HomeMy WebLinkAboutE001 - Symbols and AbbreviationsOHE OHEOHE
UGE UGEUGE
T TT
PIV
PS
WF
VS SYMBOLS, ABBREVIATIONS, AND GENERAL SPECIFICATIONSSOME SYMBOLS AND/OR ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT -ADDITIONAL SYMBOLS MAY BE USED WHERE NEEDEDSTANDARD ABBREVIATIONS
A AMPERES
AC ALTERNATING CURRENT
AF AMPERE FUSE
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING
CAPACITY
AL ALUMINUM
ARCH ARCHITECT(URAL)
ATS AUTOMATIC TRANSFER
SWITCH
AUTO AUTOMATIC
AVG AVERAGE
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BHP BRAKE HORSEPOWER
BPS BOOSTER POWER SUPPLY
BTM BOTTOM
C CONDUIT
CB CIRCUIT BREAKER
C/C CENTER TO CENTER
CCTV CLOSED CIRCUIT
TELEVISION
CF CUBIC FEET
CKT CIRCUIT
CL CENTERLINE
CLG CEILING
COMM COMMUNICATIONS
COMP COMPRESSOR
CONT CONTINUOUS
CR CRITICAL LOAD
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
DP DISTRIBUTION PANEL
DPST DOUBLE POLE, SINGLE
THROW
DWG DRAWING
DWH DOMESTIC WATER HEATER
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EGC EQUIPMENT GROUNDING
CONDUCTOR
EM EMERGENCY (LOAD)
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXIT
EXH EXHAUST
EXP EXPLOSIONPROOF
EXT EXTERIOR
FA FIRE ALARM
FAAP FA ANNUNCIATOR PANEL
FACP FA CONTROL PANEL
FC FLAT CABLE
FCU FAN COIL UNIT
FFC FOOD FACILITY
CONTRACTOR
FFS FOOD FACILITY SUPPLIER
FHC FIRE HOSE CABINET
FIXT FIXTURE
FLUOR FLUORESCENT
FPC FIRE PROTECTION
CONTRACTOR
FSS FUSED SAFETY SWITCH
FTG FOOTING
FTL FEED THROUGH LUGS
FV FULL VOLTAGE
G, GND GROUND
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEC GROUNDING ELECTRODE
CONDUCTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT
INTERRUPTOR
GFP GROUND FAULT
PROTECTION
GTB GENERATOR TAP BOX
H, HV HIGH VOLTAGE
HID HIGH INTENSITY
DISCHARGE
HO HAND OPERATED
HOA HAND-OFF-AUTO
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
Hz HERTZ
IC INTERCOM
ID INSIDE DIAMETER
ISG ISOLATED GROUND
J, JB JUNCTION BOX
KEC KITCHEN EQUIPMENT
CONTRACTOR
kV KILOVOLTS
kVA KILOVOLT-AMPERES
kVAR KILOVOLT-AMPERES
REACTIVE
kW KILOWATTS
L or LV LOW VOLTAGE
LB POUND
LCP LIGHTING CONTROL PANEL
LF LINEAR FEET
LP LIGHTING PANEL
LS LIFE SAFETY LOAD
LT LIGHT
LTG LIGHTING
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT
BREAKER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MSB MAIN SWITCHBOARD
NIC NOT IN CONTRACT
OCP OVERCURRENT
PROTECTION
OD OUTSIDE DIAMETER
OF/CI OWNER FURNISHED,
CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED,
OWNER INSTALLED
OR OPERATING ROOM
P POLE
PB PUSH BUTTON
