANT TREATED C-C INT APA WITH EXTERIOR GLUE OR OTHER MISCELLANEOUS
FASTENINGS.
PROVIDE BLOCKING AS REQUIRED IN WALL, PARTITIONS, ETC., TO RECEIVE HARDWARE, OR OTHER MISCELLANEOUS FASTENINGS.
MILLWORK TO COMPLY WITH ALL PERTINENT CODES AND REGULATIONS, ALSO COMPLY WITH "ARCHITECTURAL WOODWORK QUALITY
STANDARDS, GUIDE SPECIFICATION AND QUALITY CERTIFICATION PROGRAM" PUBLISHED BY THE ARCHITECTURAL WOODWORK
INSTITUTE. ALL INTERIOR WORK SHALL CONFORM TO PREMIUM GRADE. INTERIOR AWI QUALITY GRADE: PREMIUM GRADE FOR
TRANSPARENT FINISH, EXTERIOR: AWI QUALITY GRADE: ECONOMY GRADE FOR OPAQUE FINISH.
CUSTOM CASEWORK SHALL BE FABRICATED IN ACCORDANCE WITH ARCHITECTURAL WOODWORKING INSTITUTE'S PREMIUM GRADE
QUALITY STANDARD. CONTRACTOR SHALL COORDINATE LOCATION OF BLOCKING BEHIND ALL CASEWORK MOUNTING. IT IS
SUBCONTRACTOR'S RESPONSIBILITY TO FIELD MEASURE TO ASSURE PROPER FIT. FINISH AS NOTED IN MATERIALS LIST. GENERAL
PURPOSE-150 GRADE 10/HGS, .048" THICKNESS. VERTICAL SURFACING-150 GRADE 55/VGS .048" THICKNESS. CABINET LINER TO BE 150
GRADE 72/CLS: .02" THICKNESS. CORE BOARD SHALL BE 3/4" THREE-PLY, FINE-SURFACED, MEDIUM-DENSITY FIBER BOARD. BACK AND
DRAWER BOTTOM TO 1/4", SHELVES OVER 36" TO BE 1" FLUSH OVER LAY DESIGN. COLORS AS SPECIFIED IN MATERIALS LIST.
HARDWARE-HEAVY DUTY INSTITUTIONAL QUALITY
1. DRAWER SLIDES: ACCURIDE 3832
2. FILE DRAWER SLIDES ACCURIDE 3640
3. KEYBOARD SLIDES ACCURIDE 2009
4. SHELF STANDARDS HAFELE "EX-CELLENT H" #282.23.725-CABINET MOUNTED
5. SHELF STANDARDS K&V 186ANO OR 187ANO-87 STANDARDS-WALL MOUNT
6. GROMMETS HAFELE 429.99.32
7. HINGES, CONCEALED GRASS 3900 SERIES
8. PULLS, BAR
9. CATCH, MAGNETIC STANLEY SP46
10. CATCH, SPRING HAFELE 245.55.913
11. BRACKET, COUNTER STANLEY 796
12. CLOTHES ROD K&V 7705 AND 764 CHR FLANGES
TWO HINGES PER DOOR UP TO 35 1/2" H
THREE HINGES PER DOOR 35 1/2" H TO 63" H
CARPENTRY
FIBERGLASS WALL INSULATION SHALL BE 3-5/8" (R-11) THICK BATTS AS SHOWN, UNFACED FRICTION-FIT, SOUND BATTS. CONSULT
ARCHITECT FOR ALL OTHER WALL SIZES.
THERMAL PROTECTION
GYPSUM WALLBOARD SHALL BE EQUAL TO USG "SHEET ROCK", 48" WIDE X THICKNESS, FIRE RATING, AND LEAD BACKED AS SHOWN,
WITH TAPERED EDGES. USE WALLBOARD OF MAXIMUM LENGTH TO MINIMIZE END JOINTS. END JOINTS SHALL OCCUR OVER STUDS OR
BLOCKING. APPLY WALLBOARD WITH LENGTH OF BOARDS HORIZONTAL. APPLY JOINT TAPE AND SPACKLING COMPOUND IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. SAND JOINTS SMOOTH SURROUNDING WALLBOARD SURFACE.
