1ST FLOOR
ELEVATOR LOBBY
2ND FLOOR
ELEVATOR LOBBY
3RD FLOOR
ELEVATOR LOBBY
4TH FLOOR
ELEVATOR LOBBY
FIRE ALARM
CONTROL
PANEL (FACP)
120V BY E.C.
1ST FLOOR
LOBBY
W.P.
@FACP SPRINKLER RISERS
STAIRWELL RISERS
A B C N
20' MIN.
CONCRETE ENCASED
REBAR
NEC 250.52(A)(3)
F
10' MIN
(2) 5/8"x8'
GROUND
RODS, 24" MIN
FROM EDGE
OF BUILDING
NEC 250.52(A)(5)
#4 AWG CU
C #1/0 AWG CU
METAL WATER PIPING
NEC 250.52(A)(1)
NEC 250.104(A)
F
H
G
SOURCE
TRANSFORMER
MAIN BONDING JUMPER / SCREW.
DETAIL NOTES
A
NON-CURRENT CARRYING METAL EQUIPMENT CONTAINING SERVICE
CONDUCTORS SHALL BE BONDED TOGETHER. WHERE POSSIBLE,
USE SCH. 40 PVC OR SCH. 80 PVC. (NEC 250.80, 250.92, 250.102)
B
GROUNDING ELECTRODE CONDUCTOR. (NEC 250.66)C
CONNECTIONS SHALL BE MADE USING LISTED CONNECTORS, AND
GRADE 2 HARDWARE WITH CORROSION RESISTANT COATING.
REMOVE PAINT AND OTHER NON-CONDUCTIVE COATINGS FROM
GROUNDING ELECTRODES PRIOR TO MAKING CONNECTIONS.
E
FERROUS METAL RACEWAYS AND ENCLOSURES CONTAINING
GROUNDING ELECTRODE CONDUCTORS SHALL BE BONDED TO THE
GROUNDING ELECTRODE. (NEC 250.64(E))
F
PROVIDE BONDING JUMPERS AROUND WATER METERS, FILTERS,
HEAT TRAPS, AND SIMILAR DEVICES. (NEC 250.53(D)(1)) (NEC 250.104)
G
BOND METAL WATER PIPING TO EITHER STRUCTURAL STEEL OR
SERVICE ENTRANCE GROUNDED CONDUCTOR BUS. (NEC 250.104)
H
#1/0 AWG CU
G
MAIN
A B C
METER
B
A
N
(TYP)
STRUCTURAL STEEL
NEC 250.52(A)(2)
F
ADDITIONAL SERVICE DISCONNECTING MEANS AND SEPARATELY
DERIVED SYSTEMS SHALL BE BONDED TO BUILDING STEEL, OR TO A
COMMON GROUNDING ELECTRODE CONDUCTOR.
D
N
SHEET NO.
DATE
SCALE
CHECKED BY
DRAWN BY
CERTIFIED BY
CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLEAs indicated
10/25/2021 11:31:55 AMDETAILSJLS
JLS
10/25/2021
E701
NTS2FIRE ALARM RISER DIAGRAM
FIRE ALARM - KEYED NOTES
01 RATE OF RISE HEAT DETECTOR AT TOP OF ELEVATOR SHAFT.
02 RATE OF RISE HEAT DETECTOR LOCATED IN ELEVATOR LOBBY.
03 POST INDICATOR VALVE (PIV). PROVIDE TAMPER SWITCH AT THE VALVE
FOR A SUPERVISORY SIGNAL TO THE FACP.
04 PROVIDE HORN STROBE IN A WEATHER PROOF ENCLOSURE.
05 FIRE ALARM CONTROL PANEL. PROOVIDE DEDICATED 120VOLT CIRCUIT AND
CONNECT AS DIRECTED. THE FIRE ALARM PANEL IS TO BE PROVIDED WITH
INPUT AND OUTPUT CONTACTS TO ALLOW CONNECTION TO FUTURE RETAIL
AND RESIDENTIAL SYSTEMS.
06 FIRE ALARM ANNUNCIATOR PANEL.
01
02
03
04
05
06
FIRE ALARM - GENERAL NOTES
A INITIATING CIRCUITS SHALL BE 18/2 AWG TWISTED PAIR FPL CABLE, AND
FPLP CABLE WHERE OPEN PLENUM RETURN IS USED.
B NAC CIRCUITS SHALL BE 12/2 AWG FPL CABLE, AND FPLP CABLE WHERE
OPEN PLENUM RETURN IS USED.
NTS1SERVICE GROUNDING DETAILS - PANELBOARDS
No. Description Date
1 ISSUE
FOR
PERMIT
10/25/
2021