PC PLUMBING CONTRACTOR
PF POWER FACTOR
PH, Φ, Ø PHASE
PIV POST INDICATOR VALVE
PL PILOT LIGHT
PNL PANELBOARD
PREFAB PREFABRICATED
PT PNEUMATIC TUBE
PTS PNEUMATIC TUBE STATION
PTZ PAN-TILT-ZOOM
PW PART WINDING
PWR POWER
RCPT RECEPTACLE
REF REFRIGERATOR
RM ROOM
RP RECEPTACLE PANEL
RPM REVOLUTIONS PER MINUTE
SCCR SHORT CIRCUIT CURRENT
RATING
SG SURGE GUARD
SN SOLID NEUTRAL
SPEC SPECIFICATIONS
SQ FT SQUARE FEET
SS SAFETY SWITCH
SSBJ SUPPLY SIDE BONDING
JUMPER
STD STANDARD
STN STATION
STR STRUCTUR(E),(AL)
SUSP SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TCC TEMPERATURE CONTROL
(CONTRACTOR), (CABINET)
TELE TELECOMMUNICATION
TEMP TEMPORARY
TV TELEVISION
TYP TYPICAL
UCR UNDER COUNTER
REFRIGERATOR
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED
OTHERWISE
V VOLT
VFD VARIABLE FREQUENCY
DRIVE
VP VAPORPROOF
W/WITH
W/O WITHOUT
WP WEATHERPROOF
WTR WATER
Z IMPEDANCE
ADA ACCESSIBLE ROOM -ALL OPERABLE DEVICES SHALL
BE MOUNTED BETWEEN 18" AFF TO BOTTOM AND 48" AFF
TO TOP OF DEVICE.
HEARING IMPAIRED COMMUNICATIONS FEATURE ROOM -
VISUAL NOTIFICATION REQUIRED FOR AS SHOWN ON
PLANS.
KEYED DEMOLITION PLAN NOTE
KEYED NEW WORK PLAN NOTE
01
01
SECTION VIEW REFERENCE
VIEW REFERENCE, INCLUDING DETAILS
& ENLARGED PLANS
1
E-301
1
E-501
1 / E-301 VIEW REFERENCE TAG
GENERAL DRAWING ANNOTATIONS
15.ALL WIRING SHALL BE INSTALLED PARALLEL & PERPINDICULAR TO THE
BUILDING STRUCTURAL MEMBERS, EXCEPT WHERE INSTALLED
UNDERGROUND.
16.A DEDICATED COPPER OR ALUMINUM EGC SHALL BE INSTALLED IN ALL
RACEWAYS, EXCEPT IN SERVICE ENTRANCE CONDUITS. PARTICULAR
CARE SHALL BE TAKEN TO ELIMINATE OBJECTIONAL CURRENT, SEE
GROUNDING & BONDING DETAILS FOR SITE SPECIFIC REQUIREMENTS.
17.IT SHALL BE THE EC'S RESPONSIBILITY TO REVIEW CONDUIT SIZES AND
WIRE AMPACITY PRIOR TO INSTALLATION, TO ENSURE A
CODE-COMPLIANT INSTALLATION.
18.IT SHALL BE THE EC'S RESPONSIBILITY TO CONTACT THE DESIGNER
WITH ANY QUESTIONS, CONCERNS, OR PROPOSED CHANGES BEFORE
COMMENCING WORK.
19.CIRCUITS MAY BE COMBINED IN CONDUITS, CABLES, OR RACEWAYS,
PROVIDED THAT THE CONDUCTORS ARE PROPERLY DERATED & ALL
RACEWAYS ARE SIZED PER THE NEC. NO MORE THAN (9) CURRENT-
CARRYING CONDUCTORS ARE ALLOWED PER RACEWAY.
20.CIRCUITS ARE SIZED FOR VOLTAGE DROP BASED ON ESTIMATED
ROUTING. THE EC SHALL VERIFY THAT THE ACTUAL ROUTING CHOSEN
COMPENSATES FOR VOLTAGE DROP AS FOLLOWS:
A.ALL CONDUCTORS SHALL BE SIZED TO PREVENT EXCESSIVE
VOLTAGE DROP. FEEDERS SHALL NOT EXCEED 2% VOLTAGE
DROP & BRANCH CIRCUITS SHALL NOT EXCEED 3%
VOLTAGE DROP.
