HomeMy WebLinkAboutM100 HVAC & PLUMBING FLOOR PLANSS HSS
SHS HS
F.E.C.C
4
5
6
C2
DD
EXISTING
TO REMAIN
RTU ABOVE
250 CFM
10" DIA
250 CFM
10" DIA
250 CFM
10" DIA
175 CFM
8" DIA
75 CFM
6" DIA
250 CFM
10" DIA
250 CFM
10" DIA
250 CFM
10" DIA
250 CFM
10" DIA
250 CFM
10" DIA
C
4
5
6
OPEN AREA
100
LABORATORY
101
OFFICE
103 UTILITY CLOSET
104
TOILET
105
HALL
102
103A104A105AETRETRWH
ABOVE
CONNECT TO EXISTING WATER
LAV
WC
LAV
MOP
4" V
THROUGH ROOF
2"
4"
3"
2"
C.O.
TO
EXISTI
N
G
WA
S
TE MAIN
COLD WATER
HOT WATER
SOIL & WASTE (B.G.)
1. THE PLUMBER WILL SUPPLY AND INSTALL A WATER PRESSURE REGULATOR ON
INCOMING WATER SUPPLY. THE PLUMBER WILL SET THE REGULATOR NOT TO
EXCEED 65 PSI.
2. THE PLUMBER WILL SUPPLY AND INSTALL SEPARATE MANUAL SHUT-OFF VALVES
ON ALL SINKS AND OUTLETS REQUIRING WATER.
3. ALL SINKS AND FAUCETS WILL BE CONNECTED BY THE PLUMBER.
4. ALL PIPES WILL BE CONCEALED WITHIN THE WALLS, CEILING, AND/OR FLOOR,
UNLESS OTHERWISE NOTED.
5. ALL PIPES WILL BE FLUSHED CLEAR OF ALL DEBRIS BY THE PLUMBER.
6. THE PLUMBER WILL SUPPLY AND INSTALL ANY AND ALL MATERIALS INDICATED IN
THE PLUMBING DRAWINGS AND THE MANUFACTURER'S INSTALLATION
INSTRUCTION SHEETS.
7. THE PLUMBER WILL PROVIDE AND INSTALL ALL WATER SAFETY DEVICES (I.E.
CHECK VALVES, BACKFLOW PREVENTERS, ETC.) IN ACCORDANCE WITH LOCAL
CODE.
24 x 24 SQUARE CEILING DIFFUSERS
STEEL, ROUND NECK, LAY IN T-BAR
24 x 24 OR 24 x 12 EGG CRATE
RETURN, LAY IN T-BAR
CEILING MOUNT EXHAUST / VENTILATION
1. THESE CONTRACT DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT
INTENDED TO SHALL ALL POSSIBLE CONDITIONS. IT IS INTENDED THA A
COMPLETE HVAC SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT,
APPURTENANCES, AND CONTROLS. COMPLETELY COORDINATED WITH ALL
DISCIPLINES. A PARAMETERS GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY
CONFORMED WITH FURNISHED ALL ITEMS AND LABOR REQUIRED FOR A
COMPLETE HVAC SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES AND
STANDARDS.
2. SCOPE OF WORK FOR THE PROJECT SHALL CONSIST OF PROVIDING ALL LABOR,
MATERIAL, EQUIPMENT, HOISTING AND OTHER ITEMS AS NECESSARY FOR A
COMPLETE OPERATIONAL HVAC SYSTEM.
3. NO EQUIPMENT SHALL BE OPERATED DURING CONSTRUCTION UNTIL SUCH TIME
AS CONTRACTOR IS NOTIFIED THAT SYSTEMS ARE READY TO BE STARTED FOR
FINAL DELIVERY TO THE OWNER.
4. DUCTWORK SHALL BE GALVANIZED STEEL, FABRICATED AND ISNTALLED IN
ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS. SEALL ALL
LANGITUDINAL AND TRANSVERSE DUCT SEAMS. SEALANT SHALL BE DESIGNED
FOR OPERATING TEMPERATURES UP TO 500 DEGREES FARENHEIT.
5. BALANCING TAMPERS SHALL BE PROVIDED FOR BALANCING OF SUPPLY AND
OUTDOOR AIR.
6. ALL WORK SHALL BE WARRANTED FOR A PERIOD OF ONE YEAR BY THE
CONTRACTOR.
7. AIR HANDLING UNITS AND CONDENSING UNITS ARE EXISTING. CONTRACTOR
SHALL INSPECT EQUIPMENT FOR PROPER OPERATION AND MAKE ADJUSTMENTS
AS REQUIRED.
8. HVAC DIFFUSER LAYOUT SHOWN IN THESE PLANS IS FOR DESIGN PURPOSES
ONLY AND IS A SUGGESTED LAYOUT. DIFFUSERS MAY BE RELOCATED TO AVOID
CONFLICT WITH LIGHTING AND OTHER EQUIPMENT.
www.studio3design.net
Phone: (317) 595.1000
8604 Allisonville Road, Suite 330
Indianapolis, IN 46250
A
B
C
D
E
1 2 3 4 5 6 7
A
B
C
D
E
THESE DRAWINGS ARE THE PROPERTY
OF STUDIO 3 DESIGN, INC. ALL RIGHTS
RESERVED
PROJECT NUMBER:
DATE:
CERTIFICATION:
SHEET DESCRIPTION:
SHEET NUMBER:
REVISION SCHEDULE:
1 2 3 4 5 6 7
21046
08-19-21
HVAC & PLUMBING
FLOOR PLANS
M100Carmel OverlookSTEMTREE LEARNING CENTER5790 E. Main StreetCarmel, IN 46033NORTH
1/4" = 1'-0"M100
NEW HVAC PLAN4E
NORTH
1/4" = 1'-0"M100
NEW PLUMBING FLOOR PLAN1E
NOT TO SCALEM100
PLUMBING RISER7E
PLUMBING LEGEND
PLUMBING NOTES
HVAC SCHEDULE
HVAC NOTES
# Revision Description
Date
Issued
09/22/21