HomeMy WebLinkAboutES001 - ELECTRICAL SITE PLANS24
26
15
07
15 03
28
10
EXISTING BUILDING
19,960 SQ.FT.
PROPOSED BUILDING
EXPANSION
F.F.E. = 843.09
MFPG = 843.70
MLAG = 843.70
12,058 SQ.FT.
TOTAL PARKING = 128
30
M.P.H
CITY CENTER
DRIVE
CENTERLINEHANCOCK STREET(50' PUBLICRIGHT-OF-WAY)CITY CENTER DRIVE
(A.K.A 122ND
STREET)(PUBLIC
RIGHT-OF-WAY)
ADJOINER
CITY OF
CARMELINSTR.
#200200043828
POND
CONCRETE
WALK
EDGE OF
WATER
GRASS
GRASSGRASS
ASPHALTASPHALT
ASPHALT
CONCRETEWALKWOOD
DECK
CONCRETEROLLED
CURBS
CHAIRBACK
CURB
COLUMN
CANOPY
EDGE OF
ASPHALT
14.63'10'20'EXISTING
MASONRY
BLOCK
BUILDING
(CARMEL
TOTAL
FITNESS)
10096
842.19
INS
AC
AC
10124
845.30
ACU
AC
10125
845.13
ACU
G
10126
845.23
GMT
6"
G
F.F.E. =
843.09
FO
10208
841.38
FPB
E
10240
842.86
EMT
E
10241
EBX
T
10242
842.87
TPD
10243
842.79
SCO
10251
841.06
INS
10252
841.58
INS
10254
840.34
INS
BLDG. HT. =
27'±
S
10282
841.40
SMH
T
10283
842.12
TMH
T
10311
841.81
TPDC
10317
842.30
CPD
C
10335
843.37
CPD
STREET
SIGN
10408
841.61
HCP
10409
841.66
HCP
10416
841.81
HCP
10417
841.77
HCP
10438
841.65
CIN
FO
25045
841.22
FMH25049
840.65
CIN
25058
841.00
CIN
25072
841.46
CIN
FO
25086
842.69
FMH
25117
842.04
CIN
25130
841.81
CIN
D
25144
842.18
DMH
D
25145
842.37
DMH
S
25146
843.27
SMH25147
842.57
CIN
25148
841.99
CIN
T
25295
843.37
TPB
W
25302
844.84
WMT
W
25303
844.78
WMT
T
25312
843.78
TPB
WV
DYH HYD
W
25319
843.83
WMT
15" RCP
INV.= 832.39
54" RCP
INV.= 831.98
ET843 C
C C
D
10281
841.14
DMH
D
10280
841.68
DMH
G
EXISTING UTILITY
TRANSFORMER
TO REMAIN
EXISTING UTILITY
SECTIONALIZING
CABINET
NEW 1600A, 208/120V,3-PH
UTILITY CT CABINET TO
REPLACE EXISTING.
1600A, 208/120V, 3-PH, 4-WIRE,
NEMA 3R, I-LINE DISTRIBUTION
PANELBOARD "DP".
EXISTING UNDERGROUND
SECONDARY TO EXISTING
BUILDING TO REMAIN
DP M
UTILITY METER
S
S
S
S
S
S
U2
U3U1
U1
U3
U2
U2
U3
U1
Z1Z1
Z1Z1
L8L8
-31L2
L7
S
PROVIDED NEW POLE AND FIXTURE.
MATCH EXISTING POLES AND FIXTURES
ON SITE.
Z1
L8
Z1
Z1
Z1
Z1
Project No. 1131-01
05/19/2021CARMEL HEALTH &WELLNESS COMPLEX820 City Center DriveCarmel. Indiana 46032ES001
CONSTRUCTION
DOCUMENTSELECTRICAL SITE UTILITIESPLANGENERAL NOTES (SITE):
A. DO NOT SCALE FROM MECHANICAL AND ELECTRICAL DRAWINGS. FIELD
VERIFY REQUIRED DIMENSIONS AND COORDINATE WITH CIVIL
DRAWINGS AND SURVEYS.
B. REFER ALSO TO ALL OTHER PLANS AND THE SPECIFICATION, BUT
ESPECIALLY TO: THE SITE SURVEY, THE ARCHITECTURAL SITE PLAN,
THE SITE GRADING PLAN, THE PLANTING PLAN (WHERE AVAILABLE),
FOUNDATION PLAN(S), APPROPRIATE MECHANICAL & ELECTRICAL
FLOOR PLANS FOR SERVICE CONTINUATIONS, THE SITE UTILITY PLAN -
MECHANICAL & ELECTRICAL. WHERE THERE ARE CONFLICTS AMONG
THESE PLANS AND/OR RELATED SPECIFICATIONS, ADVISE THESE
ENGINEERS AT LEAST TEN DAYS PRIOR TO SUBMISSION OF BIDS.
C. ALL FEES AND ANY OTHER COSTS TO UTILITY COMPANIES,
MUNICIPALITIES, INSPECTORS, REVIEWING AGENCIES, ETC. ARE TO BE
INCLUDED AS A PART OF THIS CONTRACT.