B.IN GENERAL, CONDUCTORS SHALL NOT BE REQUIRED TO
INCREASE MORE THAN TWO (2) SIZES FOR THIS PURPOSE,
UNLESS NOTED OTHERWISE.
C.THE EGC SHALL INCREASE PROPORTIONALLY FROM THE SIZE
REQUIRED BY THE NEC, AS REQUIRED BY NEC 250.122(B).
21.WIRES SHALL BE COLOR CODED AS FOLLOWS, OR AS REQUIRED BY
THE AHJ:
A.240/120V SYSTEMS = BLACK (L1), RED (L2), WHITE (N)
B.208Y/120V SYSTEMS = BLACK (A), RED (B), BLUE (C), WHITE (N)
C.240D/120V SYSTEMS = BLACK (A), ORANGE (B), BLUE (C),
WHITE (N)
D.480Y/277V SYSTEMS = BROWN (A), ORANGE OR PURPLE (B),
YELLOW (C), GRAY (N)
22.ALL PANELBOARDS, SWITCHBOARDS, AND SWITCHGEAR SHALL HAVE A
PERMANENT LEGEND SHOWING THE DESIGNATED CONDUCTOR
COLORS, AS REQUIRED BY NEC 210.5(C).
23.WIRING SHALL BE #12 AWG COPPER, UNO. IN ALL CASES, THE EC SHALL
VERIFY THE CORRECT SIZE WIRING IS INSTALLED, FOR A
CODE-COMPLIANT INSTALLATION.
24.CONDUCTOR SIZES SHOWN ARE BASED ON 75° C RATED TERMINATIONS
PER NEC 110.14(C), UNO. EC SHALL FIELD VERIFY TERMINATIONS TO
CONFIRM PRIOR TO TERMINATING CONDUCTORS.
01.ALL MATERIAL & WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE
CODES, SPECIFICATIONS, LOCAL ORDINANCES, AND ACCEPTED
INDUSTRY STANDARDS.
02.THIS PROJECT CONSISTS OF TWO PARTS: THE CONTRACT DRAWINGS &
THE PROJECT SPECIFICATIONS. WHERE THESE DOCUMENTS ARE NOT
IN AGREEMENT, THE MOST STRINGENT CONDITION SHALL APPLY. IN ALL
CASES, THE EC SHALL REQUEST WRITTEN CLARIFICATION.
03.ALTHOUGH NOT ALL BRANCH WIRING & CONDUIT ARE SHOWN ON
THESE DRAWINGS, IT IS THE INTENT OF THESE DOCUMENTS THAT A
COMPLETE AND FUNCTIONING BRANCH WIRING SYSTEM BE INSTALLED.
04.ALL CONDUITS, CABINETS, CABLES, AND BOXES SHALL BE SECURELY
FASTENED AND SUPPORTED PER THE NEC.
05.ALL DIMENSIONS SHALL BE OBTAINED FROM ARCHITECTURAL AND CIVIL
SITE PLANS. IN NO CASE SHALL THE ELECTRICAL DRAWINGS BE
SCALED.
06.ALL DIMENSIONS SHOWN SHALL BE TO THE CENTERLINE OF THE
EQUIPMENT OR DEVICE BOX, UNLESS NOTED OTHERWISE.
07.VERIFY ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT PROVIDED BY
OTHERS & CONNECTED BY ELECTRICAL CONTRACTOR, PRIOR TO
INSTALLATION OF WIRING, INCLUDING RECEIVING & REVIEWING
APPROVED SUBMITTALS FOR EQUIPMENT PROVIDED BY OTHER
BUILDING TRADES.
08.THE ENTIRE SET OF PROJECT DRAWINGS HAS INFORMATION
PERTAINING TO THE CONSTRUCTION OF THE BUILDING, AND THE
ELECTRICAL CONTRACTOR SHALL REVIEW ALL DRAWINGS TO
COORDINATE THE INSTALLATION OF ELECTRICAL SYSTEMS.
