HomeMy WebLinkAboutE101 - Electrical Site Plan1746 sfUnit B31431 sfUnit B21431 sfUnit B2Mail/Package1917 sfUnit C11297 sfUnit B12065 sfUnit C2TrashH
H
V
H
H
RRRRRRRRRRR
V
26 27
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6 5 4 3 2 1
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44 45 46 47 48
STOPLONG-TERM
BYCYCLE
PARKING
(MINIMUM
48 BIKES)
WALL MOUNT
ELECT.
TRASH
CARMEL STREET DEPT
AND STORAGE
-1'-6" AFF
CONDO
ACCESS
ELEC.
DOG WASH
PUBLIC
PARKING
ENTRY
RESIDENTIAL
PARKING
ENTRY
STOR.RISER
STORAGE
UNDER
STAIRS
24'-0" SPEED
GATE
DECORATIVE SEE
THROUGH FENCING TO
MATCH SPEED GATE
BIKE
STACK
RACK
RAMP
UP
GEN.
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
DATA
RAMP
DOWN
UP
SARIS PUMP
STOR.
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
EV (R.I.) FOR TWO (2)
SPACES, TYPICAL
EMERGENCY CALL
BUTTON
NO PARKING
NO PARKING
NO PARKING
NO CURB AT HATCHED
AREA, TYPICAL
8'-0" ROLL-UP
DOOR
RAMP
UP
RAMP
UP
UP
10'
16'
9'11'
11'
11'
11'
11'
11'
11'
11'
11'
10'
18'
15'
15'
15'
15'
15'
15'
18'
12'
12'
10'
11'
12'
12'
9'
13'x15'
13'x15'
13'x15'
9'11'13'26'x10'15'x13'ELECTRIC TRANSFORMER
BY DUKE ENERGY. CONTRACTOR TO PROVIDE PAD PER
DUKE STANDARDS.
53 LF OF
SECONDARY
ELECTRIC LINE.
BOX.
FIBER /
COMMUNICATIONS
SERVICE FOR GARAGE.FOOSOSOS OS OS
HV1
HV-2A
HV-2B
GEN-HV1
T-OP1
HV-OP1
ATS-OP1
ATS-EM1
HV-EM1
T-EM1
LV-EM1
01
02
03
03
LV-OP1
CONTACT:
PHONE:
EMAIL:
Gabe Gibson
+1(765) 827-2212
Gabe.Gibson@duke-energy.com
SHEET NO.
DATE
SCALE
CHECKED BY
DRAWN BY
CERTIFIED BY
CIVIC SQUARE PARKING GARAGE50 Red Truck Rd, Carmel, IN 46032TITLEAs indicated
10/25/2021 11:31:45 AMELECTRICAL SITE PLANJLS
JLS
10/25/2021
E101
1/16" = 1'-0"1 ELECTRICAL SITE PLAN
E101 - KEYED NOTES
01 LOCATION TBD. UTILITY CT AND METERING CABINET. PROVIDE
TRANSFORMER PAD PER DUKE ENERGY STANDARDS CONTACT DUKE
ENERGY, GABE GIBSON AT (765) 827-2212 TO VERIFY REQUIREMENTS.
02 (2) 4"C FROM HANDHOLD TO INSIDE BUILDING STAIRWELL WALL, CONVERT
TO (2) 2"C AND TAKE THEM TO THE SECOND LEVEL MDF ROOM.
03 (2) 1"C TO SIGN. (1) DATA, AND (1) POWER. EC TO COORDINTE WITH GC FOR
EXACT LOCATION AND TERMINATION DETAILS.
SITE - GENERAL NOTES
A EC IS RESPONSIBLE FOR AN ON-SITE COORDINATION MEETING WITH THE
UTILITY COMPANY'S PROJECT MANAGER TO DISCUSS ROUTING AND SCOPE
OF WORK, PRIOR TO INSTALLATION AND / OR THE PURCHASE OF ANY
MATERIALS RELATED TO THE ELECTRICAL SERVICE. ANY ROUTING SHOWN
IS DIAGRAMMATIC IN NATURE, AND THE UTILITY COMPANY SHALL HAVE THE
FINAL AUTHORITY IN DETERMINING ROUTING.
B EC IS RESPONSIBLE FOR COMPLYING WITH THE UTILITY COMPANY'S
REQUIREMENTS FOR MEANS, METHODS, AND MATERIALS RELATING TO THE
PRIMARY AND SECONDARY CONDUITS, METERING, AND OTHER ITEMS
WHICH THE UTILITY COMPANY HAS JURISDICTION OVER.
C INSTALL (1) 1" C. TO EACH PIV LOCATION FROM THE BUILDING, WITH PULL
STRING. FIELD COORDINATE FINAL LOCATION(S).
N
No. Description Date
1 ISSUE
FOR
PERMIT
10/25/
2021