HomeMy WebLinkAboutE105.0NO DUCTWORK OR PIPING IN THIS AREA DUCTWORK ALLOWED IN THIS AREA. NO PIPING ALLOWED FLOOR OR ROOF DECK ABOVE FIRE DAMPER 30" MIN. PIPING DUCTWORK DEDICATED ELECTRICAL SPACE. NO EQUIPMENT, DUCTS, OR PIPING IN THIS AREA DUCTWORK CONDUIT PIPING (NOT OVER TRANSFORMER) 6" ABOVE PANEL (78" MIN.) 6"WALL CEILING 30" MIN. DUCTWORK TABLE 110.26(A)(1) REF. TO NEC ELECTRICAL PANEL MOUNTED TO UNISTRUT ON WALL CONDUIT TRANSFORMER PANEL TRANSFORMER FRONT VIEW DEDICATED ELECTRICAL SPACE. NO EQUIPMENT, DUCTS, OR PIPING IN THIS AREA SIDE VIEW6'-0" TO 6'-6"6'-6" MIN.NEC EQUIPMENT CLEARANCES N.T.S.2 ORIGINAL SHEET - ARCH E1 DATE:PRINT TIME STAMP:REVIEWED: MTFDRAWN BY: ABCOPYRIGHT © 2021 WALGREEN CO.WALGREENS11555 N. Meridian St.Carmel, IN 46032222702245AREA OFFICE - TWO PENN MARK - SUITE 140REVISIONSNO. DATE BY DESCRIPTIONLOC# 1397-1DESIGN PROJECT NO: Store Planning and Design Development106 Wilmot RoadDeerfield, IL 60015-5105224 S. Michigan Ave.STE 1400Chicago, IL 60604Tel: 312.554.1400 • www.stantec.comThe Contractor shall verify and be responsible for all dimensions. DO NOT scale thedrawing - any errors or omissions shall be reported to Stantec without delay.The Copyrights to all designs and drawings are the property of Stantec. Reproduction oruse for any purpose other than that authorized by Stantec is forbidden.Copyright ReservedPermit/Seal KEY PLAN:100 % CONSTRUCTION DOCUMENT REVIEW2021.06.18ISSUE FOR BIDDING AND PERMIT2021.07.02Stantec Architecture and Engineering, LLC.E-200Electrical Riser Diagram & SchedulesM UTILITY TRANSFORMER ELECTRIC UTILITY COMPANY PRIMARY SERVICE SERVICE LATERAL. SIX (6) PARALLEL SETS OF 4#500MCM IN 3.5"C. (EACH) COPPER FEEDERS ID NOMINAL CIRCUIT RATING SETS CONDUCTORS GROUND CONDUIT W/ N (4W) CONDUIT W/O N (3W) C01 20 1 #12 #12 3/4" 3/4" C02 30 1 #10 #10 3/4" 3/4" C03 40 1 #8 #10 3/4" 3/4" C04 50 1 #6 #10 1" 3/4" C05 60 1 #4 #10 1 1/4" 1" C06 70 1 #4 #8 1 1/4" 1 1/4" C07 80 1 #3 #8 1 1/4" 1 1/4" C08 90 1 #2 #8 1 1/2" 1 1/4" C09 100 1 #1 #8 1 1/2" 1 1/2" C10 125 1 #1 #6 1 1/2" 1 1/2" C11 150 1 #1/0 #6 2" 1 1/2" C12 175 1 #2/0 #6 2" 2" C13 200 1 #3/0 #6 2" 2" C14 225 1 #4/0 #4 2 1/2" 2" C15 250 1 250 kcmil #4 3" 2 1/2" C16 300 1 350 kcmil #4 3" 2 1/2" C17 350 1 500 kcmil #3 3 1/2" 3" C18 400 1 500 kcmil #3 3 1/2" 3" C19 450 2 #4/0 #2 2 1/2" 2" C20 500 2 250 kcmil #2 3" 2 1/2" C21 600 2 350 kcmil #1 3" 2 1/2" C22 800 2 500 kcmil #1/0 3 1/2" 3" C23 900 3 350 kcmil #2/0 3" 3" C24 1000 3 500 kcmil #2/0 3 1/2" 3" C25 1200 4 350 kcmil #3/0 3" 3" C26 1600 5 500 kcmil #4/0 3 1/2" 3" C27 2000 6 500 kcmil 250 kcmil 3 1/2" 3" C28 2500 7 500 kcmil 350 kcmil 3 1/2" 3 1/2" C29 3000 8 500 kcmil 500 kcmil 4" 3 1/2" C30 4000 11 500 kcmil 500 kcmil 4" 3 1/2" SERVICE LATERAL. SIX (6) PARALLEL SETS OF 4#500MCM IN 3.5"C. (EACH) N G 2000A BUSBARSPANELL1 TR-75 PANELP1 PANELP1 1 ELECTRICAL PARTIAL ONE LINE DIAGRAM C13 1 3 1 200A/3P 3-200AF C10 1 3 1 C13 13 1 NOTES: 1. REPLACE EXISTING 42-CIRCUIT BREKAER PANEL 'P1' WITH SINGLE-WIDTH 60-CIRCUIT BREAKER PANEL (AS MANUFACTURED BY EATON OR SQUARE D), INCLUDING LINE SIDE FEEDER. RETAIN EXISTING BRANCH CIRCUITS FOR RECONNECTION TO NEW PANEL. COORDINATE PANEL 'P1' SHUTDOWN WITH LANDLORD. REFER TO PANEL SCHEDULE FOR ADDITIONAL INFORMATION. 2. MAXIMUM DEMAND LOAD FOR THIS PROJECT WILL NOT EXCEED UPSTREAM TRANSFORMER 'TR-75' CAPACITY OF FEEDER RATING OR PANEL 'P1' MAIN CIRCUIT BREAKER RATING. 2000A CURRENT TRANSFORMER AND METERING COMPARTMENT 2000A MAIN FUSE 480Y/277V 3-PHASE 4-WIRE SWITCHBOARD MAIN COMPARTMENT 2000A 480Y/277V 3-PHASE 4-WIRE SWITCHBOARD DISTRIBUTION MAIN COMPARTMENT 75KVA 480V 3-WIRE+GROUND PRIMARY 208/120V 3-PHASE 4-WIRE SECONDARY TRANSFORMER C27 1 3 1 EXISTING GROUNDING ELECTRODE SYSTEM (NOT SHOWN): EFFECTIVELY GROUNDED STEEL STRUCTURE, METALLIC WATER PIPE (WITHIN 5' OF WATER SERVICE ENTRANCE, AND GROUND RODS. 2000A/3P 3-2000AF BPS GFP 09/29/21