09.REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
COORDINATION OF LIGHTING FIXTURES & EQUIPMENT FURNISHED OR
PROVIDED BY OTHERS. EC SHALL TAKE PARTICULAR CARE TO
COORDINATE WITH THE FPC, PC, AND THE MC.
10.REFER TO ARCHITECTURAL PLANS & INTERIOR ELEVATIONS TO
COORDINATE ALL WALL MOUNTED DEVICES WITH CABINETRY &
CASEWORK. ENSURE THAT ALL DEVICE PLATES AND OTHER
EQUIPMENT WILL NOT CONFLICT WITH COUNTERTOPS, BACKSPLASHES,
WALL TILE, TRIM, ETC.
11.ALL DEVICES MOUNTED ABOVE A COUNTERTOP OR BACKSPLASH SHALL
BE INSTALLED AT THE SAME HEIGHT.
12.DEVICES INSTALLED IN BLOCK OR TILED WALLS SHALL BE INSTALLED
WITH THE BOX SET ON TOP OF NEAREST COURSE, WITH THE OPENING
FOR THE BOX CUT INTO THE COURSE ABOVE. ALL DEVICE BOXES SHALL
BE INSTALLED ON TOP OF THE COURSE NEAREST TO THE SCHEDULED
MOUNTING HEIGHT.
13.WHERE MULTIPLE DEVICES OF THE SAME VOLTAGE ARE INSTALLED IN
CLOSE PROXIMITY, THEY SHALL BE GANGED TOGETHER IN A COMMON
BOX AND COVER PLATE.
14.COORDINATE ALL FASTENERS USED WITH WALL, CEILING, AND
STRUCTURAL SYSTEMS. EC SHALL TAKE PARTICULAR CARE NOT TO
USE FASTENERS IN A METHOD WHICH VIOLATES MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
GENERAL PROJECT NOTES / SPECIFICATIONS
DEVICE TYPE: "X" INDICATES THE TYPES LISTED BELOW, UNO:
BLANK = NORMAL POWER / STANDARD RECEPTACLE
IG = NORMAL POWER / ISOLATED GROUND RECEPTACLE
TR = NORMAL POWER / TAMPERPROOF RECEPTACLE
WP = NORMAL POWER / WEATHER RESISTANT RECEPTACLE WITH
WEATHERPROOF IN-USE COVER
EM = EMERGENCY POWER / STANDARD RECEPTACLE WITH RED
BODY
USB = NORMAL POWER / STANDARD RECEPTACLE WITH (2)
INTEGRAL USB CHARGING PORTS AND 5V POWER SUPPLY
OC = INSTALL AT 8" ABOVE COUNTERTOP HEIGHT -COORDINATE
WITH ANY BACKSPLASH OR TILED FINISHES
RECEPTACLES / ELECTRICAL DEVICES
SIMPLEX RECEPTACLE, WALL MOUNTED.X
X
DUPLEX RECEPTACLE, WALL MOUNTED
SOLID CENTER INDICATES DEDICATED CIRCUIT.X
SPLIT WIRED DUPLEX RECEPTACLE, WALL
MOUNTED.
DOUBLE DUPLEX (QUAD) RECEPTACLES, WALL
MOUNTED. SOLID CENTER INDICATES DUAL
DEDICATED CIRCUITS.
X
GFCI RATED RECEPTACLE, WALL MOUNTED
SOLID CENTER INDICATES DEDICATED CIRCUIT.
X
SPECIAL PURPOSE RECEPTACLE, NEMA
CONFIGURATION AS NOTED ON PLANS, WALL
MOUNTED.
X
DESCRIPTIONSYMBOL MOUNTING
HEIGHT
+18" AFF
+18" AFF
+18" AFF
+18" AFF
+18" AFF
+18" AFF
DUPLEX RECEPTACLE, CEILING MOUNTED.X N/A
JUNCTION BOX
X
SEE PLANS
MULTI-SERVICE CEILING OUTLET,
CONFIGURATION AS NOTED ON PLANS,
CEILING MOUNTED.
