Loading...
HomeMy WebLinkAboutH-100 - HVAC FOUNDATION PLANSnow Melt Design:140.0 Btu/(hr·ft²) Backloss:28.0 Btu/(hr·ft²) Total:168.0 Btu/(hr·ft²) Circuit A-9 204 ft @ 9 in Flow: 2.09 USGPM ΔT: 25 °F Circuit A-1 196 ft @ 9 in Flow: 1.98 USGPM ΔT: 25 °F Circuit A-15 193 ft @ 9 in Flow: 2.00 USGPM ΔT: 25 °F Circuit A-3 196 ft @ 9 in Flow: 2.02 USGPM ΔT: 25 °F Circuit A-4 203 ft @ 9 in Flow: 2.02 USGPM ΔT: 25 °FCircuit A-5 193 ft @ 9 in Flow: 1.90 USGPM ΔT: 25 °FCircuit A-6 194 ft @ 9 in Flow: 1.97 USGPM ΔT: 25 °F Circuit A-7 206 ft @ 9 in Flow: 2.08 USGPM ΔT: 25 °F Circuit A-8 220 ft @ 9 in Flow: 2.15 USGPM ΔT: 25 °F Circuit A-14 204 ft @ 9 in Flow: 1.94 USGPM ΔT: 25 °F Circuit A-10 204 ft @ 9 in Flow: 1.99 USGPM ΔT: 25 °F Circuit A-11 209 ft @ 9 in Flow: 1.98 USGPM ΔT: 25 °F Circuit A-12 206 ft @ 9 in Flow: 1.98 USGPM ΔT: 25 °F Circuit A-13 201 ft @ 9 in Flow: 1.85 USGPM ΔT: 25 °F Manifold 1 (103.5 °F) Manifold (103.5 °F) 0'-9" 0'-6"T/ FOR ENLARGED PLANS REFER TO 1 H-304 GEF-1 GEF-2 GEF-1 EUH-6 EUH-8 EUH-9 EUH-4 EUH-5 GEF-3 LV1 60/20 J8800 60/2060/2066/424"ø COMBUSTION AIR AND EXHAUST AIR VENTS ROUTE UP TO FLOOR ABOVE. TERMINATE WITH MANUFACTURER APPROVED CONCENTRIC VENT KIT. 6"ø EXHAUST AIR DUCT ROUTES UP TO FLOOR ABOVE. EUH-10 EUH-10 EUH-10 EUH-10 DS-21 DS-1 1 18166 Project: Developer: Sheet Number: Engineer: By: Sheet Title: CDG Number: Last Revision Date: Set Issue Date Drawn By Checked By Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION DOCUMENTS800 West Monon Green Blvd.H-100 HVAC FOUNDATION PLAN 08/31/202108/31/2021 THOMAS KENNEDY JOE BOLYARD 1/8" = 1'-0" HVAC FOUNDATION PLAN1 11700201 No. STATE OFJOSEPHR.BO L Y ARDPROFE S S IONA L E N G INEERDATE SIGNED 08/31/21REGISTER E D I ND I A N AN 0 16'8'4'