HomeMy WebLinkAboutE-501 - ELECTRICAL SCHEDULESINTERIOR LIGHTING CONTROL SEQUENCENOTES:1. LIGHTING SHALL COMPLY WITH THE FOLLOWING CODES AND STANDARDS: NATIONAL ELECTRIC CODE (NEC), NATIONAL FIRE PROTECTION AGENCY (NFPA), IES LIGHTING HANDBOOK 10TH EDITION, AMERICAN NATIONAL STANDARDS INSTITUTE(ANSI), INDIANA BUILDING CODE, ASHRAE 90.1-2010.2. EXTERIOR LIGHTING SHALL COMPLY WITH CITY OF CARMEL EXTERIOR LIGHTING STANDARDS.3. BUILDING TO BE OCCUPIED 7 DAYS A WEEK AND ON HOLIDAYS AND WEEKENDS.4. SURFACE REFLECTANCE TO VARY BASED ON SPACE/AREA TYPE.CONTROL DESIGNATIONSPACE/AREA TYPELOCAL CONTROLDIMMING / SWITCHING/SENSORSEMERGENCYNOTESLC1PUBLIC LOBBY/PUBLIC CORRIDOR/ELEVATOR LOBBYLIGHT FIXTURES TO BE SWITCHED VIA PANELBOARD.ARCHITECTURAL FIXTURES TO DIM TO 10%, DECORATIVE FIXTURE DIMMING COORDINATED WITH INDIVIDUAL FIXTURE.NIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR BOTH EGRESS AND EMERGENCY LIGHTING.-STAIRSLIGHT FIXTURES COME TO FULL ON WHEN OCCUPANCY ISDETECTED. WHEN OCCUPANCY HAS NOT BEEN DETECTED FOR15 MINUTES, FIXTURES DIM TO 50%.0-10V DIMMING TO 50%.UPON LOSS OF NORMAL POWEREMERGENCY LIGHT FIXTURES TOCOME TO FULL ON.SHELL TENANT SPACESCEILING MOUNTED OCCUPANCY SENSORMECHANICAL/ELECTRICALLOCAL SNAP SWITCH TURNS LIGHTS ON/OFFNA-PUBLIC RESTROOMSWALL MOUNTED OR CEILING MOUNTED OCCUPANCYSENSORSTORAGE/TRASH/FACILITIESLIGHT FIXTURES COME TO FULL ON WHEN OCCUPANCY ISDETECTED. WHEN OCCUPANCY HAS NOT BEEN DETECTED FOR15 MINUTES FIXTURES TURN OFF.CEILING MOUNTED 360 DEGREE DUAL TECHNOLOGYOCCUPANCY SENSORLC2RESIDENCE LOBBY/RESIDENCE CORRIDOR/ELEVATOR LOBBYLIGHT FIXTURES TO BE SWITCHED VIA PANELBOARD.ARCHITECTURAL FIXTURES TO DIM TO 10%, DECORATIVE FIXTURE DIMMING COORDINATED WITH INDIVIDUAL FIXTURE.-LC3LC4LIGHT FIXTURES COME TO FULL ON WHEN OCCUPANCY ISDETECTED. WHEN OCCUPANCY HAS NOT BEEN DETECTED FOR15 MINUTES FIXTURES TURN OFF.NIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR BOTH EGRESS AND EMERGENCY LIGHTING.-LC4--LC5LIGHT FIXTURES COME TO FULL ON WHEN OCCUPANCY ISDETECTED. WHEN OCCUPANCY HAS NOT BEEN DETECTED FOR15 MINUTES FIXTURES TURN OFF.NIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR BOTH EGRESS AND EMERGENCY LIGHTING.NIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR BOTH EGRESS AND EMERGENCY LIGHTING.LC5NIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR BOTH EGRESS AND EMERGENCY LIGHTING.