X N/A
MULTI-SERVICE FLOORBOX OR POKE THRU,
CONFIGURATION AS NOTED ON PLANS,
FLOOR MOUNTED.
X N/A
J
JUNCTION BOX WITH FLEXIBLE EQUIPMENT
CONNECTION, (6) FEET MAX LENGTH.SEE PLANSJ
DOUBLE DUPLEX (QUAD) RECEPTACLES,
CEILING MOUNTED.N/A
MULTI-SERVICE POWER POLE, CONFIGURATION
NOTED ON PLANS.N/A
PUSHBUTTON, TYPE AND QUANTITY OF
BUTTONS AS NOTED ON PLANS.SEE PLANS
X
X
X
TTHERMOSTAT, FURNISHED BY OTHERS UNO.
SEE MECHANICAL SCHEDULES FOR DETAILS.+44" AFF
ABORT SWITCH / EMERGENCY POWER OFF
SWITCH, SEE PLANS FOR DETAILS +44" AFFEPO
POWER DISTRIBUTION
MAIN SWITCHBOARD, MAY BE SWITCHBOARD OR
SWITCHGEAR CONSTRUCTION, SEE PLANS FOR
DETAILS. FLOOR MOUNTED, FREE STANDING.
DASHED LINES REPRESENT CODE REQUIRED
CLEARANCES.
DESCRIPTIONSYMBOL
MSB-A
SURFACE MOUNTED DISTRIBUTION
PANELBOARD. DASHED LINES REPRESENT
CODE REQUIRED CLEARANCES.
SURFACE MOUNTED BRANCH PANELBOARD.
DASHED LINES REPRESENT CODE
REQUIRED CLEARANCES.
FLUSH MOUNTED BRANCH PANELBOARD.
DASHED LINES REPRESENT CODE
REQUIRED CLEARANCES.
HV-1
HV-1
T-1 DRY TYPE TRANSFORMER, 15kVA OR LARGER.
T DRY TYPE TRANSFORMER, LESS THAN 15kVA.
SEE PLANS FOR DETAILS.
SEGB SERVICE ENTRANCE GROUNDING BUS. SEE
PLANS FOR DETAILS.
NF DISCONNECT SWITCH, NON-FUSED. MOUNT AT
48" AFF, UNO.
DISCONNECT SWITCH, FUSIBLE. FUSE RATING
SHOWN. MOUNT AT 48" AFF, UNO.
COMBINATION MOTOR STARTER / FUSIBLE
DISCONNECT. NEMA STARTER SIZE AND FUSE
RATING SHOWN. MOUNT AT 48" AFF, UNO.
60A
N1/60A
ELECTRIC MOTOR, NUMBER INDICATES
HORSEPOWER. NOT DRAWN TO SCALE.500
25,769 A AVAILABLE BOLTED FAULT CURRENT
FEEDER TAG, SEE SCHEDULE FOR DETAILS.F0500NG-CU
~150', 1.5% VD
LIGHTING FIXTURES / DEVICES
FIXTURE TYPES AND/OR SWITCHING ARE INDICATED AS LISTED BELOW, UNO:
#= FIXTURE TYPE MARK, REFER TO FIXTURE SCHEDULES.
NL = "NIGHT LIGHT" FIXTURE, WIRED FOR 24 HOUR OPERATION.
a,b = INDICATES SWITCH GROUP WITHIN ROOM OR AREA
SHADING INDICATES FIXTURE EITHER CONTAINS AN INTEGRAL BATTERY
OPERATED EMERGENCY INVERTER OR IS CONNECTED TO AN EMERGENCY
POWER SUPPLY SYSTEM. REFER TO PLANS FOR DETAILS.
