Loading...
HomeMy WebLinkAboutE-602 - ELECTRICAL DETAILSSCALE:SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:04'2'1'SCALE:04'2'1'DISTRIBUTION PANEL, PANELBOARD ANDDISCONNECT SWITCH LABELING DETAILNONE1DISTRIBUTION PANEL, PANELBOARD ANDDISCONNECT SWITCH LABELING DETAILNONE2TYPICAL DUCTBANK DETAILNONE31-1/2" AND SMALLERCONDUIT SUPPORT DETAILNONE42" AND LARGERCONDUIT SUPPORT DETAILNONE5COLUMN GROUNDING DETAILNONE6CONDUIT ROOFPENETRATION DETAILNONE7KEY TO ELECTRICAL CIRCUIT WIRINGNONE8CABLE SLEEVEINSTALLATION DETAILNONE9GROUND MOUNTED LIGHT DETAILNONE10OVERHEAD FEED TOINTERIOR WALL DETAILNONE11CONDUIT STUB UP DETAILNONE12FLOOR SLEEVES FORSE CABLES AT PLAYFAIR BUILDING1/2" = 1'-0"14FLOOR SLEEVES FORSE CABLES AT HOLAND BUILDING1/2" = 1'-0"15FINISHED GRADESUPPORTSTRUCTUREROOFING(BY OTHERS)BUILT-UP ROOF DECK.(BY OTHERS)BUILDING STRUCTURE6"6"12" DIA.30"!FINISHEDFLOORTHREADEDPLUGTHREADEDCOUPLINGCONDUITWARNINGArc Flash HazardAppropriate PPE RequiredEquipmentTypeGroundingWorkDistanceAvailable 3-Ph BoltedCurrentFlash ProtectionBoundaryIncident Energy at 11inchesRiskCategoryEquipmentName:480VSwitchgearGrounded11 inches (300mm)25kA27inches4.39cal/cm22SwitchboardWARNING LABEL FOR ELECTRICALEQUIPMENT SUCH AS MAINSWITCHGEAR AND BRANCHPANELBOARDS.LIGHTING FIXTURECONDUITSEE PLANFOR SIZEFINISHGRADESTANCHIONMOUNTCONCRETEBASECONC. SLAB PER PLANSFINISHED FLOORCLSTEEL COLUMN PER PLANSCLFOOTINGS PER PLANSPRECAST SLEEVESE CABLE(4 PER SLEEVE)4" RGS X16" LONGCONDUITSEAL CONDUITWITH FIRESTOPMATERIAL2ND FLOOR SLABPRECAST SLEEVESE CABLE(4 PER SLEEVE)4" RGS X16" LONGCONDUITSEAL CONDUITWITH FIRESTOPMATERIAL2ND FLOOR SLABLAMACOIDNAMEPLATENOTE: LABELS SHALL BE:NORMAL POWER: BLACK WITH WHITE LETTERSEMERGENCY POWER: RED WITH WHITE LETTERS1/2" HIGHLETTERS1/4" HIGHLETTERS1. SEE ONE LINE DIAGRAM FOR SIZE AND NUMBER OF CONDUITS, AND DUCT BANK ARRANGEMENT.2. PROVIDE 1 REINFORCING BAR PER CONDUIT WHEN EVER A DUCTBANK POUR IS STOPPED MID-RUN.BARS SHALL BE ASTM A-615, GRADE 60.3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS.NOTES:USE SIDE FORMSAS REQUIREDBASE SPACER3000 PSICONCRETEINTERMEDIATESPACERWARNING TAPE7/8" X 4"WOOD BASECONDUIT SUPPORT ANDSPACERS 4'-0" MAXIMUM6" MIN. BETWEENADJACENT COUPLINGS3" MIN3" MIN.24" MIN. U.O.N.3" MIN6"1"3"3" MIN.PLANSECTION A-ASECTION B-BCONDUITBEAM CLAMPBEAM CLAMPCONDUIT CLAMPSCONDUIT CLAMPSCONDUIT CLAMPSSLOTTED CHANNELTO SUPPORT 400%OF CONDUIT WEIGHTDOUBLE NUT TOPAND BOTTOMSLOTTED CHANNELTO SUPPORT 400%OF CONDUIT WEIGHT.BEAM CLAMPTHREADED RODCONDUIT CLAMPS3/4" x 10'-0" COPPERCLAD STEEL GROUND RODBONDING PLATE OREXOTHERMIC WELDTO STEEL COLUMNEXOTHERMIC CONNECTIONTO GROUND RODCLASS II COPERGROUNDINGCONDUCTOR1" PVC CONDUITSLEEVESTEPPED PVC BOOTCONDUITSTAINLESS STEEL CLAMPSSPUN ALUMINUM FLASHINGBASECONDUITPANEL DESIGNATIONGROUND CONDUCTOR(S)PHASE CONDUCTOR(S)NEUTRAL CONDUCTOR(S)ALL CONDUCTORS NOT LESSTHAN #12ALL CONDUIT NOT LESS THAN 3/4"CIRCUIT NO. DESIGNATIONAL11,3,5}FIRE/SMOKE RATED OR UNRATED PARTITIONOF VARIOUS CONSTRUCTIONS-REFER TOARCHITECTURAL PLANS OR FIELD VERIFY TYPECEILING STRUCTURESIZE CONDUIT SLEEVE (SIZE AS INDICATED)WITH INSULATED THROAT CONDUIT TERMINATORSEACH END-PROVIDE A THREADED CAP ONEACH END IF NOT USED FOR WIRING. LINE-UPWITH "BRIDLE RINGS" WHERE APPLICABLE.AFTER CABLE INSTALLATION, PROVIDEFIRESTOPPING IN SLEEVE.ACCESSIBLE CEILING EACH SIDE OF SLEEVEJBRANCH CIRCUIT CONDUITDOWN TO OUTLETWALL OUTLETLAY-IN TYPE CEILINGBRANCHCIRCUIT CONDUITJUNCTION BOXPANEL LXW120/208V/3PH/4WFEED: 150 AMPSFED FROM: MDP-3AABB19030Project:Developer:Sheet Number:Engineer:By:Sheet Title:CDG Number:Last Revision Date:Set Issue DateDrawn ByChecked BySheet Issue DateWREN BUILDINGCarmel, IN 46032CONSTRUCTION DOCUMENTS750 Veterans WayNOT FOR CONSTRUCTIONE-602ELECTRICAL DETAILS11/24/2111/24/2111/24/2111/24/21 BUILDING SHELLBID PHASE III