HomeMy WebLinkAboutE-601 - ELECTRICAL DETAILSH
S
B
B
B
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
ELECTRICAL ROUGH-IN AT DOOR FRAME
FOR CARD ACCESS AND SECURITY SYSTEM
NONE11
CEILING T-BAR
CEILING
STRUCTURE
LAY-IN FIXTURE SUPPORT DETAIL
NONE2
TYPICAL APARTMENT UNIT SWITCH
LIGHT AND FUTURE CEILING FAN DETAIL
NONE3
GROUNDING TRIANGLE DETAIL
NONE4
OCCUPANCY SENSOR
MOUNTING DETAIL
NONE5
TYPICAL OCCUPANCY
SENSOR WIRING DIAGRAM
NONE6
ELECTRICAL SERVICE
GROUNDING BUSBAR DETAIL
NONE7
EXIT LIGHT ON LAY-IN
CEILING MOUNTING DETAIL
NONE8
TYPICAL OCCUPANCY SENSOR POWER/
SWITCHING AND RELAY PACK MOUNTNG DETAIL
NONE9
TELECOMMUNICATIONS SERVICE ENTRANCE
POINT MAIN GROUNDING BUSBAR (TMGB) DETAIL
NONE10
TELECOMMUNICATIONS DISTRIBUTION
FRAME GROUNDING BUSBAR (TGB) DETAIL
NONE12
ELECTRICAL ELEVATIONS
NONE1
EXIT
23 3/4"1"5 3/8"1/2"1/2"FLOOR LINE
CEILING
FLOOR LINE
CEILING
IC
VC
11.
10.
9.
7.
6.
5.
4.
3.
2.
1.VERIFY ALL DIMENSIONS FROM ARCHITECTURAL PLANS.
DIMENSIONS SHOWN ON OUTLET BOXES SHALL BE FROM THE FINISHED FLOOR TO THE
TOP OF THE BOX - SEE ELEVATION DETAIL THIS SHEET.
CONDUIT TO LIGHTS IS SHOWN TO INDICATE SWITCHING AND DOES NOT INDICATE QUANTITY
OR EXACT LOCATION. OTHER CONDUIT SHOWN INDICATES CONNECTION, BUT DOES NOT
INDICATE QUANTITY OR LOCATION.
SUPPORT FLUORESCENT FIXTURES FROM STRUCTURE ABOVE. SEE DETAIL ON E-500 SERIES
SHEETS.
VERIFY LOCATION OF LIGHTS IN ROOMS CONTAINING EXPOSED DUCTWORK AND PIPING BY
OTHER TRADES AND RELOCATE, IF NECESSARY, AS REQUESTED BY THE ARCHITECT.
VERIFY LOCATION OF MOTOR STARTERS, DISCONNECTS, PANELBOARDS, ETC., IN ROOMS
CONTAINING EXPOSED DUCTWORK AND PIPING BY OTHER TRADES AND RELOCATE TO AN
ADJACENT, UNOBSTRUCTED AREA AS REQUESTED BY ARCHITECT.
VERIFY HEIGHT AND LOCATION OF OUTLETS BEHIND WATER COOLERS WITH OTHER TRADES
SO THAT OUTLETS ARE CONCEALED.
SEE MECHANICAL PLANS FOR MECHANICAL EQUIPMENT LOCATIONS.
VERIFY EXACT LOCATION OF ALL OUTLETS IN BUILT-INS AND CASEWORK FURNITURE WITH
EQUIPMENT SUPPLIERS ROUGH-IN DRAWINGS BEFORE ROUGHING IN.
MULTI-SWITCHED LIGHT FIXTURES SHALL HAVE THE OUTSIDE LAMPS CONTROLLED BY THE
SWITCH(ES) CLOSEST TO THE DOOR OPENING AND THE MIDDLE LAMP(S) CONTROLLED BY
THE OTHER SWITCH(ES).
TERMINATE ALL COMMUNICATIONS/TECHNOLOGY SYSTEM CONDUIT STUBS WITH A BUSHING.11.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.
12" X 2" X 1/4" COPPER
GROUND BUS BAR
BUS BAR STAND-OFF
(TYPICAL)
12" X 4" X 1/4" COPPER
GROUND BUS BAR
BUS BAR STAND-OFF
(TYPICAL)
12" X 4" X 1/4" COPPER
GROUND BUS BAR
BUS BAR STAND-OFF
(TYPICAL)
EXIT
PR
R WC
SYMBOLS:
FLOOR
CEILING
EQUIPMENT MOUNTING HEIGHTS SHALL BE INDICATED UNLESS OTHERWISE NOTED ON
THE DRAWINGS OR IN THE SPECIFICATIONS.
CONCEAL RECEPTACLE BEHIND WATER COOLER. VERIFY EXACT MOUNTING HEIGHTS.
WHERE DEVICES ARE LOCATED IN MASONRY WALLS LOCATE DEVICE WITHIN COARSING SO
THAT MOUNTING INDICATED HERE IN IS NOT EXCEEDED.
