DISTRIBUTION PANEL, PANELBOARD AND
DISCONNECT SWITCH LABELING DETAIL
NONE1
DISTRIBUTION PANEL, PANELBOARD AND
DISCONNECT SWITCH LABELING DETAIL
NONE2
TYPICAL DUCTBANK DETAIL
NONE3
1-1/2" AND SMALLER
CONDUIT SUPPORT DETAIL
NONE4
2" AND LARGER
CONDUIT SUPPORT DETAIL
NONE5
COLUMN GROUNDING DETAIL
NONE6
CONDUIT ROOF
PENETRATION DETAIL
NONE7
KEY TO ELECTRICAL CIRCUIT WIRING
NONE8
CABLE SLEEVE
INSTALLATION DETAIL
NONE9
GROUND MOUNTED LIGHT DETAIL
NONE10
OVERHEAD FEED TO
INTERIOR WALL DETAIL
NONE11
CONDUIT STUB UP DETAIL
NONE12
FLOOR SLEEVES FOR
SE CABLES AT PLAYFAIR BUILDING
1/2" = 1'-0"14
FLOOR SLEEVES FOR
SE CABLES AT HOLAND BUILDING
1/2" = 1'-0"15
FINISHED GRADE
SUPPORT
STRUCTURE
ROOFING
(BY OTHERS)
BUILT-UP ROOF DECK.
(BY OTHERS)
BUILDING STRUCTURE6"6"12" DIA.30"!
FINISHED
FLOOR
THREADED
PLUG THREADED
COUPLING
CONDUIT
WARNING
Arc Flash Hazard
Appropriate PPE Required
Equipment
Type
GroundingWork
DistanceAvailable 3-Ph Bolted
CurrentFlash Protection
BoundaryIncident Energy at 11
inchesRisk
CategoryEquipment
Name:
480V
Switchgear
Grounded11 inches (300
mm)25
kA27
inches4.39
cal/cm2
2
Switchboard
WARNING LABEL FOR ELECTRICAL
EQUIPMENT SUCH AS MAIN
SWITCHGEAR AND BRANCH
PANELBOARDS.
LIGHTING FIXTURE
CONDUIT
SEE PLAN
FOR SIZE
FINISH
GRADE
STANCHION
MOUNT
CONCRETE
BASE
CONC. SLAB PER PLANS
FINISHED FLOOR
CL
STEEL COLUMN PER PLANS
CL
FOOTINGS PER PLANS
PRECAST SLEEVE
SE CABLE
(4 PER SLEEVE)
4" RGS X
16" LONG
CONDUIT SEAL CONDUIT
WITH FIRESTOP
MATERIAL
2ND FLOOR SLAB
PRECAST SLEEVE
SE CABLE
(4 PER SLEEVE)
4" RGS X
16" LONG
CONDUIT
SEAL CONDUIT
WITH FIRESTOP
MATERIAL
2ND FLOOR SLAB
LAMACOID
NAMEPLATE
NOTE: LABELS SHALL BE:
NORMAL POWER: BLACK WITH WHITE LETTERS
EMERGENCY POWER: RED WITH WHITE LETTERS
1/2" HIGH
LETTERS
1/4" HIGH
LETTERS
1. SEE ONE LINE DIAGRAM FOR SIZE AND NUMBER OF CONDUITS, AND DUCT BANK ARRANGEMENT.
2. PROVIDE 1 REINFORCING BAR PER CONDUIT WHEN EVER A DUCTBANK POUR IS STOPPED MID-RUN.
BARS SHALL BE ASTM A-615, GRADE 60.
3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS.
NOTES:
USE SIDE FORMS
AS REQUIRED
BASE SPACER
3000 PSI
CONCRETE
INTERMEDIATE
SPACER
WARNING TAPE
7/8" X 4"
WOOD BASE
CONDUIT SUPPORT AND
SPACERS 4'-0" MAXIMUM
6" MIN. BETWEEN
ADJACENT COUPLINGS3" MIN3" MIN.24" MIN. U.O.N.3" MIN 6"1"
3"
3" MIN.
PLAN
SECTION A-A SECTION B-B
CONDUIT
BEAM CLAMP
BEAM CLAMP
CONDUIT CLAMPS
CONDUIT CLAMPS
CONDUIT CLAMPS
SLOTTED CHANNEL
TO SUPPORT 400%
OF CONDUIT WEIGHT
DOUBLE NUT TOP
AND BOTTOM
SLOTTED CHANNEL
TO SUPPORT 400%
OF CONDUIT WEIGHT.
BEAM CLAMP
THREADED ROD
CONDUIT CLAMPS
3/4" x 10'-0" COPPER
CLAD STEEL GROUND ROD
BONDING PLATE OR
EXOTHERMIC WELD
TO STEEL COLUMN
EXOTHERMIC CONNECTION
TO GROUND ROD
CLASS II COPER
GROUNDING
CONDUCTOR
1" PVC CONDUIT
SLEEVE
STEPPED PVC BOOT
CONDUIT
STAINLESS STEEL CLAMPS
SPUN ALUMINUM FLASHING
BASE
CONDUIT
PANEL DESIGNATION
GROUND CONDUCTOR(S)
PHASE CONDUCTOR(S)
NEUTRAL CONDUCTOR(S)
ALL CONDUCTORS NOT LESS
THAN #12
ALL CONDUIT NOT LESS THAN 3/4"CIRCUIT NO. DESIGNATION
AL1
1,3,5
}FIRE/SMOKE RATED OR UNRATED PARTITION
OF VARIOUS CONSTRUCTIONS-REFER TO
ARCHITECTURAL PLANS OR FIELD VERIFY TYPE
CEILING STRUCTURE
SIZE CONDUIT SLEEVE (SIZE AS INDICATED)
WITH INSULATED THROAT CONDUIT TERMINATORS
EACH END-PROVIDE A THREADED CAP ON
EACH END IF NOT USED FOR WIRING. LINE-UP
WITH "BRIDLE RINGS" WHERE APPLICABLE.
AFTER CABLE INSTALLATION, PROVIDE
FIRESTOPPING IN SLEEVE.
ACCESSIBLE CEILING EACH SIDE OF SLEEVE
J
BRANCH CIRCUIT CONDUIT
DOWN TO OUTLET
WALL OUTLET
LAY-IN TYPE CEILING
BRANCH
CIRCUIT CONDUIT
JUNCTION BOX
PANEL LXW
120/208V/3PH/4W
FEED: 150 AMPS
FED FROM: MDP-3
A
A
B
B
18166
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION
DOCUMENTS800 West Monon Green Blvd.E-602
ELECTRICAL DETAILS
08/31/202108/31/2021
KREG SMEAD BARRY SIMPSON