HomeMy WebLinkAboutE-401 - ELECTRICAL RISER DIAGRAMSIZE
CONDUCTOR
125 AMP APARTMENT UNIT FEEDER CONDUCTOR SIZES
CONDUCTOR
GROUNDING
#2/0 AL #4 AL
#3/0 AL
#4/0 AL
#250 KCM AL
#300 KCM AL
#350 KCM AL
NOTES
CONDUCTOR
MAXIMUM
LENGTH
153
184
231
264
305
345
#2 AL
#2 AL
#1 AL
#1/0 AL
#2/0 AL
1. FOR ANY FEEDERS THAT EXCEED 448 FEET, CONTRACTOR SHALL PROVIDE
ENGINEER WITH THE PROPOSED LENGTHS OF FEEDERS THAT EXCEED 448 FEET
TO PROPERLY CALCULATE THE CONDUCTOR SIZES.
1
1
1
1
1
1
RATING
CONDUCTOR
135
155
180
205
230
250
#500 KCM AL 448#3/0 AL 1310
#400 KCM AL 378#2/0 AL 1310
ALUMINUM ALUMINUM
SIZE
CONDUCTOR
125 AMP APARTMENT UNIT FEEDER CONDUCTOR SIZES
NOTES:
CONDUCTOR
GROUNDING
#1 CU #6 CU
#1/0 CU
#2/0 CU
#3/0 CU
#4/0 CU
#250 KCM CU
NOTES
CONDUCTOR
MAXIMUM
LENGTH
161
196
228
285
338
385
#4 CU
#4 CU
#3 CU
#2 CU
#1 CU
1. FOR ANY FEEDERS THAT EXCEED600 FEET, CONTRACTOR SHALL PROVIDE
ENGINEER WITH THE PROPOSED LENGTHS OF FEEDERS THAT EXCEED 600 FEET
TO PROPERLY CALCULATE THE CONDUCTOR SIZES.
1
1
1
1
1
1
RATING
CONDUCTOR
130
150
175
200
230
255
#500 KCM CU
#400 KCM CU 528#2/0 CU 1335
600#3/0 CU 1380
#300 KCM CU 434#1/0 CU 1285
COPPER COPPER
#350 KCM CU 480#2/0 CU 1310
900A
1200A
3P
METER CENTER MC-RES-A
120/208V, 3 PH, 4 WIRE
1200A MAIN FUSIBLE SWITCH,
(41) 120/208V, SINGLE PHASE, 3 WIRE WITH 5TH
JAW AND MAIN CIRCUIT BREAKER.
1200A-3PH
BUS
81
82
83
84
85
71
72
73
74
75
61
62
63
64
65
51
52
53
54
55
91
92
93
94
95
41
42
43
44
45
31
32
33
34
35
21
22
23
24
25
11
12
13
14
15
150A-2P
150A-2P
150A-2P
150A-2P
150A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
SE CABLES IN CHASE TO
LOAD CENTERS IN 2ND, 3RD
AND 4TH FLOOR APARTMENT
UNITS. (TYPICAL OF 41)
125A-2P 125A-2P
125A-2P
125A-2P
125A-2P
125A-2P125A-2P
125A-2P
125A-2P
125A-2P
125A-2P 125A-2P125A-2P
125A-2P 125A-2P
125A-2P 125A-2P
125A-2P 125A-2P
125A-2P 125A-2P
UTILITY TRANSFORMER #1
(HOUSE & COMMERCIAL
TENANT LOADS)
120/208V, 3 PH, 4W
WYE SECONDARY
PRIMARY CABLES
BY LOCAL UTILITY
COMPANY
400A
3P
MAIN
300A
3P
400A
3P
DISTRIBUTION PANEL DPH-A
120/208V, 3 PH, 4 WIRE
400A MAIN BUS
(HOUSE LOADS)
WINDSOR BUILDING RESIDENTIAL SERVICE
HOUSE SERVICE 1ST FLOOR COMMERCIAL
TENANT SERVICES
UTILITY
METERING
CABINET
UTILITY
METERING
CABINET
240V, 400A, 3P,
NEMA1 WITH
AUXILIARY
CONTACT SWITCH
INSTALL CABLES ABOVE
2ND FLOOR CEILING
UP TO PANELS
ON 3RD AND 4TH
FLOOR
DOWN TO PANELS
ON 2ND FLOOR
INSTALL CABLES IN
VENTILATED TROUGH ON 1ST
FLOOR
225A
3P
4 -4/0 CU, 1 #4 CU GRD,
2-1/2" C. OR
4-300 KCMIL AL, 1 #2 AL
GRD, 2-1/2"C.
2- 2"C. EACH WITH 4 -3/0
CU, 1 #3 CU GRD, 2" C.
OR
2- 2-1/2"C. EACH WITH 4-
250 KCMIL AL, 1- #1 AL
GRD
2- 2"C. EACH WITH 4 -3/0
CU, 1 #3 CU GRD, 2" C.
OR
2- 2-1/2"C. EACH WITH 4-
250 KCMIL AL, 1- #1 AL
GRD
SEE MOTORIZED EQUIPMENT
SCHEDULE ON SHEET E-502
FOR FEEDER SIZE
SEE MOTORIZED EQUIPMENT
SCHEDULE ON SHEET E-502
FOR FEEDER SIZE
100A
3P
200A
3P (SPACE)
400A
3P (SPACE)
3- 3"C. EACH WITH 4
-350 KCMIL CU OR
3- 3"C. EACH WITH 4-
500 KCMIL AL
SEE APARTMENT UNIT FEEDER
CONDUCTOR SIZE TABLES ON THIS SHEET
TO LOAD CENTERS IN
SECOND FLOOR APARTMENT
UNITS
TO LOAD CENTERS ON THIRD AND
4TH FLOOR APARTMENT UNITS
#3/0 CU #3/0 CUUTILITY
METERING
CABINET
2- 2"C. EACH WITH 4 -3/0
CU, 1 #3 CU GRD, 2" C.
OR
2- 2-1/2"C. EACH WITH 4-
250 KCMIL AL, 1- #1 AL
GRD
SEE MOTORIZED EQUIPMENT
SCHEDULE ON SHEET E-502
FOR FEEDER SIZE
2- 2"C. EACH WITH 4 -3/0 CU, 1 #3 CU GRD, 2" C. OR
2- 2-1/2"C. EACH WITH 4- 250 KCMIL AL, 1- #1 AL
GRD
2- 2"C. EACH WITH 4 -3/0 CU, 1 #3 CU GRD, 2" C. OR
2- 2-1/2"C. EACH WITH 4- 250 KCMIL AL, 1- #1 AL
GRD
2- 2"C. EACH WITH 4 -3/0 CU, 1 #3 CU GRD, 2" C. OR
2- 2-1/2"C. EACH WITH 4- 250 KCMIL AL, 1- #1 AL
GRD
400AS/
400AF
400AS/
400AF
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
-
-
-
-
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
PANEL
1HA1
208/120V
3PH
4W
PANEL
1HA2
208/120V
3PH
4W
75 HP
ELEV. #1
CONTROLLER
ELEVATOR
M
FUTURE
TENANT
208/120V
3PH
4W
M
FUTURE
TENANT
208/120V
3PH
4W
18166
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION
DOCUMENTS800 West Monon Green Blvd.E-401
ELECTRICAL RISER
DIAGRAM
08/31/202108/31/2021
KREG SMEAD BARRY SIMPSON