HomeMy WebLinkAboutP101 - Second and Third Floor Plumbing PlanI.T. ROOM
I.T. ROOM
UP
DN
1 2 32.61.3
A
C
D
E
F
G
H
I
J
L
B
K RAMPDOWNRAMPUP2.5
STOR.
STOR. /
SOLAR
POWER
UP
DN
1 2 32.61.3
A
C
D
E
F
G
H
I
J
L
B
K RAMPDOWNRAMPUP6
P500
1 2
1 2
4"FD-1
4"FD-1
1 2
4"FD-1
3
HB-1
HB-1
3
1 2
4"FD-1
4
6"AD-1
6"AD-1
6"AD-1
6"AD-1
4
3
HB-1
3
HB-1
GENERAL NOTES:
1. PROVIDE NEW DOMESTIC WATER, SANITARY WASTE, STORM
DRAINAGE AND NATURAL GAS SYSTEMS FOR THIS BUILDING. PROVIDE
ALL NECESSARY COMPONENTS FOR FULLY OPERATIONAL SYSTEM.
INSTALL SYSTEMS IN ACCORDANCE WITH STATE REQUIREMENTS AND
LOCAL AUTHORITY HAVING JURISDICTION. COORDINATE THE
LOCATION OF ALL UTILITY CONNECTION POINTS, FLOOR DRAINS AND
HUB DRAINS FOR EQUIPMENT WITH OTHER TRADES.
2. ALL FLOOR PENETRATIONS TO BE SEALED WATER TIGHT BY TRADE
CONTRACTORS.
3. ALL PENETRATIONS THROUGH FIRE RESISTANCE RATED
CONSTRUCTION SHALL BE PROVIDED A UL LISTED THROUGH
PENETRATION FIRESTOP ASSEMBLY. THE RATINGS OF ALL FIRESTOP
ASSEMBLIES SHALL BE GREATER THAN OR EQUAL TO THE RATING OF
THE PENETRATED BARRIER.
4. CORE DRILL PENETRATIONS IN CONCRETE FLOORS OR WALLS 1-2
INCHES LARGER THAN THE PIPE DRIAMETER OF THE PENETRATING
PIPE.
5. NO STURCTURAL MEMBERS SHALL BE CUT, DRILLED OR BURNED
WITHOUT THE KNOWLEDGE AND WRITTEN APPROVAL OF OWNER.
6. MAINTAIN MAIXIMUM HEADROOM AT ALL LOCATIONS. ALL PIPING TO
BE AS TIGHT TO THE UNDERSIDE OF DECK AS POSSIBLE. ALL
EXPOSED PIPING SHALL BE APPROVED BY ARCHITECT AND SHALL
MAINTAIN REQUIRED CLEARANCES.
7. STORM AND SANITARY PIPING ARE TO BE INSTALLED SLOPED AT CODE
ALLOWABLE SLOPES.RD
PE11400027
NENOISS
AL
EFORP D
STATE OF
NI I A N A ERGIN ESIGE T E RE
No.CAMERO NT .YAMA
SHITASHEET NO.
DATE
SCALE
CHECKED BY
DRAWN BY
REVISIONSYM.DATE
CERTIFIED BY
CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLEAs indicated
10/25/2021 10:14:51 AMSECOND AND THIRDFLOOR PLUMBING PLANC.Y.
D.T.
10/25/21
P101
1/16" = 1'-0"P101
1 SECOND FLOOR PLUMBING PLAN
1/16" = 1'-0"P101
2 THIRD FLOOR PLUMBING PLAN
# PLAN NOTES
1 6" STORM UP TO AREA DRAIN.
2 6" STORM CONDUCTOR.
3 3/4" COLD WATER RISER WITH HOSE BIBB AT 24" A.F.F. EACH
FLOOR. RISER INSTALLED TO BE ABLE TO DRAIN DOWN THROUGH
LOWEST HOSE BIBB.
4 4" VENT UP TO ABOVE THIRD FLOOR.