SCREW GYPSUM WALLBOARD TO STUDS OR OTHER FRAMING MEMBERS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
JOINT CEMENT AND REINFORCING TAPE SHALL BE MANUFACTURER'S STANDARD. METAL TRIM SHALL BE EQUAL TO USG METAL TRIM AS
NOTED BELOW:
CORNER BEAD: USG "DUR-A-BEAD"
METAL TRIM (SPACKLE-IN TYPE): USG #200-B
METAL TRIM (J-MOULD TYPE): USG #400
CONTROL JOINT: USG #1093 AT 32 FEET ON CENTER MAX.
GYPSUM WALL BOARD
MEET REQUIREMENTS OF ASTM E-814-13a THROUGH PENETRATION FIRE TEST BY A NATIONALLY RECOGNIZED TESTING AGENCY.
INSTALLER SHALL SPECIALIZE IN FIRE STOPPING WITH NO LESS THAN ONE YEAR EXPERIENCE AND APPROVED BY THE MANUFACTURER.
WORK SHALL BE COORDINATED WITH ALL OTHER TRADES. CONTRACTOR TO VERIFY OWNER'S SYSTEM PREFERENCE PRIOR TO
RELEASING CONTRACTS.
ACCEPTABLE MANUFACTURERS:
A. PENETRATION SEALANTS
1. DOW CORNING FIRE STOP FOAM AND FIRE STOP SEALANT
2. 3M BRAND FIRE BARRIER CAULK
3. HILTI FIRESTOPP MATERIALS
B. INTUMESCENT SEALANTS
1. DOW CORNING FIRE STOP INTUMESCENT WRAP STRIP
2. 3M BRAND FIRE CAULK
3. HILTI INTUMESCENT FIREPROOFING
FIRE STOPPING
HOLLOW METAL FRAMES SHALL BE COLD ROLLED STEEL, OF GAUGES LISTED, HAVING ADJUSTABLE BASE ANCHORS AND THREE STUD
ANCHORS PER JAMB. FRAMES SHALL BE MORTISED AND REINFORCED TO RECEIVE REQUIRED HARDWARE. STRIKE JAMBS SHALL HAVE
THREE RUBBER SILENCERS. FRAMES SHALL BE BONDERIZED AND SHALL RECEIVE ONE SHOP COAT OF PRIMER.
INTERIOR FRAMES: 18 GAUGE EXTERIOR FRAMES: 16 GAUGE
HOLLOW METAL KNOCK DOWN FRAMES WILL BE ACCEPTABLE WHERE SHOWN ON DRAWINGS.
DOOR HARDWARE, SPECIALTY DOORS AND OVERHEAD DOORS SHALL BE AS SPECIFIED ON DRAWINGS.
HOLLOW METAL DOORS AND FRAMES
FLUSH INTERIOR WOOD DOORS TO BE EQUAL TO MASONITE ASPIRO SERIES SELECT WOOD VENEER (5-PLY CONSTRUCTION): PREMIUM
SELECT VENEER, WITH HARDWOOD VENEER CROSSBAND. HARDWOOD TOP, SIDE AND BOTTOM EDGES TO MATCH FACE VENEER.
OPENINGS FOR LOUVERS OR GLASS LIGHTS SHALL BE SHOP MADE: USE WOOD MOLDINGS FOR GLASS LIGHT FRAMES. FACTORY OR
FIELD FINISH SATIN TOPCOAT PER THE MATERIALS LIST.
PROVIDE WARRANTY AGAINST WARPING OR TELEGRAPHING OF CORE CONSTRUCTION FOR THE LIFE OF THE INSTALLATION.
PRE-FINISHED DOORS MAY BE APPROVED EQUAL. SUBMIT COLOR SAMPLE TO ARCHITECT.
SEE MATERIALS LIST AND DOOR SCHEDULE FOR VENEER AND FINISH SELECTIONS.
