HomeMy WebLinkAboutH-601 - HVAC DETAILSROOF
INSTALL CURBS PER NRCA
AND MFGRS RECOMMENDATIONS
EQUIPMENT
SUPPORT CURB OR
RAIL (TYPICAL)
WOOD NAILER
FIELD APPLIED
CANT
EQUIPMENT BASE
REFER TO STRUCTURAL DWGS
FOR SUPPORT ATTACHMENT TO
STRUCTURE BELOW
ROOF, SEE ARCH
PLANS FOR DETAILS
CONDENSING UNIT
CAULK OR GASKET
NOTES:
1. PROVIDE 2 - 1-1/4" WIDE METAL STRAPS OVER TOP OF UNIT, ONE ON EACH SIDE. STRAPS SHALL BE ANCHORED TO EQUIPMENT RAILS AT THE BASE. STRAPS SHALL BE PRIMED AND PAINTED
WHITE, 2 COATS EACH MINIMUM, ON BOTH SIDES PRIOR TO INSTALL.
2. PROVIDE 2 - #14 LAG BOLTS, SPACED 5/8" APART, AT THE END OF EACH METAL STRAP. BOLTS SHALL GO THROUGH METAL STRAPPING AND INTO WOOD NAILER OF EQUIPMENT RAILS TO
ANCHOR UNIT TO EQUIPMENT RAILS.
3. STRAPS SHALL BE PLACED A MINIMUM OF 3" IN FROM TOP EDGE OF UNIT.
4. STRAPPING SHALL BE VERIFIED BY EQUIPMENT MANUFACTURER TO ENSURE ADEQUATE RESTRAINT OF SUPPLIED EQUIPMENT AT 115 MPH WIND LOAD. ANY DEVIATIONS FROM ABOVE MUST
BE SUBMITTED TO ENGINEER FOR REVIEW.
CONDENSING UNIT
DOOR MIN. 30"
WATER HEATER PAN
WATER HEATER
FAN COIL UNIT
PLENUM
CLEARANC
E
RACK
REFRIGERANT
LINE SETS ON SIDE
WALL OF MECH
ROOM
RETURN
GRILLE,
SEE PLANS
CONDENSATE DRAIN;
ROUTE
TO HUB DRAIN
MAIN SHUT-OFF
POSSIBLE
FUTURE
TENANT
SUBMETE
R
WATER
HEATE
R
PAN
SLEEVE
FLEX
CONN.
DUCTFIRE DAMPER
W/ACCESS
PANEL
FAN
COIL
UNIT
WATER HEATER
HW CW VALVE (TYP.)
SIDE VIEW
TOP VIEW
NOTE: TYPICAL CONDITION SHOWN, REFER
TO
MECHANICAL AND PLUMBING FLOOR PLANS
FOR ADDITIONAL REQUIREMENTS.
CEILING
RADIATIO
N
DAMPER
PLENUM BOX
OR
ELBOW, R/D=1.5
MIN.
15.2"9'-0" REFER TO PLANS13" MINNOM. 41"12"MIN.NOM.36"FOAM SEAL BETWEEN DOOR AND
FAN COIL SUPPORT SHELF4"NOTES:
1. ROUTE CONDENSATE PIPING (SIZE PER
MANUFACTURER) TO HUB DRAIN.
2. REFER TO STRUCTURAL UNIT PLAN
DRAWINGS FOR ACTUAL CONDITION AT
EACH CLOSET. HARD DUCT MAIN ALWAYS
ROUTES PARALLEL TO JOISTS.
3. COORDINATE HARD DUCT ELEVATION AT
JOIST SPACE WITH FIRE PROTECTION AND
PLUMBING PIPING PRIOR TO INSTALLATION.
4. FIRESTOP ALL PENETRATIONS AT
CEILING, FLOOR AND THROUGH FCU
SUPPORT.
NOM. 30"
FIRE RATED RATED PLYWOOD FLOOR
ON FAN COIL SUPPORT SHELF.
SUPPORT SHELF BY CONTRACTOR.