--EXTERIOR LIGHTING CONTROL SEQUENCENOTES:1. LIGHTING SHALL COMPLY WITH THE FOLLOWING CODES AND STANDARDS: NATIONAL ELECTRIC CODE (NEC), NATIONAL FIRE PROTECTION AGENCY (NFPA), IES LIGHTING HANDBOOK 10TH EDITION, AMERICAN NATIONAL STANDARDS INSTITUTE(ANSI), INDIANA BUILDING CODE, ASHRAE 90.1-2010.2. EXTERIOR LIGHTING SHALL COMPLY WITH CITY OF CARMEL EXTERIOR LIGHTING STANDARDS.3. BUILDING TO BE OCCUPIED 7 DAYS A WEEK AND ON HOLIDAYS AND WEEKENDS.4. SURFACE REFLECTANCE TO VARY BASED ON SPACE/AREA TYPE.CONTROL DESIGNATIONSPACE/AREA TYPELOCAL CONTROLEMERGENCYNOTESEL1DRIVE THRUPHOTOCELL & TIMECLOCKNIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR BOTH EGRESS AND EMERGENCY LIGHTING.-EXTERIOR EGRESSLIGHTINGPHOTOCELL & TIMECLOCKUPON LOSS OF NORMAL POWEREMERGENCY LIGHT FIXTURES TOCOME TO FULL ON.EL2EXTERIOR ACCENT LIGHTINGPHOTOCELL & TIMECLOCK-EL3NIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR BOTH EGRESS AND EMERGENCY LIGHTING.-19030Project:Developer:Sheet Number:Engineer:By:Sheet Title:CDG Number:Last Revision Date:Set Issue DateDrawn ByChecked BySheet Issue DateWREN BUILDINGCarmel, IN 46032CONSTRUCTION DOCUMENTS750 Veterans WayNOT FOR CONSTRUCTIONE-501ELECTRICALSCHEDULES11/24/2111/24/21MOTORIZED EQUIPMENT SCHEDULENAME QUAN FURN. BY HP / KW AMPS VOLT PHASESTARTER DATADISCONNECT SWITCHFEEDERPANEL/CIRCUITBREAKERTYPE NEMC. ENCL CONTROLS BY TYPE NEMA ENCL BYCC-1, CC-2, CC-3 MFGR .04 .2 208 1 TS - WALL MT MF - - - 2#12, #12G, 3/4"C H2/20A-2PCU-1MFGR 2.6 12.3 208 1 CP - - MF FUSED NEMA 3R EC 2#12, #12G, 3/4"C H2/20A-2PCU-2MFGR 3.7 17.8 208 1 CP - - MF FUSED NEMA 3R EC 2#10, #10G, 3/4"C H2/25A-2PCU-3MFGR 3.5 16.8 208 1 CP - - MF FUSED NEMA 3R EC 2#12, #12G, 3/4"C H2/20A-2PDS-1MFGR .05 .4 120 1 CP - - MF FUSED NEMA 1 EC 2#12, #12G, 3/4"C H2/20A-1PDWBP-1 MFGR 2.7 7.6 208 3 CP - - MF FUSED NEMA 3R EC 3#12, #12G, 3/4"C H2/20A-3PDWH-1MFGR 9 25 208 3 CP - - MF FUSED NEMA 1 EC 3#8, #10G, 3/4"C H2/40A-3PDWH-2MFGR 9 25 208 3 CP - - MF FUSED NEMA 1 EC 3#8, #10G, 3/4"C H2/40A-3PDWH-3MFGR 5 24 208 1 CP - - MF FUSED NEMA 1 EC 2#8, #10G, 3/4"C H2/40A-2PEF-1MFGR .24120 1 CP - - MF FUSED NEMA 3R EC 2#12, #12G, 3/4"C H2/20A-1PEF-2MFGR 1.2 9.8 120 1 CP - - MF - - MF 2#12, #12G, 3/4"C H2/20A-1PEF-3MFGR .7 1.23 120 1 CP - - MF - - MF 2#12, #12G, 3/4"C H2/20A-1PEUH-1MFGR 15 41.7 208 3 TS - INTERNAL MF - - MF 3#6, #10G, 3/4"C H2/60A-3PEUH-2MFGR 5 24 208 1 TS - INTERNAL MF - - MF 2#8, #10G, 3/4"C H2/40A-2PEUH-3MFGR 10 48 208 1 TS - INTERNAL MF - - MF 2#6, #10G, 3/4"C H2/60A-2PEUH-4MFGR 3 14.5 208 1 TS - INTERNAL MF - - MF 2#12, #12G, 3/4"C H2/20A-2PEWH-1MFGR 1.5 12.5 120 1 TS - INTERNAL MF - - MF 2#12, #12G, 3/4"C H2/20A-1PFCU-1MFGR 8 39.6 208 1 TS - - MF FUSED NEMA 1 EC 2#8, #10G, 3/4"C H2/40A-2PFCU-2MFGR 10 50.4 208 1 CP - - MF FUSED NEMA 1 EC 2#6, #10G, 3/4"C H2/60A-2PFCU-3MFGR 10 48.8 208 1 CP - - MF FUSED NEMA 1 EC 2#8, #10G, 3/4"C H2/50A-2PHP-CC-1 MFGR 3.7 18 208 1 CP - - MF FUSED NEMA 3R EC 2#10, #10G, 3/4"C H2/25A-2PHP-CC-2 MFGR 3.7 18 208 1 CP - - MF FUSED NEMA 3R EC 2#10, #10G, 3/4"C H2/25A-2PHP-CC-3 MFGR 3.7 18 208 1 CP - - MF FUSED NEMA 3R EC 2#10, #10G, 3/4"C H2/25A-2PHP-DS-1 MFGR 1.8 15 120 1 CP - - MF FUSED NEMA 3R EC 2#12, #12G, 3/4"C H2/20A-1PRTU-1MFGR 23 81 208 3 CP - - MF FUSED NEMA 3R EC 3#4, #8G, 1"C HDP-3PRTU-2MFGR 54 81 208 3 CP - - MF FUSED NEMA 3R EC 3#2/0, #6G, 2"C HDP-3PLIGHTING FIXTURE SCHEDULEFIXTURETYPEBASE MANUFACTURER WATTAGE LAMP TYPE VOLTS MOUNTDESCRIPTIONEMR METALUX: ENC-SA1C-830-U-T4W-BK 33 LED 3000K3300LMUNV WALL ARCHITECTURAL WALL LUMINAIRE (EXTERIOR)K1 METALUX: 4SLSTP4035DD-UNV / 40 LED 3500K4600LMUNV SURFACE /SUSPENDED48" LONG LENSED STRIPLIGHT. LOW PROFILE, WIDE DISTRIBUTION, FROSTEDLENS. ACCESSORIES AS REQUIRED TO MOUNT.K2 MCGRAW-EDISON:IST-AF-600-LED-120-T3-BZ-CWB30 LED 3500K600LM120 SURFACE QUARTER SPHERE CUTOFF WALL PACK. DIE-CAST ALUMINUM HOUSING, WETLOCATION LISTED, EMERGENCY BATTERY BACKUP. (EMERGENCY EGRESS)K4 HALO: HC610D010-61MDH-HM612930 44 LED 3000K3780LM120 FLUSH DECORATIVE FLUSH MOUNT. TRIAC/ELV DIMMER REQUIRED. FINISH TBD BYARCHITECT. (PUBLIC LOBBIES)K5 HALO: SLD612930WH 14.8 LED 3000K1215LM120 SURFACE 6" SURFACE LED DOWNLIGHT (3RD-7TH CORRIDORS)K6 KUZCO BENGAL WS39210-BK 14 LED 3000K1000LM120 SURFACE SURFACE MOUNT LED SCONCE, BLACK FINISH, ELV DIMMER REQUIREDK8-E METALUX:4SWLED-60HL-LW-UNV-EL14W-L835-CD1-SVPD1-U55 LED 3500K1200LMUNV SURFACE 4' WALL MOUNTED LED BRACKET WITH INTEGRAL BATTERY BACKUP ANDHIGH/LOW MOTION SENSOR. FROSTED IMPACE RESISTANT LENS. 0-10V DIMMINGTO 10%. (STAIRS)K9 KICHLER: 9654TZ MAX 10 LED A19 E26BASE120 SURFACE EXTERIOR DECORATIVE WALL SCONE. CLEAR BEVELED DIFFUSER, BRONZEFINISH. LAMPING NOT INCLUDED. E.C. TO PROVIDE LED EQUIVALENT. (EXTERIOR)K10 LIGHTWAY:MANW-1126-LED-A-U-42W-3-Z1-WSA-DIM42 LED 3500K UNV SURFACE EXTERIOR WALL SCONCE