FLUSH WOOD DOORS
COORDINATE THE FURNISHING AND INSTALLATION OF ALL HARDWARE ITEMS WITH DOORS, FRAMES, AND OTHER RELATED ITEMS TO
DETERMINE THE SUITABILITY OF ALL SPECIFIED HARDWARE.
ALL HARDWARE SHALL MEET FEDERAL, STATE AND LOCAL CODES. ANY HARDWARE PROVIDED THAT IS NOT IN CONFORMANCE WITH THE
CODES SHALL BE REPLACED AT NO ADDITIONAL COST TO THE OWNER.
FINISHES SHALL BE US26D DULL CHROME UNLESS OTHERWISE NOTED.
FINISH HARDWARE
HARDWARE STANDARDS -U.N.O.
1. BUTTS & HINGES: HAGER, MCKINNEY, STANLEY
A. CONTINUOUS HINGES: PEMKO
2. LOCK SETS: BEST
3. CYLINDERS: BEST, SCHLAGE
4. HOSPITAL LATCHES: GLYNN JOHNSON, SERGEANT
5. ROLLER LATCHED: GLYNN JOHNSON
6. FLUSH BOLTS: HAGER, IVES, ROCKWOOD
7. PANIC EXIT DEVICES: VONDUPRIN, SERGEANT
8. CLOSERS & LIFE SAFETY HARDWARE: LCN, STANLEY
9. PULLS & PUSH PLATES: FORMS & SURFACES
10. ASTRAGALS: NATIONAL GUARD, PEMKO
11. DOOR ARMOR (PLASTIC): CONSTRICTION SPECIALTIES
12. DOOR ARMOR (STAINLESS): HAGER
13. STOPS: HAGER, HIAWATHA, IVES
14. COORDINATOR: DOOR CONTROL INTERNATIONAL
15. ELECTRONIC DOOR HOLDER: RIXON
16. SILENCERS: GLYNN JOHNSON
17. SLIDING DOOR LOCK: ADAMS RITE
18. THRESHOLDS: NATIONAL GUARD, PEMKO
19. WEATHER STRIPPING: NATIONAL GUARD, PEMKO
20. SWEEPS: NATIONAL GUARD,PEMKO
21. PIVOT HINGES: RIXON, MCKINNEY, STANLEY
22. FLOOR CLOSER/PIVOTS: RIXON
23. WALL TYPE HOLDER: MODRIC
24. ELECTROMAGNETIC LOCK: SARGENT
25. SMOKE SEAL: PEMKO
26. AUTOMATIC DOOR BOTTOMS: NATIONAL GUARD
27. ELECTROMAGNETIC HOLD OPEN: SARGENT
EXCEPT WHERE LABEL PROVISIONS REQUIRE LARGER OR HEAVIER HINGES OR WHERE SPECIFIED OTHERWISE HEREIN. PROVIDE
HINGES OF THE FOLLOWING SIZES AND WEIGHTS:
1. DOORS LESS THAN 3'-6" WIDE: 3 PAIR 4-1/2" X 4-1/2" OR CONTINUOUS (STANDARD)
2. DOORS 3'-6" WIDE TO 4'-0" WIDE: 3 PAIR 5" X 4-1/2" OR CONTINUOUS (EXTRA HEAVY)
3. DOORS 5'-0" HIGH AND NOT OVER 7'-6" HIGH: 1-1/2 PAIR OR CONTINUOUS
4. DOORS 7'-6" HIGH AND NOT OVER 10'-0" HIGH: 2 PAIR OR CONTINUOUS
5. AUTOMATIC DOORS: 5" X 4-1/2" (2 PAIR) OR CONTINUOUS
COORDINATION OF KEYS AND KEYING:
1. ALL LOCKS SHALL BE KEYED, MASTER KEYED, AND GRAND MASTER KEYED. AFTER AWARD OF CONTRACT, THE HARDWARE
SUPPLIER SHALL CONFER WITH THE OWNER TO DETERMINE KEYING SYSTEM. SUBMIT A KEYING DIAGRAM AFTER THIS
CONFERENCE.