FASTEN FIRE DAMPER FRAME TO
SLEEVE AS REQUIRED BY U.L. LABEL
DUCT CONNECTOR-FULL WIDTH OF
SLEEVE REQUIRED AT TOP ONLY
'S'-SLIP TYPICAL CONNECTION
TO DUCTWORK
160°F FUSIBLE LINK
CONNECT DUCT TO DAMPER
COLLAR BOTH SIDES OF PARTITION
AS REQUIRED BY U.L. LABEL
ANGLES 1 1/2"x1 1/2"x1/8" MINIMUM; FASTENED
TO SLEEVE AS REQUIRED BY U.L. LABEL;
ANGLES TO LAP MASONRY OPENING MINIMUM 1"
FIRE RATED FLOOR
OR PARTITION
TOP BLADE RIVETED TO FRAME
WALL SLEEVE; MINIMUM 16 GA. FOR
DAMPERS NOT EXCEEDING
36"Wx24"H AND 14 GAUGE FOR
LARGER SIZES
NOTE: PROVIDE HINGED OR DOUBLE
CATCH ACCESS DOOR SIZED AND
LOCATED TO PERMIT REPLACEMENT
OF FUSIBLE LINK LABELED "FIRE
DAMPER ACCESS"
DUCT CONNECTOR-FULL WIDTH OF
SLEEVE REQUIRED AT TOP ONLY
ROOF MEMBRANE
PIPE
INSULATION
BASE
GALVANIZED
CHANNEL
SECURE PIPING TO
SUPPORT WITH
STRAPFLOOR TO FLOOR STRUCTURE OR BULKHEADALL CONCEALED 4"
DRYER DUCT SHALL
BE NON-
CORRUGATED
SMOOTH METAL
WITHOUT SCREWS.
EXTERIOR WALL CAP
WITHOUT SCREEN.
24"x10" TRANSFER
GRILLES ON EACH SIDE,
CENTERED ABOVE
DOOR. (160 SQ. IN.)
DRYER BOX IN SIDE WALL
MOUNTED AT 4" A.F.F. 0' - 4"1' - 9"MOTOR
DISCONNECT SWITCH
BY UNIT MFGR.
PIGTAIL CORD
EXTERNAL ALUM. WIRE
POST BY UNIT MFGR.
REFER TO ARCHITECTURAL
PLANS FOR ROOF
CONSTRUCTION
AUTO BACKDRAFT DAMPER
SEE PLANS FOR DUCT SIZE
ALUM. HOUSING
FAN WHEEL
BIRDSCREEN
FLASH AND
COUNTERFLAS
H
16" HIGH
PRE-FAB CURB
PROVIDE HOLE
THRU ROOF
ROUTE WIRE OUTSIDE DAMPER,
BY OTHERS
ROOF CURB CAP
WALL SLEEVE
FAN HOUSING
REAR GUARD
SCREEN
MOTOR
FAN
GRAVITY
BACKDRAF
T DAMPER
WALL -SEE
ARCHITECTURAL PLANS
LOUVER
STACKED
WASHER
AND DRYER
4" DIA DRYER DUCT
ROUTES UP IN WALL
DRYER BOX
LINT TRAP, PAINT METAL
TO MATCH WALL FINISH
MOUNT 7' A.F.F.
DRYER DUCT ROUTES
OUT OF BUILDING
18166
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION
DOCUMENTS800 West Monon Green Blvd.H-601
HVAC DETAILS
08/31/202108/31/2021
THOMAS KENNEDY JOE BOLYARD
NOT TO SCALE
FCU Above Water Heater DetailB
NOT TO SCALE
Fire Damper Installation DetailC
NOT TO SCALE
Pipe Roof Support DetailD
NOT TO SCALE
Typical Dryer Vent Connection DetailE
NOT TO SCALE
Typical Exhaust Fan (Flat) DetailF
NOT TO SCALE
Wall Mounted Exhaust Fan Detail - Direct DriveG
NOT TO SCALE
Lint Trap Above Dryer Box DetailH
NOT TO SCALE
Condensing Unit Support DetailA
11700201
No.
STATE OFJOSEPHR.BO
L
Y
ARDPROFE
S
S
IONA L E N G INEERDATE SIGNED 08/31/21REGISTER
E
D
I
ND I A N A