D. FEDERAL, STATE, LOCAL, MUNICIPALITY AND UTILITY COMPANY CODES,
RULES, REGULATIONS AND REQUIREMENTS APPLY UNLESS EXCEEDED
BY THIS DESIGN.
E. WHEN INTERRUPTION OF AN EXISTING UTILITY OR SERVICE IS PLANNED
OR OCCURS ACCIDENTALLY, THE CONTRACTOR(S) SHALL WORK
CONTINUOUSLY AS NEEDED TO RESTORE SAME PROVIDING PREMIUM
TIME AS NEEDED AT NO INCREASE IN THE CONTRACT PRICE.
F. LOCATIONS, DEPTHS, MATERIAL TYPES, ELEVATIONS, ETC. OF ALL
APPURTENANCES, LINES, BUILDINGS, ETC. INDICATED ON THESE
DRAWINGS WERE TAKEN FROM VARIOUS SOURCES, ARE
DIAGRAMMATIC ONLY AND ARE SUBJECT TO SUBSTANTIAL VARIATION
FROM EXISTING CONDITIONS, EXISTING UTILITIES LOCATIONS MAY
VARY. CONSEQUENTLY ALL CONTRACTORS SHALL EXERCISE EXTREME
CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY
DO NOT INTERRUPT ANY EXISTING SERVICE. FOR SAFETY PURPOSES,
PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO
NATURAL GAS AND ELECTRICAL LINES. ALL WORK SHALL BE
PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE, AND/OR
LOCAL RULES, REGULATIONS, STANDARDS AND SAFETY
REQUIREMENTS.
G. PROVIDE LONG RADIUS ELBOWS FOR UNDERGROUND CONDUIT BENDS.
WHERE SERVING A UTILITY OWNED TRANSFORMER, THE UTILTY
STANDARDS SHALL TAKE PRECEDENCE.
H. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE
MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE
MOST STRINGENT REQUIREMENT SHALL APPLY. IF ANY VARIATION
OCCURS, CONSULT THE ENGINEER. CONTRACTOR SHALL VISIT THE
SITE AND FIELD VERIFY THE ROUTING OF ALL UTILITIES NEW AND
EXISTING PRIOR TO SUBMISSION OF BIDS. SUBMISSION OF A BID
PROPOSAL INDICATES THAT THE CONTRACTOR IS FULLY AWARE OF ALL
OBSTRUCTIONS AND WILL INSTALL ALL OF THE NEW UTILITIES WITHOUT
REQUESTS FOR ANY ADDITIONAL CHANGES.
I. PROVIDE GALVANIZED RIGID CONDUIT FOR EXTERIOR UNDERGROUND
TRANSITIONS TO ABOVE GRADE; EXTEND CONDUIT A MINIMUM OF 6”
ABOVE GRADE.
J. CONTRACTOR SHALL PERFORM A SMOKE TEST ON ALL CONDUITS
INSTALLED ON SITE AND SHALL TAKE ALL NECESSARY CORRECTIVE
ACTION IF NOT FOUND IN COMPLIANCE WITH FACILITY STANDARDS.
K. CONTRACTOR SHALL CONTACT ENGINEER FOR INSPECTION OF
TRENCHES PRIOR TO INSTALLATION OF CONDUITS OR RACEWAYS.
PROVIDE PHOTOS UPON REQUEST.
L. CONTRACTOR SHALL CUT AND PATCH ALL PAVEMENT, CURBING, ETC.
AS REQUIRED FOR WORK. CONTRACTOR SHALL REPAIR ALL
LANDSCAPING THAT IS DAMAGED FOR WORK. FINISH GRADE, SEED AND
STRAW ALL DISTURBED GREEN SPACES. ALL PATCH AND REPAIR WORK
SHALL BE IN ACCORDANCE WITH BOTH CIVIL AND LANDSCAPE
DRAWINGS AND SPECIFICATIONS.
SCALE: 1" = 20'-0"
ELECTRICAL SITE UTILITIES PLAN1
TAGGED NOTES
L7 ROUTE EXTERIOR LIGHTING BRANCH CIRCUIT THROUGH LIGHTING
CONTACTOR PANEL. REFER TO SHEET E503 DETAIL "EXTERIOR LIGHTING
CONTROL DIAGRAM" FOR REQUIREMENTS.
L8 EXSITING WALL PACK LIGHT FIXTURES IN THIS LOCATION TO BE
REMOVED AND REPLACED WITH NEW. CONTRACTOR TO RECONNECT
NEW FIXTURE TO EXISTING CIRCUIT.
U1 EXISTING POLE MOUNTED FIXTURE TO REMAIN.
U2 EXISTING POLE MOUNTED FIXTURE TO BE RELOCATED. POLE BASE TO
BE DEMOLISHED AND EXISTING CONDUIT AND CABLE TO BE EXTENDED
TO NEW LOCATION.
U3 RELOCATED POLE MOUNTED FIXTURE. PROVIDE NEW POLE BASE AND
EXTEND EXISTING CONDUIT AND CABLE TO NEW LOCATION.