HomeMy WebLinkAboutGN010.1G002
CODE SUMMARY +
LIFE SAFETY PLAN
LIFE SAFETY PLAN
SCALE: 3/16" = 1'-0"1N
PROJECT NUMBER:2021-049CARMEL, IN 4603310.27.2021
CERTIFICATION:SITE ARCHITECTUREarchitecture + landscape architectureDATE ISSUED:
REVISIONS ISSUED:ATI PHYSICAL THERAPY4765 EAST 126TH STREETARCHITECT:
SITE ARCHITECTURE
architecture + landscape architecture
BRAD SMITH, RA | LEED AP
13144 EAST 186TH STREET
NOBLESVILLE, IN. 46060
PH: 317.374.8720
E-MAIL: brad@site-architecture.com
PROJECT CONTACT:TENANT IMPROVEMENTThese drawings are intended for the purposes
State of Indiana/City of Carmel plan review,
permitting, bidding, and construction.
CONSTRUCTION DOCUMENTS
MEP ENGINEER:
PHIL HIX
2707 RAND ROAD
INDIANAPOLIS, IN. 46241
317.281.6342
phix@daengineering.com
PROJECT CONTACT:
DESIGN-AIRE
ENGINEERING, INC.
EXIT
OPEN
TREATMENT
AREA
101TREATMENT
103
CORR.
102
RR
105
LAUNDRY /
MECH.
104
SEMI-RECESSED FIRE EXTINGUISHER
CABINET AND FIRE EXTINGUISHER.
F
BUILDING INFO/CODE SUMMARY
PROJECT SCOPE INFORMATION
BUILDING AREA
CONSTRUCTION TYPE
OCCUPANCY
IIB - FULLY SPRINKLERED
OCCUPANT LOAD
EGRESS
-InIBC 2014 - TABLE 1015.1
B OCCUPANCY
22 PEOPLE < 49
-ONLY 1 EXIT REQUIRED - COMPLIES
-InIBC 2014 - 1007.1 ACCESSIBLE MEANS
OF EGRESS
1 ACCESSIBLE MEANS OF EGRESS
REQUIRED - 1 PROVIDED - COMPLIES
-InIBC 2014 - 1016.2 TRAVEL DISTANCE
B OCCUPANCY WITH SPRINKER
= 300'
-MAX TRAVEL DISTANCE =
125' < 300' - COMPLIES
PLUMBING FIXTURES
-InIBC 2014 - 2902.1 - NUMBER OF
FIXTURES
- B OCCUPANCY
-WATER CLOSETS =
1 PER 25 FOR FIRST 50
(MALE AND FEMALE COMBINED)
OCCUPANCY = 22 / 2
11 MALE < 25 - 1 REQUIRED
-1 PROVIDED - COMPLIES
11 FEMALE < 25 - 1 REQUIRED
-1 PROVIDED - COMPLIES
-LAVATORIES = 1 PER 40 FOR THE
FIRST 80 REQUIRED
11 MALE - 1 PROVIDED - COMPLIES
22 FEMALE - 1 PROVIDED -
COMPLIES
InIBC 2014 2902.2
OCCUPANT LOAD = 22 > 15
SEPARATE MALE/FEMALE FACILITIES
REQUIRED - 2 PROVIDED - COMPLIES
-DRINKING FOUNTAINS =
1 PER 100 REQUIRED
-22 < 100 - 1 REQUIRED
-2 PROVIDED - COMPLIES
-SERVICE SINK =
1 REQUIRED, 1 PROVIDED
-COMPLIES
FIRE PROTECTION
-SPRINKLER SYSTEM
-BUILDING IS FULLY SPRINKLERED
-FIRE ALARM
-PER InIBC 2014 - 907.2.2 - GROUP B
-NO REQUIREMENTS APPLY TO THIS
PROJECT.
-NO FIRE ALARM REQUIRED.
TOTAL OCCUPANT LOAD = 22 PEOPLE FIRE EXTINGUISHER NOTE:
CONFIRM LOCATION OF FIRE EXTINGUISHERS
WITH ARCHITECT AND CARMEL FIRE DEPT.
EXTINGUISHERS TO BE MINIMUM 5 POUND ABC
RATED EXTINGUISHERS - WALL MOUNTED NOT
HIGHER THAN 5 FEET FROM THE FLOOR TO THE
TOP OF THE UNIT. EXTINGUISHERS SHALL BE
SERVICED ANNUALLY BY A FIRE EXTINGUISHER
COMPANY.
-OVERALL BUILDING AREA =43,599 S.F.
B OCCUPANCY
-PROFESSIONAL SERVICES - PHYSICAL THERAPY
BUSINESS AREA = 2,091 S.F.
LIFE SAFETY KEY
EXIT PATH
CEILING MOUNTED SMOKE DETECTORS
(GENERAL LOCATION IS INDICATED -
CONTRACTOR VERIFY SPECIFIC
LOCATION WITH ARCHITECT PRIOR TO
INSTALLATION)
THIS PROJECT SCOPE INCLUDES INTERIOR DEMISING AND
TENANT FINISH WORK WITHIN AN EXISTING BUILDING.
-TENANT FINISH
PROJECT SCOPE AREA =2,527 S.F.
2,091 S.F. / 100 S.F. GROSS =
20.91 = 21 PEOPLE
MECHANICAL / UTILITY AREA = 200 S.F.
200 S.F. / 300 S.F. GROSS =
0.67 = 1 PERSON
SEPARATION OF OCCUPANCIES
-InIBC 2014 - TABLE 508.4
PROJECT SCOPE AREA =
B OCCUPANCY SPRINKLERED
EXISTING ADJACENT TENANT WEST =
M OCCUPANCY SPRINKLERED
-NO RATED SEPARATION REQUIRED
PROJECT SCOPE AREA =
B OCCUPANCY SPRINKLERED
PROPOSED ADJACENT TENANT EAST=
A-2 OCCUPANCY SPRINKLERED
-1 HOUR RATED SEPARATE REQUIRED
-1 HOUR DEMISING WALL PROVIDED
-COMPLIES
LONGEST PATH OF EGRESS = +/-125'
RR
106
F
FS
S
S
ADJACENT EXISTING TENANT
HATCHED AREA NOT
IN PROJECT SCOPE
M OCCUPANCY
(GROCERY STORE)
ADJACENT PROPOSED TENANT
HATCHED AREA NOT
IN PROJECT SCOPE
A-2 OCCUPANCY
(RESTAURANT)
112'-5 1/2"21'-7 1/2"112'-5 1/2"23'-3"1 HOUR FIRE RATED WALL
1 HOUR RATED DEMISING WALL
1 HOUR RATED DEMISING WALL