2. SUPPLY (6) MASTER KEYS AND (3) GRAND MASTER KEYS. EACH LOCK SHALL HAVE (2) INDIVIDUAL KEYS.
3. KEYS SHALL BE STAMPED AS DIRECTED BY OWNER.
4. ALL MASTER KEYS AND GRAND MASTER KEYS SHALL BE SENT TO THE OWNER VIA REGISTERED MAIL SUPPLIER.
A. BLOCKING
I. COORDINATE BLOCKING IN WALL BEHIND WALL STOPS, ELECTROMAGNETIC DOOR HOLDERS.
MOUNTING HEIGHTS:
1. UNLESS SPECIFIED OTHERWISE, HARDWARE MOUNTING HEIGHTS SHALL BE AS FOLLOWS, MEASURED FROM FINISHED FLOOR
LINE (TO CENTER LINE OR AS STATED):
A. STRIKE: 40-5/16"
B. EXIT DEVICE CROSS BAR: 39-13/16"
C. PUSH PLATES: 46"
D. PULL: 46"
2. COMPLY WITH CURRENT STANDARDS FOR HANDICAPPED ACCESS, INCLUDING UNITED STATES ARCHITECTURAL AND
TRANSPORTATION BARRIERS COMPLIANCE BOARD (A&T BCB) "MINIMUM GUIDELINES AND REQUIREMENTS FOR ACCESSIBLE
DESIGN, FINAL RULE" AND ANSI A117.1 (2009).
INSTALL ALL JOINT SELANTS PER MANUFACTURER'S INSTRUCITONS. EQUAL SUBSTITUTIONS ALLOWED UPON REVIEW AND APPROVAL
BY ARCHITECT. SEALANT WORK SHALL BE PERFORMED BY A CONTRACTING SPECIALIZING IN PERFORMING SEALANT WORK WITH A
MINIMUM OF 3 YEARS OF EXPERIENCE.
TYPE A JOINTS IN CONCRETE AND TILE FLOORS AND PAVED SURFACES SUBJECT TO FOOT TRAFFIC:
MULTIPLE COMPONENT, SELF-LEVELING POLYURETHANE BASED SEALANT CONFORMING TO ASTM C920,
TYPE M, GRADE P, CLASS 25.
A. MAMECO INTERNATIONAL VULKEM 245.
B. SIKA CORPORATION SIKAFLEX 2C-SL.
C. SONNEBORN BUILDING PRODUCTS SONOLASTIC PAVING JOINT SEALANT.
D. TREMCO THC-900.
E. PECORA CORPORATION NR-200.
TYPE B EXTERIOR JOINTS IN MASONRY AND EIFS AND AROUND METAL DOOR, WINDOW AND LOUVER FRAMES
PENETRATING THESE SURFACES. DO NOT USE SINGLE COMPONENT SEALANTS WHEN EXCESSIVE
MOVEMENT IS EXPECTED WITHIN THE CURING TIME OF THE SEALANT:
SINGLE OR MULTIPLE COMPONENT, NON-SAG, POLYURETHANE-BASED SEALANT CONFORMING TO ASTM C920, TYPE S OR
M, GRADE NS, CLASS 25.
A. MAMECO INTERNATIONAL, VULKEM 116 OR 227.
B. SIKA CORPORATION SIKAFLEX 1A OR 2C-NS.
C. SONNEBORN BUILDING PRODUCTS SONOLASTIC NP I OR NP II.
D. TREMCO DYMONIC OR DYMERIC.
E. PECORA CORPORATION DYNATROL II.
TYPE C INTERIOR WALL PENETRATIONS FOR PIPE AND CONDUIT THAT WILL BE CONCEALED BY ESCUTCHEONS AND
OTHER TRIM AND PLATE, AND FORLAP JOINTS IN SHEET METAL, FOR ALL PENETRATIONS IN THE
CONCESSION AREAS NOT EXPOSED TO VIEW:
BUTYL RUBBER BASED SEALANT CONFORMING TO FS TT-S-001657, TYPE 1.