DESCRIPTIONSYMBOL MOUNTING
HEIGHT
RECESSED FIXTURE
NL
#a,b
a,b#SURFACE MOUNTED FIXTURE
#a,b LINEAR FIXTURE, SUSPENDED.
RECESSED DOWNLIGHT. ARROW INDICATES
DIRECTION OF WALL WASH LENS, WHERE USED.
#a,b
#a,b WALL MOUNTED FIXTURES
#
NL
a,b SURFACE MOUNTED STRIP FIXTURES
#
#
##
EMERGENCY EXIT SIGN. SHADING INDICATES
FACES USED, ARROWS INDICATE EGRESS PATH.
MAY BE CEILING MOUNTED, NOT EXCEEDING
+12'-0" AFF.
WALL MOUNTED EMERGENCY LIGHTING UNIT
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
+8'-0" AFF
+8'-0" AFFEMERGENCY LIGHTING REMOTE HEAD, MOUNT
+12" ABOVE DOOR FRAMES OR AS NOTED.
WALL =
+8'-0" AFF
X
a
DEVICE TYPE: "X" INDICATES THE TYPES LISTED
BELOW, UNO:
BLANK = SINGLE POLE TOGGLE SWITCH
2 = DOUBLE POLE TOGGLE SWITCH
3 = THREE WAY TOGGLE SWITCH
4 = FOUR WAY TOGGLE SWITCH
M = MOTOR RATED SWITCH
LV = DIGITAL LOW VOLTAGE SWITCH
D = DIMMING SWITCH
T = TIMER SWITCH
WP = WEATHERPROOF SWITCH
K = KEY OPERATED SWITCH
OS = OCCUPANCY SENSOR SWITCH
+48" AFF
OS a
SEE
SCHEDULES
OCCUPANCY SENSOR, TYPE AS INDICATED IN
SCHEDULES.
PC a
SEE
SCHEDULES
PHOTOCELL, TYPE AS INDICATED
IN SCHEDULES.
PP a
SEE
SCHEDULES
LIGHTING CONTROL RELAY, TYPE AS INDICATED
IN SCHEDULES.
DEVICE TYPE: "X" INDICATES THE TYPES LISTED BELOW, UNO:
BLANK = STANDARD OUTLET, SINGLE PORT FOR EACH
SYSTEM TYPE PRESENT
# (2,4..) = NUMBER OF PORTS FOR TYPE OF SYSTEM PRESENT
W = WALL MOUNTED AT 44", UNO
OC = INSTALL AT 8" ABOVE COUNTERTOP HEIGHT -COORDINATE
WITH ANY BACKSPLASH OR TILED FINISHES
WAP = WIRELESS ACCESS POINT
TELECOMMUNICATIONS / AUDIO-VISUAL
DATA OUTLET, WALL MOUNTEDX
X
COMBINATION DATA / TELEPHONE OUTLET,
WALL MOUNTEDX
TELEPHONE OUTLET, WALL MOUNTED
DESCRIPTIONSYMBOL MOUNTING
HEIGHT
+18" AFF
+18" AFF
+18" AFF
INTERCOM STATION, SEE PLANS FOR TYPE +42" AFF
DATA OUTLET, CEILING MOUNTEDX N/A
SINGLE-LINE DIAGRAM
DESCRIPTIONSYMBOL
400AT
400AF
LSI
CIRCUIT BREAKER -TRIP RATING / FRAME SIZE,
AND/OR NUMBER OF POLES. SETTINGS AND
OTHER ACCESSORIES AS NOTED ON PLANS.
400AT
400AF
LSIG
EB
DRAWOUT CIRCUIT BREAKER -TRIP RATING /
FRAME SIZE, AND/OR NUMBER OF POLES.
SETTINGS AND OTHER ACCESSORIES AS NOTED
ON PLANS.
TRANSFORMER -VOLTAGE CONFIGURATION,
KVA RATING, WIRING CONFIGURATION. SEE
PLANS FOR OTHER DETAILS AND
REQUIREMENTS.