TO MATCH PLAYFAIR/HOLLAND. (EXTERIOR)K13-E METALUX:4VT2-LD5-6-DR-UNV-EL10W-L840-CD1-WL-U50 LED 4000K4000LM120 SURFACE 4'-0" FULLY ENCLOSED & GASKETED INDUSTRIAL LUMINAIRE. FROSTED RIBBEDIMPACT RESISTANT ACRYLIC LENS. EMERGENCY BATTERY PACK. (ELEVATORPITS/MACHINE ROOMS)K14 CREE IG: IG-B-NM-5S-4L-35K8-UL-WH-XX,IG-JB-XX33 LED 3500K3800LMUNV SURFACE 15" SQUARE PARKING GARAGE CANOPY FIXTURE TO CLOSELY MATCH EXISTING.E.C. TO CONFIRM MOUNTING CONDITIONS. (CANOPY DRIVEWAY)K16 METALUX: 2SLSTP2035DD-UNV 23 LED 3500K2671LM120 SURFACE/SUSPENDED2' LED LENSED STRIP FIXTURE, DIRECT WIRED, MOTION SENSORED UNLESSNOTED OTHERWISE, MOUNTING PER PLANS. PROVIDE MOUNTING ACCESSORIESAS REQUIRED.K18 METALUX: 4SLSTP2035DD-UNV 45 LED 3500K5000LM120 SURFACE/SUSPENDED4' LED LENSED STRIP FIXTURE, DIRECT WIRED, MOTION SENSORED UNLESSNOTED OTHERWISE, MOUNTING PER PLANS. PROVIDE MOUNTING ACCESSORIESAS REQUIRED. (MECHANICAL/ELECTRICAL CLOSETS)L1 METALUX: FM15WRCCRMETALUX:FM15WRCCR20 LED 3000K1300LM120 SURFACE 15" DIAMETER FLUSH MOUNT FIXTURE. (UNIT LAUNDRY)L2 METALUX:FM15WRCCRMETAULX:FM11WRCCR15 LED 3000K1000LM120 SURFACE 11" DIAMETER FLUSH MOUNT FIXTURE. (UNIT CLOSET)L3/24" BROWNLEE FLOW:5160-24-BL-H20-EC3-30K-100043XX13 LED 3000K1600LM120 SURFACE 24" VANITY SCONCE. CENTER OVER LAVATORY. FINISH TBD BY ARCHITECT. TRIACDIMMING. (UNIT BATHROOM)L3/36" BROWNLEE FLOW:5160-36-BL-H20-EC3-30K-100043XX20 LED 3000K2400LM120 SURFACE 36" VANITY SCONCE. CENTER OVER LAVATORY. FINISH TBD BY ARCHITECT. TRIACDIMMING. (UNIT BATHROOM)L5 ASL LIGHTING: CKM-BLK 9 LED 3500K800LM120 SURFACE EXTERIOR DECORATIVE SCONCE. (UNIT BALCONY)L6 KUZCO LENA: PD21703 9 LED 3000K600LM120 SUSPENDED DECORATIVE PENDANT. BLACK FINISH. ELV DIMMING. (UNIT KITCHEN)L7 BROWNLEE BREEZE:2335-BL-C17-WHL-30K-DTR16 LED 3000K2000LMUNV SURFACE 15" DIAMETER DRUM FLUSH MOUNT WITH BLACK FINISH AND WHITE LINENDIFFUSER. TRIAC DIMMING. (UNIT ENTRY)L8 BROWNLEE FABO:2323-BL/BZ-C23-WHL-30K-DTR23 LED 3000K3000LMUNV SURFACE 15" DIAMETER DRUM SEMI-FLUSH MOUNT WITH BLACK/BRONZE FINISH AND WHITELINEN DIFFUSER. TRIAC DIMMING. (UNIT BEDROOM)L9 METALUX: 2SLSTP2035DD-UNV 23 LED 3500K2671LM120 SURFACE 2' LED FIXTURE, DIRECT WIRED, MOTION SENSORED, MOUNTED ON WALL ABOVEDOOR. (MECHANICAL CLOSETS)L10 KUZCO GUIDE: WS33407-BK 7 LED 3000K500LM120 SURFACE DECORATIVE CORRIDOR WALL SCONCE. BLACK FINISH (UNIT ENTRY)L11 KUZCO ASTON: FM48618 32 LED 3000K2000LM120 SURFACE DECORATIVE FLUSH MOUNT WITH CLEAR/OPAL GLASS FINISH. (APARTMENTCORRIDORS)L12 TECH LIGHTING: 700BCLNG-2-XX-LED930 18 LED 3000K1140LM120 SURFACE DECORATIVE WALL SCONCE, VERTICAL MOUNT. FINISH PER ARCHITECT.