HomeMy WebLinkAboutE-401 - ELECTRICAL RISER DIAGRAMUTILITY TRANSFORMER 120/208V, 3 PH, 4WWYE SECONDARYPRIMARY CABLESBY LOCAL UTILITYCOMPANY1200A1200A3PMETER CENTERMC-RES-A120/208V, 3 PH, 4 WIRE1200A RATED ASSEMBLY WITH 800A FUSE,(62) 120/208V, SINGLE PHASE, 3 WIRE WITH 5THJAW AND MAIN CIRCUIT BREAKER.1200A-3PHBUS313233342627282921222324150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P#3/0 CUMMMMMMMMMMMM150A-2P150A-2P150A-2PM M M16171819150A-2P150A-2P150A-2PMMMM20150A-2PM11121314150A-2P150A-2P150A-2PMMMM15150A-2PM6789150A-2P150A-2P150A-2PMMMM10150A-2PM1234150A-2P150A-2P150A-2PMMMM5150A-2PM150A-2P150A-2P150A-2P150A-2P253035NORTH WALL OF AREA B. 1ST FLOOR1200A1200A3PMETER CENTERMC-RES-B120/208V, 3 PH, 4 WIRE1200A MAIN FUSIBLE SWITCH,(14) 120/208V, SINGLE PHASE, 3 WIRE WITH 5THJAW AND MAIN CIRCUIT BREAKER.1200A-3PHBUSHOUSE-B565758595152535446474849800A-3P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P150A-2P#3/0 CUMMMMMMMMMMMMM150A-2P150A-2PM M50556063646566150A-2P150A-2P150A-2P150A-2PMMMM1200A1200A3PMETER CENTERMC-COMMERCIAL120/208V, 3 PH, 4 WIRE1200A MAIN FUSIBLE SWITCH,(4) 208V, THRE PHASE, 4 WIRE WITH 5THJAW AND MAIN CIRCUIT BREAKER.1200A-3PHBUSTENANT-1200A-3P#3/0 CUM150A-2PM6768697071150A-2P150A-2P150A-2P150A-2PMMMM150A-2PM72NORTH WALL OF AREA B. 1ST FLOORNORTH WALL OF AREA B. 1ST FLOOR200A-3PMTENANT-2TENANT-3400A-3PM400A-3PMHOUSE-A(1) 208V, THREE PHASE, 4 WIRE WITH 5TH6162150A-2P150A-2P150A-2P150A-2PMMMM150A-2PMPANELH1120/2083P, 4W200AMLOPANELH2120/2083P, 4W200AMLOPANELEM120/2083P, 4W200AMLOENLTRANSFERSWITCHGGENERATORTRANSFER SWITCH NOTESTRANSFER SWITCH TYPE: AUTOMATICCURRENT RATING: 225ARATED VOLTAGE: 120/208V3-PHASE/ 4WIRE# OF POLES: 4NEUTRAL CONFIGURATION:SWITCHEDIN-SYNC TRANSFER:YMAIN CIRCUIT BREAKER: N GROUND FAULT ON MAIN: NSERVICE ENTRANCE RATED: NREMOTE ANNUNCIATION: NBY-PASS/ISOLATION: N NEC LOAD BRANCH: 701 KAIC:42SEE SPECIFICATIONS FOR ADDITIONAL FEATURESNEMA RATING: 1 CYCLE RATING: 3PANELHDP-B120/2083P, 4W800AMLOGROUNDFLOORGROUNDFLOORDRIVE TRHOUGH AREAHOUSE ELECTRICAL ROOMHOUSE ELECTRICAL ROOMDRIVE TRHOUGH AREADRIVE TRHOUGH AREADRIVE TRHOUGH AREAUTILITY TRANSFORMER AREAUTILITY TRANSFORMER AREAHOUSE ELECTRICAL ROOMHOUSE ELECTRICAL ROOMEXISTING GENERATOR ROOM IN ADJACENT BUILDING19191917111010PANELT1120/2083P, 4W200AMLOPANELT2120/2083P, 4W200AMLO1010200AF200ATENLTRANSFERSWITCHEXISTINGEXISTINGSWBDTO UTILITY SOURCEEXISTINGEXISTING GENERATOR ROOM IN ADJACENT BUILDINGPANELEL-A480/2773P, 4W100AMCB45KVA TRANSFORMER 208V DELTA PRIMARY 480/277V WYE SECONDARY6610ELEVATOR #1ELEVATOR #4ELEVATOR #5666ELEVATOR #2ELEVATOR #34150A-2P150A-2P150A-2P150A-2PMMMM150A-2PM150A-2P150A-2P150A-2P150A-2PMMMM150A-2PM150A-2P150A-2PMM11PANELEL-B480/2773P, 4W100AMCBELEVATOR #6ELEVATOR #724266PANELHDP-A120/2083P, 4W400AMLO143637383940414243444573747576TENANT-4400A-3PM45KVA TRANSFORMER 208V DELTA PRIMARY 480/277V WYE SECONDARYINSTALL NEW CIRCUIT BREAKERIN EXISTING SWBD200AS200AFFEEDER SCHEDULECOPPER FEEDERS AND COPPER GROUNDALUMINUM FEEDERS AND COPPER