A. ADCO SEAL NO. B-100.
B. PECORA CORPORATION BC-158.
C. PTI SEALANTS NO 707.
D. TREMCO BUTYL SEALANT.
TYPE D JOINTS, VOIDS AND PENETRATIONS NOT OTHERWISE SPECIFIED FOR INTERIOR SURFACES EXPOSED TO
VIEW AND REQUIRING PAINTING. FIXTURES, PARTITIONS, EQUIPMENT AND ACCESSORIES FASTENED TO WALLS
AND FLOORS, FLANGES, AND ESCUTCHEONS OF ITEMS PENETRATING SURFACES IN CONCESSIONS, TOILET ROOMS,
AND OTHER AREAS REQUIRING SANITARY CONDITIONS TO ELIMINATE ANY OPEN JOINTS BETWEEN CONTACT
SURFACES:
LATEX ACRYLIC BASED SEALANT CONFORMING TO ASTM C834.
A. DOW CORNING CORPORATION NO. 795.
B. GENERAL ELECTRIC COMPANY SILPRUF.
C. SONNEBORN BUILDING PRODUCTS OMNISEAL.
D. TREMCO SPECREM 1.
TYPE E EXTERIOR AND INTERIOR JOINTS IN CONTACT WITH ORGANICALLY-COATED ALUMINUM:
LOW MODULUS SILICONE SEALANT CONFORMING TO ASTM C920, TYPE S, GRADE NS, CLASS 25.
A. DOW CORNING NO. 792.
B. GENERAL ELECTRIC SILPRUF.
C. SONNEBORN OMNISEAL.
D. TREMCO SPECREM 1.
TYPE F PERIMETER AND TACK SEAT JOINTS AROUND SOUND-RETARDANT PARTITIONS AND ELECTRICAL BOXES
AND OTHER PENETRATIONS IN SUCH PARTITIONS:
COMPOUND: PERMANENTLY RESILIENT TYPE MANUFACTURED SPECIFICALLY FOR ACOUSTICAL APPLICATIONS.
A. USG ACOUSTICAL SEALANT.
B. TREMCO ACOUSTICAL SEALANT.
BACKER ROD MATERIAL: CLOSED-CELL FOAM, NON-STAINING, RESILIENT MATERIAL SUCH AS NEOPRENE, BUTYL, OR POLYURETHANE,
COMPATIBLE WITH SEALANT TO BE USED. SIZED AND SHAPED TO CONTROL DEPTH OF SEALANT AND TO PROVIDE 20 TO 50 PERCENT
COMPRESSION UPON INSERTION.
SEALANT INSTALLATION, INCLUDING SURFACE PREPARATION, BACK-UP MATERIALS AND SEALANT CURING, SHALL BE IN ACCORDANCE
WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. CONTROL JOINTS IN ALL SURFACES AND MATERIALS SHALL HAVE
PROPER BACKER ROD, IN ACCORDANCE WITH SEALANT MANUFACTURER'S RECOMMENDATION, INSTALLED IN JOINTS BEFORE SEALANT
INSTALLATION.
SEALANT WORK FOR THE GLASS AND GLAZING WORK SHALL BE PERFORMED BY THE GLASS AND GLAZING CONTRACTOR.
PROVIDE 2 TUBES EA. COLOR AND TYPE UTLILZED FOR OWNER'S FUTURE USE.
CAULKING AND JOINT SEALANTS
ALL SURFACES TO BE PAINTED OR STAINED SHALL BE PROPERLY PREPARED BEFORE STARTING THE PAINTING WORK SHOP OR PRIME
COATS SHALL BE PUT IN GOOD ORDER BEFORE PAINTING BEGINS. WOOD SHALL BE SMOOTH AND FREE FROM RAISED GRAIN OR OTHER
SURFACE IMPERFECTIONS. METAL SURFACES SHALL BE WIRE BRUSHED TO REMOVE ALL RUST OR MILL SCALE. BEFORE PAINTING,
REMOVE OR PROTECT HARDWARE, ACCESSORIES, PLATES, LIGHT FIXTURES AND SIMILAR ITEMS AND REPLACE UPON COMPLETION OF
THE PAINTING OPERATION.