ALL RECEPTACLES ABOVE KITCHEN COUNTER AND NEAR BATH VANITIES SHALL BE INSTALLED
HORIZONTALLY AT +44" AFF TO TOP OF THE BOX.
NOTES:
1.
2.
3.
4.
M
W
S
JUNCTION
BOXES
HIGH VOLTAGE
WIRING
LOW VOLTAGE
WIRING
POWER
PACK
NOTES:
DO NOT INSTALL POWER PACKS
CLOSER THAN 6-12 INCHES
FROM SENSOR.
DO NOT INSTALL POWER PACKS
WITHOUT JUNCTION BOXES.
RJ-45
KEYNOTES:
LOCK/STRIKE POWER SUPPLY IN 6"X6"X4" JUNCTION BOX. MOUNT
ABOVE ACCESSIBLE CEILING ON SECURE SIDE OF DOOR.
8"X8"X4" JUNCTION BOX. MOUNT ABOVE ACCESSIBLE CEILING ON
SECURE SIDE OF DOOR.
PROXIMITY READER BACKBOX. 4" SQUARE BOX WITH SINGLE
GANG ADAPTER RING. FLUSH MOUNT IN WALL. COORDINATE
POSITION OF ROUGH-IN WITH CONSTRUCTION MANAGER BEFORE
ROUGH-IN.
1" CONDUIT.
3/4" CONDUIT.
ALL CONDUITS SHALL INCLUDE A NYLON PULL STRING. PULL
STRING SHALL BE TIED OFF AT EACH END. FOR CONDUITS
ENTERING DOOR FRAME, PULL STRING SHALL CONTINUE THE
LENGTH OF THE FRAME BOTH ACROSS AND DOWN (2 STRINGS)
AND SHALL NOT BE TIED OFF.
USED FOR DOORS OVER 250' FROM
TELECOM ROOM.
USED FOR DOORS WITHIN 250' FROM
TELECOM ROOM.96"96"48"48"72"48"36"20"20"20"NOTE220"20"96"96"72"96"48"20"48"48"84"F
S
F S
FN
D
TOP VIEW
SUPPORT BRACKET END VIEW
GENERAL NOTES - APPLY TO
ALL ELECTRICAL SHEETS
10'-0"10'-0"10'-0"
SINGLE POLE
LIGHT SWITCH
TWO-GANG BOX WITH
NYLON COVER PLATE
SPACE FOR
FUTURE
CEILING FAN
SWITCH
REAR
HOUSING
FRONT
COVER
CEILING
MANUFACTURER
PRE-TERMINATED
CABLES OR CAT 5e
SPRING
CLIPS (2)
CEILING HOLE
LOCAL
THREE-WAY
SWITCHES
HOT BLK
LOAD
WHT CONTROL
COMMON
+24VDC
OCCUPANCY
SENSOR
24VDC
LOAD
LOCAL SWITCH
PROVIDE ADDITIONAL SENSOR POWER/SWITCHING PACKS
AS REQUIRED FOR ADDITIONAL ROOM LIGHT SWITCHING.
PROVIDE OTHER RELAY PACKS AS INDICATED.
NEUTRAL
(UNSWITCHED)
FLEXIBLE CONDUITCUSTOM SHEET METAL SUPPORT
BRACKET. SEE DETAILS
LAY-IN CEILING
CEILING GRID
4"x1-1/2" BOX
CEILING SUPPORT WIRE
ADDITIONAL ROD OR
WIRE SUPPORT
STEEL JOIST OR BEAMS
18 GAUGE GALVANIZED
JUNCTION BOX
SHEET METAL
LC
LC
7/8"∅
OCCUPANCY
SENSOR POWER
AND SWITCHING
PACK
CEILING SUPPORT WIRE
1. LIGHTING FIXTURES SHALL BE SUPPORTED INDEPENDENTLY OF CEILING SYSTEM. UPON
WRITTEN REQUEST TO THE ENGINEER, OTHER MEANS OF SUPPORT WILL BE CONSIDERED FOR
APPROVAL.
NOTE:
FLEXIBLE
CONDUIT
DOUBLE LOOP SAFETY
CHAIN MIN. 2 PER FIXTURE
ANGLE IRON OR SLOTTED CHANNEL
AS REQUIRED SECURELY SUPPORTED
FROM STRUCTURE ABOVE CADDY CLAMPS
OR EQUAL
OUTLET BOX &
SUPPORT ROD
LAY-IN TYPE FIXTURE
3/0 COPPER CABLE
EXOTHERMICALLY
WELD CABLE TO
GROUND RODS
3/4" DIA. X 10' LONG
COPPER CLAD STEEL
GROUND ROD
3/0 COPPER CABLE
120V POWER CIRCUIT
1" CONDUIT TO
TELECOMMUNICATIONS
ROOM
1" CONDUIT TO
TELECOMMUNICATIONS
ROOM
1
2
3
4
5
6
42
4
442
4
4
4
1
18166
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION
DOCUMENTS800 West Monon Green Blvd.E-601
ELECTRICAL DETAILS
08/31/202108/31/2021
KREG SMEAD BARRY SIMPSON