HomeMy WebLinkAboutGN010.1SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US
OUTPUT
Rated AC Power Output 3000 3800 @ 240V
3300 @ 208V 5000 6000 @ 240V
5000 @ 208V 7600 10000 11400 @ 240V
10000 @ 208V VA
Maximum AC Power Output 3000 3800 @ 240V
3300 @ 208V 5000 6000 @ 240V
5000 @ 208V 7600 10000 11400 @ 240V
10000 @ 208V VA
AC Output Voltage Min.-Nom.-Max.
(211 - 240 - 264)9 9 9 9 9 9 9 Vac
AC Output Voltage Min.-Nom.-Max.
(183 - 208 - 229)- 9 - 9 - - 9 Vac
AC Frequency (Nominal) 59.3 - 60 - 60.5(1) Hz
Maximum Continuous Output
Current @240V 12.5 16 21 25 32 42 47.5 A
Maximum Continuous Output
Current @208V - 16 - 24 - - 48.5 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection,
Country Configurable Thresholds Yes
INPUT
Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 W
Maximum DC Power @208V - 5100 - 7750 - - 15500 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage 480 Vdc
Nominal DC Input Voltage 380 400 Vdc
Maximum Input Current @240V(2) 8.5 10.5 13.5 16.5 20 27 30.5 Adc
Maximum Input Current @208V(2) - 9 - 13.5 - - 27 Adc
Max. Input Short Circuit Current 45 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 600k Sensitivity
Maximum Inverter Efficiency 99 99.2 %
CEC Weighted Efficiency 99 99 @ 240V
98.5 @ 208V %
Nighttime Power Consumption < 2.5 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional)
Revenue Grade Data, ANSI C12.20 Optional(3)
Rapid Shutdown - NEC 2014 and
2017 690.12 Automatic Rapid Shutdown upon AC Grid Disconnect
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC Part 15 Class B
INSTALLATION SPECIFICATIONS
AC Output Conduit Size / AWG Range 1" Maximum / 14-6 AWG 1" Maximum /14-4 AWG
DC Input Conduit Size / # of Strings /
AWG Range 1" Maximum / 1-2 strings / 14-6 AWG 1" Maximum / 1-3 strings / 14-6 AWG
Dimensions with Safety Switch
(HxWxD) 17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185 in /
mm
Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 lb / kg
Noise < 25 <50 dBA
Cooling Natural Convection
Operating Temperature Range -13 to +140 / -25 to +60(4) (-40˚F / -40˚C option)(5) ˚F / ˚C
Protection Rating NEMA 4X (Inverter with Safety Switch)
(1) For other regional settings please contact SolarEdge support
(2) A higher current source may be used; the inverter will limit its input current to the values stated
(3) Revenue grade inverter P/N: SExxxxH-US000NNC2
(4) For power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf
(5) -40 version P/N: SExxxxH-US000NNU4
Single Phase Inverter
with HD-Wave Technology for North America
SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/
SE7600H-US / SE10000H-US / SE11400H-US
12/01/21