T-1
2,500 kVA
480D-208Y/120V
3000-5 CURRENT TRANSFORMER -RATIO OF PRIMARY
TO SECONDARY WINDINGS.
480-120
75 VA
POTENTIAL TRANSFORMER -RATIO OF PRIMARY
VOLTAGE TO SECONDARY VOLTAGE, HEAT
RATING.
1000A
BPS
DISCONNECT SWITCH -FRAME SIZE.
"BPS" INDICATES BOLTED PRESSURE SWITCH.
1000A
CLASS J FUSE -TRIP RATING, FUSE CLASS.
ELECTRONIC BREAKER OPERATORS:
EB = MOTOR OPERATED CLOSE / OPEN
GF = GROUND FAULT TRIP UNIT
ST = SHUNT TRIP OPEN
UV = UNDERVOLTAGE RELEASE
400AT
400AF
LSIG
GF
GROUND CONNECTION
N E TRANSFER SWITCH, SEE PLANS FOR TYPE AND
OTHER DETAILS. ARC INDICATES CLOSED
TRANSITION.
SPD SURGE PROTECTIVE DEVICE, SEE PLANS.
ELECTRONIC METER, SEE PLANS FOR TYPE.
KEYED INTERLOCK, SEE PLANS FOR DETAILS.
PROTECTIVE RELAY, SEE PLANS FOR DETAILS.
M
K1
R1
ELECTRICAL CONNECTION, BOLT / LUG / SCREW.
CIRCUITS
PHASE CONDUCTORS
GROUND CONDUCTOR (IF TWO ARE SHOWN,
THE SECOND SHALL BE AN ISOLATED GROUND)
NEUTRAL CONDUCTOR
CONDUITS
DESCRIPTIONSYMBOL
CONDUIT / RACEWAY, SEE PLANS FOR TYPE.
CONDUIT / RACEWAY, UNDERGROUND,
SEE PLANS FOR TYPE.
CONDUIT TRANSITIONS
DOWN UP
CONDUIT / RACEWAY, CAPPED AND SEALED.
OVERHEAD ELECTRICAL CONDUCTORS
UNDERGROUND ELECTRICAL RACEWAY
TELECOM SERVICE, UNDERGROUND
DEMOLITION / NEW CONSTRUCTION
DESCRIPTIONSYMBOL
XX
a
NL
#a,b DASHED LINES INDICATE DEVICE TO
BE REMOVED / DEMOLISHED.XX
a
NL
#a,b THIN LINES INDICATE DEVICE FROM PREVIOUS
PHASE / EXISTING CONDITIONS.XX
a
NL
#a,b SOLID, HEAVY LINES INDICATE DEVICE TO BE
INSTALLED DURING PHASE SHOWN / NEW WORK.
ELECTRONIC SECURITY
KEYPAD, WALL MOUNTED.
DESCRIPTIONSYMBOL MOUNTING
HEIGHT
+54" AFF
CARD READER, WALL MOUNTED.+42" AFF
BIOMETRIC ACCESS CONTROL SEE PLANS
PUSH BUTTON, SEE PLANS FOR TYPE SEE PLANS
CONTACT SWITCH, SEE PLANS FOR TYPE SEE PLANS
CONTROL PANEL +60" AFF
SECURITY CAMERA, SEE PLANS FOR TYPE SEE PLANS
AUDIO DEVICE, SEE PLANS FOR TYPE SEE PLANS
DETECTOR, SEE PLANS FOR TYPE SEE PLANS
GLASS BREAK SENSOR SEE PLANS
ELECTRONIC LOCK, SEE PLANS FOR TYPE SEE PLANS
VEHICLE GROUND LOOP SENSOR N/A
ADDRESSABLE OUTPUT RELAY N/A
FIRE ALARM / DETECTION
FACP
DESCRIPTIONSYMBOL MOUNTING
HEIGHT
FIRE ALARM CONTROL PANEL, WALL MOUNTED +60" AFF,
TOP
NAC FIRE ALARM NAC PANEL, WALL MOUNTED +60" AFF,
TOP
FAA FIRE ALARM ANNUNCIATOR, WALL MOUNTED +48" AFF
F MANUAL PULL STATION / FIRE ALARM BOX, WALL
MOUNTED
+48" AFF,
TOP
FIRE SERVICE PHONE STATION, WALL MOUNTED +48" AFF,
TOP
VISIBLE (STROBE) NOTIFICATION DEVICE, WALL
OR CEILING MOUNTED SEE PLANS
cd
AUDIBLE/VISIBLE (HORN/STROBE) NOTIFICATION
DEVICE, WALL OR CEILING MOUNTED SEE PLANS
cd
cd
AUDIBLE (HORN) NOTIFICATION DEVICE, WALL
OR CEILING MOUNTED SEE PLANSF
S
x
AUTOMATIC SMOKE DETECTOR, CEILING OR
WALL MOUNTED.