GROUNDFEEDER1CONDUCTORAMPACITY75a Cu COPPER WIREGROUNDCONDUCTORPER CONDUITCOPPER WIRE3 WIRE PLUSGROUND4 WIRE PLUSGROUND3 WIRE W/150% NEUTRAL4 WIRE W/200%NEUTRALMINIMUM CONDUIT SIZEFEEDERCONDUCTORAMPACITY75a Cu COPPER WIREGROUNDCONDUCTORPER CONDUITCOPPER WIRE3 WIRE PLUSGROUND4 WIRE PLUSGROUND3 WIRE W/150% NEUTRAL4 WIRE W/200%NEUTRALMINIMUM CONDUIT SIZE20A#12#123/4"3/4"3/4"--------230A--------350A--------460A--------570A, 80A--------6100A--------7125A-8150A-1234569175A-10200A-11225A-12300A-13350A-14400A-15500A-16600A-17800A-181000A-191200A-201600A-212000A-222500A-233000A-24NOTE:1. WIRING SHALL BE PROVIDED IN ACCORDANCE WITH NEC, UNLESS LARGER SIZES ARE SHOWN TO ACCOMMODATE FUTURE LOADS OR VOLTAGE DROP.2. FEEDERS ARE 4 WIRE UNLESS NOTED OTHERWISE.3. GROUND CONDUCTORS REQUIRED IN ALL FEEDER CONDUITS.#103/4"3/4"3/4"#101"#101"1"#81"#10#61 1/4"1 1/4"#41 1/4"1 1/4"1 1/4"#8#31 1/2"1 1/4"#81 1/2"#12"#61 1/2"2"#1/02"#62"2 1/2"#2/02"#62"2 1/2"#3/0#62"2 1/2"2 1/2"#4/0#43"2 1/2"2 1/2"350 KCMIL#43 1/2"3"3"500 KCMIL#33"3"3 1/2"500 KCMIL#33"3"3 1/2"(2) 250 KCMIL#2(2) 2 1/2"-(2) 2 1/2"(2) 350 KCMIL#1(2) 3"-(2) 3"(2) 500 KCMIL#1/0(2) 3"-(2) 4"(3) 500 KCMIL#2/0-(3) 3 1/2"(3) 3 1/2"(3) 600 KCMIL#3/0-(3) 4"(3) 4"(4) 600 KCMIL250 KCMIL-(4) 5"(4) 4"(5) 600 KCMIL250 KCMIL-(5) 4"(5) 4"(6) 600 KCMIL350 KCMIL-(6) 4"(6) 4"(8) 600 KCMIL400 KCMIL-(8) 4"(8) 4"7125A-8150A-9175A-10200A-11225A-12300A-13350A-14400A-15500A-16600A-17800A-181000A-191200A-201600A-212000A-222500A-233000A-242"#61 1/2"2"2"#62"2 1/2"#62 1/2"#62"2 1/2"2 1/2"#43"2 1/2"2 1/2"500 KCMIL#43 1/2"3"3"(2) #4/0#3#3(2) 250 KCMIL#2(2) 2 1/2"-(2) 2 1/2"#1(2) 3"-(2) 3"(2) 500 KCMIL#1/0-(4) 350 KCMIL#2/0-(4) 2 1/2"(4) 2 1/2"(4) 500 KCMIL#3/0-(4) 3"(5) 600 KCMIL-(6) 600 KCMIL250 KCMIL-(5) 4"(5) 4"(8) 600 KCMIL350 KCMIL-(6) 4"(6) 4"(9) 600 KCMIL350 KCMIL-(8) 4"(8) 4"#2/0#3/0#4/02 1/2"2 1/2"250 KCMIL300 KCMIL(2) 2 1/2"(2) 2 1/2"(2) 2 1/2"(2) 3 1/2"(2) 3"(2) 3 1/2"(2) 350 KCMIL(3) 400 KCMIL(3) 2 1/2"(3) 2 1/2"(4) 3"#4/0(9) 4"(9) 4"APARTMENT UNIT 125 AMP PANEL FEEDER CONDUCTOR SIZESALUMINUM CONDUCTOR SIZECONDUCTOR RATING (75° C)ALUMINUM GROUNDING CONDUCTORMAXIMUM CONDUCTOR LENGTHNOTES#3/0 AL155#2 AL1801,2#4/0 AL185#2 AL1201,2#250KCM AL205#1 AL252#300KCM AL230#1/0 AL289#350KCM AL250#2/0 AL324#400KCM AL270#2/0 AL353#500KCM AL310#3/0 AL4141,21,21,21,21,2NOTES:1. THE VOLTAGE DROP OF CONDUCTORS HAS BEEN ACCOUNTED FOR IN THIS TABLE2.DWELLING UNIT PANEL FEEDERS SHALL BE SIZED AS NOTED IN THE TABLE ABOVE. FOR FEEDERS THAT EXCEED 414 FEET. THE CONTRACTOR SHALL PROVIDE CIRCLE DESIGN GROUP WITH THE PROPOSED LENGTHS OF FEEDERS TO PROPERLY CALCUALTE THE CONDUCTOR SIZES. #2/0 AL135#4 AL1531,219030Project:Developer:Sheet Number:Engineer:By:Sheet Title:CDG Number:Last Revision Date:Set Issue DateDrawn ByChecked BySheet Issue DateWREN BUILDINGCarmel, IN 46032CONSTRUCTION DOCUMENTS750 Veterans WayNOT FOR CONSTRUCTIONE-401ELECTRICAL RISERDIAGRAM11/24/2111/24/21NOT TO SCALEELECTRICAL RISER DIAGRAM111/24/2111/24/21 BUILDING SHELLBID PHASE III