APPLY PAINT OR STAIN TO CLEAN, DRY AND SMOOTH SURFACES ONLY. DO NOT APPLY EXTERIOR PAINT OR STAIN IN DAMP, RAINY
WEATHER OR UNTIL ALL SURFACES HAVE THOROUGHLY DRIED. ALL WOOD AND METAL SURFACES SHALL BE SANDED SMOOTH BEFORE
AND BETWEEN COATS.
A SCHEDULE OF THE SURFACES TO BE PAINTED FOLLOWS:
SCHEDULE OF SURFACES
INTERIOR UNGALVANIZED FERROUS METAL
1 COAT NOXIDE ONE DAY PRIMER (IF UNPRIMED)
2 COATS CELLU-TONE SATIN
GYPSUM BOARD SOFFITS
1 COAT PVA PRIMER
2 COATS LATEX (EGGSHELL)
GYPSUM BOARD WALLS AND SOFFITS TO RECEIVE VWC
TO BE PRIMED
1 COAT PRIMER-SEALER
2 COATS FINISH COLOR
WOOD DOORS, WOOD CABINETWORK AND WOOD TRIM
UNLESS OTHERWISE NOTED, STAIN TO MATCH EXISTING.
SUBMIT FOR APPROVAL
1 COAT STAIN
3 COATS POLYURETHANE-LOW GLOSS
1 COAT LACQUER SEALER ON CONCEALED SURFACES OF WOOD TRIM.
SCHEDULE OF COLORS PER MATERIALS NOTED.
UNLESS NOTED OTHERWISE PAINT MISC.. METALS, ELECTRICAL AND TELEPHONE PANELS, FIRE EXTINGUISHER CABINETS (VERIFY),
EXPOSED EQUIPMENT SUPPORT, CASEWORK AND PLUMBING SUPPORT BRACKETS, CLEAN-OUT COVERS, COVERS, TO MATCH THE
SURFACE ON WHICH THEY OCCUR. PAINT EXPOSED PIPING IN FINISHED AREAS TO MATCH WALLS. PAINT ALL HOLLOW METAL FRAMES AS
NOTED IN FINISH SCHEDULE, UNLESS NOTED OTHERWISE.
PAINT METAL FRAMES AT VISION LITES IN DOORS TO MATCH DOOR FRAME FINISH, U.N.O.
PAINTED GYPSUM BOARD CEILINGS TO BE CEILING BRIGHT WHITE, U.N.O.
BOTTOMS OF SOFFITS IN PAINTED AREAS TO MATCH CEILING, U.N.O.
PAINT EXPOSED CUT EDGES OF ACM TO MATCH ACM.
PAINTING AND STAINING
ACOUSTICAL CEILING SYSTEM
IN ADDITION TO COMPLYING WITH ALL PERTINENT CODES AND REGULATIONS, CEILING INSTALLATION SHALL COMPLY WITH THE INDIANA
STATE BOARD OF HEALTH AND SHALL MEET CLASS A NFPA
REFERENCE STANDARD SUSPENSION SYSTEM
ARMSTRONG PRELUDE XL
REFERENCE STANDARD ACOUSTICAL CEILING PAD
USG SEE DRAWINGS
ERECT GRID SYSTEM SO THAT BORDERS WILL BE AS LARGE AS POSSIBLE, AVOIDING PERIMETER TILES LESS THAN 1/2 OF TILE SIZE, AND
CENTER GRID IN ROOM, U.N.O. SPACE HANGARS A MAX. OF 4 FEET APART, THERE SHALL BE NO VISIBLE GAPS AT WALL
ALL ACOUSTICAL CEILING PANELS: FLAME SPREAD OF 25 OR LESS PER ASTM E84.
