HomeMy WebLinkAboutE401 - Enlarged PlansELEC.
DOG WASH
DATA
OSOSOS STOR.RISER
FACPS
OS OS
ELECT.
H
H
LV-OP1#1
LV-OP1#1
LV-OP1#3
LV-OP1#3
LV-OP1#1EM
L3
L3
L3
L3
L2 L2
L2L2
EM EM
WH-1
+42"
+42"
HV-OP1#2
HV-EM1#2
LV-OP1#9,11
HV-OP1#15,17,19
EUH-1
EF-6
L3 L3
EUH-1
HV-OP1#12,14,16
LV-OP1#12
AIR
COMPRESSOR
HV-OP1#2
HV-EM1#2
LV-EM1#11
L3 L3 L3
LV-EM1#1
LV-EM1#1
LV-EM1T-EM1HV-EM1
ATS-EM1ATS-OP1
HV-OP1 T-OP1
HV-2B
HV-2A
HV1
LV-OP1
04
HV-OP1#2
HV-EM1#2
L4
LV-EM1#3
GEN.
HV-OP1#2
LV-OP1#16
HV-OP1#10
02
HV-OP1#9,11,13
03
TO PIT
LIGHT
01
SHEET NO.
DATE
SCALE
CHECKED BY
DRAWN BY
CERTIFIED BY
CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLE1/4" = 1'-0"10/25/2021 11:31:51 AMENLARGED PLANSJLS
JLS
10/25/2021
E401
POWER - GENERAL NOTES
A INITIATING CIRCUITS SHALL BE 18/2 AWG TWISTED PAIR FPL CABLE, AND
FPLP CABLE WHERE OPEN PLENUM RETURN IS USED.
B NAC CIRCUITS SHALL BE 12/2 AWG FPL CABLE, AND FPLP CABLE WHERE
OPEN PLENUM RETURN IS USED.
LIGHTING - GENERAL NOTES
A REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
PLACEMENT OF ALL LIGHTING FIXTURES. VERIFY CEILING CONSTRUCTION
AND PROVIDE LIGHTING FIXTURES WITH ALL NECESSARY MOUNTING
HARDWARE.
B RECESSED FIXTURES SHALL BE PROVIDED WITH STRUCTURAL SUPPORTS,
AS REQUIRED BY THE AHJ. IF REQUIRED, REFER TO DETAIL SHEETS FOR
INSTALLATION REQUIREMENTS.
C RECESSED FIXTURES LOCATED IN A FIRE RATED CEILING SHALL BE
PROVIDED WITH A FIVE SIDED ENCLOSURE, WITH A FIRE RATING GREATER
THAN OR EQUAL TO THE RATING OF THE CEILING ASSEMBLY. THE
ENCLOSURE SHALL MEET ALL NEC AND MANUFACTURER REQUIRED
CLEARANCES.
D ALL WORK SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO THE
BUILDING STRUCTURE, WHERE EXPOSED. ALL EXPOSED WIRING SHALL BE
IN CONDUIT, UNLESS OTHERWISE APPROVED BY OWNER.
E ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROPERLY
SEALED WITH AN APPROVED FIRE STOP SYSTEM GREATER THAN OR EQUAL
TO THE FIRE RATING OF THE WALL ASSEMBLY.
F RACEWAYS SHALL NOT BE PERMITTED TO SERVE AS AN EGC.
G ALL EXTERIOR PENETRATIONS, AND / OR PENETRATIONS THROUGH A
THERMAL ENVELOPE, SHALL BE SEALED WITH AN APPROVED SEALANT TO
PREVENT THE ENTRANCE OF AIR OR WATER. (NEC ART. 300.7(A))
H EMERGENCY LIGHTING WITH INDIVIDUAL BATTERY BACKUP SHALL BE FED
FROM THE SAME CIRCUIT AS THE LIGHTING IN THE AREA WHICH IT SERVES.
(NEC ART. 700.12(F))
E401 - KEYED NOTES
01 RATE OF RISE HEAT DETECTOR AT TOP OF ELEVATOR SHAFT.
02 RATE OF RISE HEAT DETECTOR LOCATED IN ELEVATOR LOBBY.
03 PROVIDE 60A, 600V NON-FUSE SAFETY SWITCH FOR ELEVATOR SUPPLY.
04 (24) EMPTY 1" CONDUITS FOR APARTMENT FEEDS STUBBED INTO THE
APARTMENT CORRIDOR FOR FUTURE EXTENSION BY OTHERS. EC TO
VERIFY HEIGHT AND COORDINATE WITH EV CHARGER PROVIDER FOR
CONNECTION METHOD. SEE CONDO DRAWINGS..
N
N
N N
1/4" = 1'-0"1 ELEC/DATA/DOG WASH PLAN
1/4" = 1'-0"2 STORAGE/RISER PLAN
1/4" = 1'-0"3 ELECTRICAL ROOM PLAN
1/4" = 1'-0"4 GENERATOR ROOM
1/4" = 1'-0"5 ELEVATOR PIT PLAN
N
1/4" = 1'-0"6 ELEVATOR TOP OF SHAFT PLAN
N
No. Description Date
1 ISSUE
FOR
PERMIT
10/25/
2021