CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLE1/16" = 1'-0"10/25/2021 11:31:49 AMLEVEL 3 ELECTRICALPLANSJLS
JLS
10/25/2021
E203
1/16" = 1'-0"1 LEVEL 3 POWER PLAN
1/16" = 1'-0"2 LEVEL 3 LIGHTING PLAN
POWER - GENERAL NOTES
A INITIATING CIRCUITS SHALL BE 18/2 AWG TWISTED PAIR FPL CABLE, AND
FPLP CABLE WHERE OPEN PLENUM RETURN IS USED.
B NAC CIRCUITS SHALL BE 12/2 AWG FPL CABLE, AND FPLP CABLE WHERE
OPEN PLENUM RETURN IS USED.
LIGHTING - GENERAL NOTES
A REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
PLACEMENT OF ALL LIGHTING FIXTURES. VERIFY CEILING CONSTRUCTION
AND PROVIDE LIGHTING FIXTURES WITH ALL NECESSARY MOUNTING
HARDWARE.
B RECESSED FIXTURES SHALL BE PROVIDED WITH STRUCTURAL SUPPORTS,
AS REQUIRED BY THE AHJ. IF REQUIRED, REFER TO DETAIL SHEETS FOR
INSTALLATION REQUIREMENTS.
C RECESSED FIXTURES LOCATED IN A FIRE RATED CEILING SHALL BE
PROVIDED WITH A FIVE SIDED ENCLOSURE, WITH A FIRE RATING GREATER
THAN OR EQUAL TO THE RATING OF THE CEILING ASSEMBLY. THE
ENCLOSURE SHALL MEET ALL NEC AND MANUFACTURER REQUIRED
CLEARANCES.
D ALL WORK SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO THE
BUILDING STRUCTURE, WHERE EXPOSED. ALL EXPOSED WIRING SHALL BE
IN CONDUIT, UNLESS OTHERWISE APPROVED BY OWNER.
E ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROPERLY
SEALED WITH AN APPROVED FIRE STOP SYSTEM GREATER THAN OR EQUAL
TO THE FIRE RATING OF THE WALL ASSEMBLY.
F RACEWAYS SHALL NOT BE PERMITTED TO SERVE AS AN EGC.
G ALL EXTERIOR PENETRATIONS, AND / OR PENETRATIONS THROUGH A
THERMAL ENVELOPE, SHALL BE SEALED WITH AN APPROVED SEALANT TO
PREVENT THE ENTRANCE OF AIR OR WATER. (NEC ART. 300.7(A))
H EMERGENCY LIGHTING WITH INDIVIDUAL BATTERY BACKUP SHALL BE FED
FROM THE SAME CIRCUIT AS THE LIGHTING IN THE AREA W HICH IT SERVES.
(NEC ART. 700.12(F))
E203 - KEYED NOTES
01 DUCTLESS SPLIT SYSTEM FOR ELEVATOR VESTIBULE.
02 TOP DECK LIGHTS WILL BE CONTROLLED BY A PHOTOCELL. FIXTURE TO BE
MOUNTED ON TOP OF COLUMNS, AT THE SAME HEIGHT EVENLY ACROSS
TOP DECK.
03 EMERGENCY CIRCUITS ARE NOT TO BE COMBINED WITH GENERAL
LIGHTING CIRCUITS PER NEC 700.
DS-3
No. Description Date
1 ISSUE
FOR
PERMIT
10/25/
2021