CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLE1/16" = 1'-0"10/25/2021 11:31:50 AMROOF LEVEL ELECTRICALPLANSJLS
JLS
10/25/2021
E205
1/16" = 1'-0"1 ROOF LEVEL POWER PLAN
POWER - GENERAL NOTES
A INITIATING CIRCUITS SHALL BE 18/2 AWG TWISTED PAIR FPL CABLE, AND
FPLP CABLE WHERE OPEN PLENUM RETURN IS USED.
B NAC CIRCUITS SHALL BE 12/2 AWG FPL CABLE, AND FPLP CABLE WHERE
OPEN PLENUM RETURN IS USED.
LIGHTING - GENERAL NOTES
A REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
PLACEMENT OF ALL LIGHTING FIXTURES. VERIFY CEILING CONSTRUCTION
AND PROVIDE LIGHTING FIXTURES WITH ALL NECESSARY MOUNTING
HARDWARE.
B RECESSED FIXTURES SHALL BE PROVIDED WITH STRUCTURAL SUPPORTS,
AS REQUIRED BY THE AHJ. IF REQUIRED, REFER TO DETAIL SHEETS FOR
INSTALLATION REQUIREMENTS.
C RECESSED FIXTURES LOCATED IN A FIRE RATED CEILING SHALL BE
PROVIDED WITH A FIVE SIDED ENCLOSURE, WITH A FIRE RATING GREATER
THAN OR EQUAL TO THE RATING OF THE CEILING ASSEMBLY. THE
ENCLOSURE SHALL MEET ALL NEC AND MANUFACTURER REQUIRED
CLEARANCES.
D ALL WORK SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO THE
BUILDING STRUCTURE, WHERE EXPOSED. ALL EXPOSED WIRING SHALL BE
IN CONDUIT, UNLESS OTHERWISE APPROVED BY OWNER.
E ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROPERLY
SEALED WITH AN APPROVED FIRE STOP SYSTEM GREATER THAN OR EQUAL
TO THE FIRE RATING OF THE WALL ASSEMBLY.
F RACEWAYS SHALL NOT BE PERMITTED TO SERVE AS AN EGC.
G ALL EXTERIOR PENETRATIONS, AND / OR PENETRATIONS THROUGH A
THERMAL ENVELOPE, SHALL BE SEALED WITH AN APPROVED SEALANT TO
PREVENT THE ENTRANCE OF AIR OR WATER. (NEC ART. 300.7(A))
H EMERGENCY LIGHTING WITH INDIVIDUAL BATTERY BACKUP SHALL BE FED
FROM THE SAME CIRCUIT AS THE LIGHTING IN THE AREA W HICH IT SERVES.
(NEC ART. 700.12(F))
E205 - KEYED NOTES
01 CONDENSOR ON ROOF TO SERVICE (4) MINI SPLIT SYSTEMS FOR ELEVATOR
VESTIBULE.
No. Description Date
1 ISSUE
FOR
PERMIT
10/25/
2021