(APARTMENT ELEVATORS)L13 LUMENWERX: RIM ROUND 24" 35 LED 3000K3000LM120 SURFACE FINISH TBD BY ARCHITECT/DESIGNER (RESIDENT LOBBIES 3RD-7TH FLOORS)L14 LUMENWERX: RIM ROUND 36" 52 LED 3000K4500LMUNV SURFACE FINISH TBD BY ARCHITECT/ DEISNGER (RESIDENTIAL LOBBIES 1ST-2ND FLOORS)L14-C LUMNEWERX: VIAPD-HLO-FH-LED-80-600-35-5 20 LED 3000K2000LMUNV SURFACE 2" APERTURE LINEAR SURFACE MOUNT, 60" LONG. FINISH PER ARCHITECT.(RESIDENTIAL LOBBY)L15 HALO-REC: SMD4R6930WH 15 LED 3000K1000LM120 SURFACE 4" DIAMETER DOWNLIGHT, SMOOTH TRIM AND 1 HR FIRE RATED JUNCTION BOX.(UNIT GENERAL)L15-B HALO-REC: SMD4R6930WH 15 LED 3000K1000LM120 SURFACE 4" DIAMETER DOWNLIGHT, SMOOTH TRIP AND 1 HR FIRE RATED JUNCTION BOX.WET LOCATION RATED. (SHOWER/TUB AREA) (UNIT GENERAL)L16 OXYGEN 3-111-XX/3-9-110-XX 48 LED 3000K254LM120 SURFACE CEILING FAN WITH LIGHT KIT. FINISH SELECTED BY ARCHITECT ("D" UNITS)X1 SURELITES:APX2 LED UNV SURFACE UNIVERSAL MOUNT THERMOPLASTIC EXIT SIGN WITH SINGLE FACE. ARCHITECTTO SELECT FINISH AND LETTERING COLOR. ARROWS AS INDICATED PERDRAWING. NICAD BATTERY.X2 SURELITES:APX2 LED UNV SURFACE UNIVERSAL MOUNT THERMOPLASTIC EXIT SIGN WITH DOUBLE FACE. ARCHITECTTO SELECT FINISH AND LETTERING COLOR. ARROWS AS INDICATED PERDRAWING. NICAD BATTERY.GENERAL NOTES1. EQUAL MANUFACTURERS TO BE APPROVED AS BIDDER TO PROVIDE PRODUCTS LISTED IN THE BASE MANUFACTURERS COLUMN AS EQUIVALENT TOBASE BID FIXTURE/MANUFACTURER AND MUST BE PROVIDED WITH PERFORMANCE, AESTHETICS, AND FABRICATION QUALITY EQUAL TO OR BETTER THAN BASE BID FIXTURE.2. CONTRACTOR RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE NECESSARY TO OPERATE AND INSTALL FIXTURES IN NORMAL FUNCTION.3. CONTRACTOR TO VERIFY COMPATIBILITY OF CEILING WITH LIGHT FIXTURES AND ADJACENT FINISHES/MATERIALS PRIOR TO SHOP DRAWING SUBMITTAL AND NOTIFY THE ARCHITECT OF ANY ISSUES WITH PROPOSED INSTALLATION.4. ALL ADJUSTABLE EXTEIROR AND INTERIOR LIGHT FIXTURES TO BE TARGETED AND ADJUSTED BY ELECTRICAL CONTRACTOR IN CONJUCTION WITH LIGHTING DESIGNER/OWNER/ARCHITECT. ALL LABOR AND MATERIAL COSTS MADE NECESSARY BY THIS REQUIREMENT SHALL BE INCLUDED AS PART OF BASE BID.11/24/2111/24/21 BUILDING SHELLBID PHASE III