DEVICE TYPE: "X" INDICATES TYPES LISTED
BELOW, UNO:
AS = AIR SAMPLING
I = IONIZATION
P = PHOTOELECTRIC
R = RELAY MODULE BASE
SB = SOUNDER BASE (520 Hz OPTIONAL)
IM = ISOLATOR MODULE BASE
SS = SINGLE/MULTIPLE STATION SMOKE
ALARM
SEE PLANS
AUTOMATIC SMOKE DETECTOR,
PHOTOELECTRIC TYPE DETECTION, DUCT
MOUNTED
IN DUCT
S
P
AUTOMATIC HEAT DETECTOR, CEILING OR WALL
MOUNTED.
DEVICE TYPE: "X" INDICATES TYPES LISTED
BELOW, UNO:
F = FIXED TEMPERATURE
R = RATE OF RISE
R/F = COMBINATION RISE/FIXED TEMP
R/C = RATE COMPENSATED
SEE PLANSH
x
ADDRESSABLE INPUT MODULE, "X" INDICATES
NUMBER OF INPUTS SEE PLANSAIM
x
ADDRESSABLE OUTPUT MODULE, "X" INDICATES
NUMBER OF OUTPUTS SEE PLANSAOM
x
POST INDICATOR VALVE SUPERVISORY SWITCH SEE PLANS
PRESSURE SWITCH SUPERVISORY DEVICE SEE PLANS
WATER FLOW SUPERVISORY SWITCH SEE PLANS
VALVE (TAMPER) SUPERVISORY SWITCH SEE PLANS
MAGNETIC DOOR HOLDER SEE PLANSDH
SHEET NO.
DATE
SCALE
CHECKED BY
DRAWN BY
CERTIFIED BY
CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLE1/8" = 1'-0"10/25/2021 11:31:41 AMSYMBOLS &ABBREVIATIONSJLS
JLS
10/25/2021
E001
ELECTRICAL SHEET INDEX
SHEET No. SHEET NAME REV No. REV DATE
E001 SYMBOLS & ABBREVIATIONS 1 10/25/2021
E002 PHOTOMETRIC PLAN 1 10/25/2021
E101 ELECTRICAL SITE PLAN 1 10/25/2021
E201 LEVEL 1 ELECTRICAL PLANS 1 10/25/2021
E202 LEVEL 2 ELECTRICAL PLANS 1 10/25/2021
E203 LEVEL 3 ELECTRICAL PLANS 1 10/25/2021
E204 LEVEL 4 ELECTRICAL PLANS 1 10/25/2021
E205 ROOF LEVEL ELECTRICAL PLANS 1 10/25/2021
E401 ENLARGED PLANS 1 10/25/2021
E501 ONE-LINE DIAGRAM 1 10/25/2021
E601 SCHEDULES 1 10/25/2021
E701 DETAILS 1 10/25/2021
No. Description Date
1 ISSUE
FOR
PERMIT
10/25/
2021