HomeMy WebLinkAboutE-602 - ELECTRICAL DETAILSSCALE: SCALE: SCALE: SCALE: SCALE: SCALE: SCALE: SCALE: SCALE: SCALE: SCALE: SCALE: SCALE:0 4'2'1' SCALE:0 4'2'1' DISTRIBUTION PANEL, PANELBOARD AND DISCONNECT SWITCH LABELING DETAIL NONE1 DISTRIBUTION PANEL, PANELBOARD AND DISCONNECT SWITCH LABELING DETAIL NONE2 TYPICAL DUCTBANK DETAIL NONE3 1-1/2" AND SMALLER CONDUIT SUPPORT DETAIL NONE4 2" AND LARGER CONDUIT SUPPORT DETAIL NONE5 COLUMN GROUNDING DETAIL NONE6 CONDUIT ROOF PENETRATION DETAIL NONE7 KEY TO ELECTRICAL CIRCUIT WIRING NONE8 CABLE SLEEVE INSTALLATION DETAIL NONE9 GROUND MOUNTED LIGHT DETAIL NONE10 OVERHEAD FEED TO INTERIOR WALL DETAIL NONE11 CONDUIT STUB UP DETAIL NONE12 FLOOR SLEEVES FOR SE CABLES AT PLAYFAIR BUILDING 1/2" = 1'-0"14 FLOOR SLEEVES FOR SE CABLES AT HOLAND BUILDING 1/2" = 1'-0"15 FINISHED GRADE SUPPORT STRUCTURE ROOFING (BY OTHERS) BUILT-UP ROOF DECK. (BY OTHERS) BUILDING STRUCTURE6"6"12" DIA.30"! FINISHED FLOOR THREADED PLUG THREADED COUPLING CONDUIT WARNING Arc Flash Hazard Appropriate PPE Required Equipment Type GroundingWork DistanceAvailable 3-Ph Bolted CurrentFlash Protection BoundaryIncident Energy at 11 inchesRisk CategoryEquipment Name: 480V Switchgear Grounded11 inches (300 mm)25 kA27 inches4.39 cal/cm2 2 Switchboard WARNING LABEL FOR ELECTRICAL EQUIPMENT SUCH AS MAIN SWITCHGEAR AND BRANCH PANELBOARDS. LIGHTING FIXTURE CONDUIT SEE PLAN FOR SIZE FINISH GRADE STANCHION MOUNT CONCRETE BASE CONC. SLAB PER PLANS FINISHED FLOOR CL STEEL COLUMN PER PLANS CL FOOTINGS PER PLANS PRECAST SLEEVE SE CABLE (4 PER SLEEVE) 4" RGS X 16" LONG CONDUIT SEAL CONDUIT WITH FIRESTOP MATERIAL 2ND FLOOR SLAB PRECAST SLEEVE SE CABLE (4 PER SLEEVE) 4" RGS X 16" LONG CONDUIT SEAL CONDUIT WITH FIRESTOP MATERIAL 2ND FLOOR SLAB LAMACOID NAMEPLATE NOTE: LABELS SHALL BE: NORMAL POWER: BLACK WITH WHITE LETTERS EMERGENCY POWER: RED WITH WHITE LETTERS 1/2" HIGH LETTERS 1/4" HIGH LETTERS 1. SEE ONE LINE DIAGRAM FOR SIZE AND NUMBER OF CONDUITS, AND DUCT BANK ARRANGEMENT. 2. PROVIDE 1 REINFORCING BAR PER CONDUIT WHEN EVER A DUCTBANK POUR IS STOPPED MID-RUN. BARS SHALL BE ASTM A-615, GRADE 60. 3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS. NOTES: USE SIDE FORMS AS REQUIRED BASE SPACER 3000 PSI CONCRETE INTERMEDIATE SPACER WARNING TAPE 7/8" X 4" WOOD BASE CONDUIT SUPPORT AND SPACERS 4'-0" MAXIMUM 6" MIN. BETWEEN ADJACENT COUPLINGS3" MIN3" MIN.24" MIN. U.O.N.3" MIN 6"1" 3" 3" MIN. PLAN SECTION A-A SECTION B-B CONDUIT BEAM CLAMP BEAM CLAMP CONDUIT CLAMPS CONDUIT CLAMPS CONDUIT CLAMPS SLOTTED CHANNEL TO SUPPORT 400% OF CONDUIT WEIGHT DOUBLE NUT TOP AND BOTTOM SLOTTED CHANNEL TO SUPPORT 400% OF CONDUIT WEIGHT. BEAM CLAMP THREADED ROD CONDUIT CLAMPS 3/4" x 10'-0" COPPER CLAD STEEL GROUND ROD BONDING PLATE OR EXOTHERMIC WELD TO STEEL COLUMN EXOTHERMIC CONNECTION TO GROUND ROD CLASS II COPER GROUNDING CONDUCTOR 1" PVC CONDUIT SLEEVE STEPPED PVC BOOT CONDUIT STAINLESS STEEL CLAMPS SPUN ALUMINUM FLASHING BASE CONDUIT PANEL DESIGNATION GROUND CONDUCTOR(S) PHASE CONDUCTOR(S) NEUTRAL CONDUCTOR(S) ALL CONDUCTORS NOT LESS THAN #12 ALL CONDUIT NOT LESS THAN 3/4"CIRCUIT NO. DESIGNATION AL1 1,3,5 }FIRE/SMOKE RATED OR UNRATED PARTITION OF VARIOUS CONSTRUCTIONS-REFER TO ARCHITECTURAL PLANS OR FIELD VERIFY TYPE CEILING STRUCTURE SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH INSULATED THROAT CONDUIT TERMINATORS EACH END-PROVIDE A THREADED CAP ON EACH END IF NOT USED FOR WIRING. LINE-UP WITH "BRIDLE RINGS" WHERE APPLICABLE. AFTER CABLE INSTALLATION, PROVIDE FIRESTOPPING IN SLEEVE. ACCESSIBLE CEILING EACH SIDE OF SLEEVE J BRANCH CIRCUIT CONDUIT DOWN TO OUTLET WALL OUTLET LAY-IN TYPE CEILING BRANCH CIRCUIT CONDUIT JUNCTION BOX PANEL LXW 120/208V/3PH/4W FEED: 150 AMPS FED FROM: MDP-3 A A B B 18166 Project: Developer: Sheet Number: Engineer: By: Sheet Title: CDG Number: Last Revision Date: Set Issue Date Drawn By Checked By Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION DOCUMENTS800 West Monon Green Blvd.E-602 ELECTRICAL DETAILS 08/31/202108/31/2021 KREG SMEAD BARRY SIMPSON