FURNISH TO OWNER TWO UNOPENED CARTONS OF ACOUSTICAL CEILING PADS OF EACH TYPE DELIVERED
SEE CONTRACT DOCUMENTS FOR TYPES OF CEILING SYSTEMS.
PROVIDE MATERIALS AS INDICATED IN CONTRACT DOCUMENTS AND INSTALL ACCORDING TO ALL MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS. CARPET SHALL COMPLY WITH DOC-FFI-70-PILL TEST, ASTM E648 (NFPA 253)-CRITICAL FLUX TEST MIN. .45 WATTS
PER SQUARE CORRIDORS AND EXITS AND .22 WATTS IN ALL OTHER AREAS. DIMENSIONAL STABILITY SHALL BE PLUS OR MINUS .02% WITH
THE AACHEN METHOD.
CARPET AND ADHESIVES SHALL COMPLY WITH STANDARDS FOR A CLASS II OR CLASS B FINISHES.
PROVIDE ATTIC STOCK EQUAL TO 3% OF TOTAL SHEET CARPET AND CARPET TILE IN EACH STANDARD COLOR TO OWNER.
PROVIDE METAL EDGE AND TRANSITION STRIPS AT ALL CHANGE OF MATERIALS.
CARPET
WALL COVERING SHALL COMPLY WITH ASTM E-84 FOR CLASS A, FS CCC-W -408A TYPE II. PROVIDE ONE ROLL OF WALLCOVERING OF
EACH COLOR FROM ORIGINAL STOCK FOR OWNER'S USE. ALL ADHESIVES SHALL BE ONLY THOSE RECOMMENDED BY THE
MANUFACTURER OF THE WALL COVERING. ALL WALL SEALER SHALL BE ONLY THAT RECOMMENDED BY THE MANUFACTURER OF THE
WALL COVERING. SEAL ALL SURFACE TO RECEIVE WALL COVERING. APPLY EVENLY SO THAT NO DEPOSITS OR IRREGULARITIES
TELEGRAPH THROUGH. INSTALL WALL COVERING IN CONSECUTIVE SEQUENCE. WRAP FABRIC 6' BEYOND INSIDE AND OUTSIDE CORNERS
AND NO CUTTING AT CORNERS UNLESS FOR COLOR SEPARATION OR PATTERN MATCH. NO HORIZONTAL SEAMS SHALL BE PERMITTED.
INSTALL WALLCOVERING BEFORE THE INSTALLATION OF PLUMBING FIXTURES, CASINGS BASES, CABINETS, AND SEALANTS.
WALL COVERING
AS NOTED IN CONTRACT DOCUMENTS. INSTALL PER MANUFACTURER'S RECOMENDATIONS.
WALL AND CORNER GUARDS, HANDRAILS
FIRE EXTINGUISHERS, CABINET AND ACCESSORIES
FIRE EXTINGUISHERS: UL LISTED AND LABELED, EQUAL TO J.L. INDUSTRIES, MULTI-PURPOSE DRY CHEMICAL.
TYPE CABINET-EQUAL TO J.L. INDUSTRIES SEMI-RECESSED (VERIFY WITH EXISTING), FULL GLASS PANEL BRUSH SATIN TRIM, BOX STEEL
WITH BAKED ENAMEL FINISH.
FIRE EXTINGUISHERS SERVING MRI AREAS MUST BE WITHIN 75' TO BE MRI SAFE.
