HomeMy WebLinkAboutE202 - Level 2 Electrical PlansI.T. ROOM
I.T. ROOM
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
UP
DN
EMERGENCY CALL
BUTTON
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL RAMPDOWNRAMPUPH
H
1 2 32.61.3
A
C
D
E
F
G
H
I
J
L
B
K
2.5
J
J
1 2 32.61.3
A
C
D
E
F
G
H
I
J
L
B
K
2.5
OSOS
(2) 2"C
FOR DATA
LV-OP1#7
LV-OP1#7
LV-OP1#5
LV-OP1#5
LV-OP1#15
LV-OP1#17
CU-5
CU-6
01
01
02
HV-OP1#7
03
LV-EM1#2
DS-6
DS-2
DS-5
EF-2
EF-3
HV-OP1#18,20,22
HV-OP1#21,23,25
PG1PG1PG1
PG1
PG1PG1
PG1
PG1 PG1 PG1 PG1
PG1PG1PG1PG1
PG1 PG1 PG1 PG1
PG1PG1PG1PG1
PG1 PG1 PG1 PG1
PG1PG1PG1PG1
PG1 PG1 PG1 PG1
PG1PG1PG1PG1PG1
PG1 PG1
PG1
PG1 PG1
D1
D1 D1
D1
L1 L1
L3 L3
L3L3
L3
L3 L3
L3 L1
L1
EM-1
EM-1
EM-1
HV-EM1#9
HV-EM1#4
HV-OP1#4
HV-OP1#4
SHEET NO.
DATE
SCALE
CHECKED BY
DRAWN BY
CERTIFIED BY
CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLE1/16" = 1'-0"10/25/2021 11:31:48 AMLEVEL 2 ELECTRICALPLANSJLS
JLS
10/25/2021
E202
1/16" = 1'-0"1 LEVEL 2 POWER PLAN
1/16" = 1'-0"2 LEVEL 2 LIGHTING PLAN
E202 - KEYED NOTES
01
02 DUCTLESS SPLIT SYSTEM FOR ELEVATOR VESTIBULE.
03 BLADE SIGN FEED CONTROLLED BY TIME CLOCK.
04 EMERGENCY CIRCUITS ARE NOT TO BE COMBINED WITH GENERAL
LIGHTING CIRCUITS PER NEC 700.
05 GARAGE LIGHTING TO REMAIN POWERED AT ALL TIME.
POWER - GENERAL NOTES
A INITIATING CIRCUITS SHALL BE 18/2 AWG TWISTED PAIR FPL CABLE, AND
FPLP CABLE WHERE OPEN PLENUM RETURN IS USED.
B NAC CIRCUITS SHALL BE 12/2 AWG FPL CABLE, AND FPLP CABLE WHERE
OPEN PLENUM RETURN IS USED.
LIGHTING - GENERAL NOTES
A REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
PLACEMENT OF ALL LIGHTING FIXTURES. VERIFY CEILING CONSTRUCTION
AND PROVIDE LIGHTING FIXTURES WITH ALL NECESSARY MOUNTING
HARDWARE.
B RECESSED FIXTURES SHALL BE PROVIDED WITH STRUCTURAL SUPPORTS,
AS REQUIRED BY THE AHJ. IF REQUIRED, REFER TO DETAIL SHEETS FOR
INSTALLATION REQUIREMENTS.
C RECESSED FIXTURES LOCATED IN A FIRE RATED CEILING SHALL BE
PROVIDED WITH A FIVE SIDED ENCLOSURE, WITH A FIRE RATING GREATER
THAN OR EQUAL TO THE RATING OF THE CEILING ASSEMBLY. THE
ENCLOSURE SHALL MEET ALL NEC AND MANUFACTURER REQUIRED
CLEARANCES.
D ALL WORK SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO THE
BUILDING STRUCTURE, WHERE EXPOSED. ALL EXPOSED WIRING SHALL BE
IN CONDUIT, UNLESS OTHERWISE APPROVED BY OWNER.
E ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROPERLY
SEALED WITH AN APPROVED FIRE STOP SYSTEM GREATER THAN OR EQUAL
TO THE FIRE RATING OF THE WALL ASSEMBLY.
F RACEWAYS SHALL NOT BE PERMITTED TO SERVE AS AN EGC.
G ALL EXTERIOR PENETRATIONS, AND / OR PENETRATIONS THROUGH A
THERMAL ENVELOPE, SHALL BE SEALED WITH AN APPROVED SEALANT TO
PREVENT THE ENTRANCE OF AIR OR WATER. (NEC ART. 300.7(A))
H EMERGENCY LIGHTING WITH INDIVIDUAL BATTERY BACKUP SHALL BE FED
FROM THE SAME CIRCUIT AS THE LIGHTING IN THE AREA WHICH IT SERVES.
(NEC ART. 700.12(F))
04
05
No. Description Date
1 ISSUE
FOR
PERMIT
10/25/
2021