ELECTROMAGNETIC AND RADIO SHIELDING
THE SUPPLIER/MANUFACTURER OF THE ELECTROMAGNETIC AND RADIO SHIELDING SHALL BE PRE-APPROVED BY THE MEDICAL
EQUIPMENT SUPPLIER/MANUFACTURER THAT THEIR INSTALLATION CONFORMS WITH THE STANDARDS REQUIRED FOR PROPER
OPERATION OF THE EQUIPMENT BEING SUPPLIED. COMPLETELY DESIGN, FURNISH AND INSTALL THE COMPLETE SHIELDED ENCLOSURE
SYSTEM FOR THE ROOM, INCLUDING ALL SUBFRAMING, ANCHORS, JOINTING, SUBFLOORS, ACCESSORIES, DOORS, AND WINDOWS, AS
WELL AS PENETRATIONS FOR EQUIPMENT. GROUNDING OF THE R-F ENCLOSURE SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
OWNER SHALL BE RESPONSIBLE FOR ALL TESTING AND CONFIRMATION OF SHIELDING COMPLIANCE, U.N.O. ALL WALL AND CEILING
SHIELDING MATERIALS ARE FRAMED OR LAMINATE PANELS MEETING THE MINUMUM REQUIREMENTS STATED IN THE PHYSICIST
SHEILDING REPORT. FLOOR SHIELDING TO HAVE A 6 MIL VAPOR BARRIERS. WOOD FRAMING SHALL BE KILN DRIED AND FIRE RETARDANT.
ALL SEAMS CONTINUOUSLY SOLDERED TOGETHER. ALL SEAMS COVERED WITH APPROPRIATE FOIL TAPE. FASTENERS TO BE NON-
FERROUS, NON-OXIDIZING TYPE INSTALLED PER SHIELDING MANUFACTURER'S CRITERIA.
DOOR UNITS SHALL CONSIST OF REQUIRED LEAVES, FRAMES, THRESHOLD, HARDWARE, AND CONTACT STRIPS. DOOR FRAME TO MEET
REQUIREMENTS NOTED IN PHYSICIST REPORT WITH SPECIFIED WOOD VENEER OR GLASS. DOOR TO HAVE REMOVABLE SWEEP.
WINDOWS TO BE COMPLETE WITH FRAME, RF SCREEN, GLASS, GLASS STOPS AND RF GASKETS. PROVIDE ALL REQUIRED FILTERS AND
WAVE GUIDES FOR ELECTRICAL, HVAC, SPRINKLERS, AND CRYOGEN VENTS SHOWN ON THE DRAWINGS. SUPPLIER/MANUFACTURER TO
PROVIDE WARRANTY THAT THE ENCLOSURE SHALL RETAIN ITS SHIELDING CHARACTERISTICS FOR 5 YEAR PERIOD AFTER TESTING. THE
SHIELD ENCLOSURE SHALL PROVIDE THE REDUCTION OF RF WAVES FROM EXTERNAL TRANSMITTERS AS SPECIFIED BY THE EQUIPMENT
MANUFACTURER AND PHYSICIST REPORT.
TOILET ACCESSORIES
TO BE EQUAL TO BOBRICK, U.N.O.
SHOP DRAWINGS
IF INCLUDED IN THE PROJECT SCOPE, SHOP DRAWINGS AND/OR PRODUCT LITERATURE ON THE FOLLOWING ITEMS SHALL BE
SUBMITTED TO THE ARCHITECT FOR APPROVAL INCLUDING BUT NOT LIMITED TO:
-DOORS AND DOOR HARDWARE -EXTERIOR FINISH MATERIALS
-CASEWORK -WATERPROOFING
-FIRE STOPPING -STEEL (FRAMING, MISC STEEL, STAIRS, REBAR, ETC)
-ACOUSTICAL CEILINGS -ROOFING AND RELATED COMPONENTS
-INTERIOR FINISHES -GLAZING AND STOREFRONT/CURTAIN WALL
-FIRE EXTINGUISHER AND CABINETS -LOCKERS
-ELECTROMAGNETIC AND RADIO SHIELDING -PLUMBING EQUIPMENT / FINISHES
-LIGHT FIXTURES -TOILET ACCESSORIES AND PARTITIONS
-HVAC EQUIPMENT, GRILLES, REGISTERS & DIFFUSERS
SUBSTITUTIONS
GENERAL CONTRACTOR TO SUBIT DATA TO ARCHITECT FOR REVIEW AND CONFIRMAITON OF EQUAL COMPLIANCE PRIOR TO
ALLOWING SUBSTITUIONS. ALL SUBSTITUTION FOR SPECIFIED PRODUCTS SHALL BE BY WRITTEN APPROVAL OF THE
ARCHITECT