HomeMy WebLinkAboutH-100 - HVAC FOUNDATION PLANSnow MeltDesign:140.0 Btu/(hr·ft²)
Backloss:28.0 Btu/(hr·ft²)Total:168.0 Btu/(hr·ft²)
Circuit A-9204 ft @ 9 inFlow: 2.09 USGPMΔT: 25 °F
Circuit A-1196 ft @ 9 in
Flow: 1.98 USGPMΔT: 25 °F
Circuit A-15193 ft @ 9 inFlow: 2.00 USGPMΔT: 25 °F
Circuit A-3196 ft @ 9 inFlow: 2.02 USGPMΔT: 25 °F
Circuit A-4203 ft @ 9 inFlow: 2.02 USGPMΔT: 25 °FCircuit A-5193 ft @ 9 inFlow: 1.90 USGPMΔT: 25 °FCircuit A-6194 ft @ 9 inFlow: 1.97 USGPMΔT: 25 °F
Circuit A-7206 ft @ 9 inFlow: 2.08 USGPMΔT: 25 °F
Circuit A-8220 ft @ 9 inFlow: 2.15 USGPMΔT: 25 °F
Circuit A-14204 ft @ 9 inFlow: 1.94 USGPMΔT: 25 °F
Circuit A-10204 ft @ 9 inFlow: 1.99 USGPMΔT: 25 °F
Circuit A-11209 ft @ 9 in
Flow: 1.98 USGPMΔT: 25 °F
Circuit A-12206 ft @ 9 inFlow: 1.98 USGPMΔT: 25 °F
Circuit A-13201 ft @ 9 inFlow: 1.85 USGPMΔT: 25 °F
Manifold 1(103.5 °F)
Manifold(103.5 °F)
0'-9"
0'-6"T1 2 3
4 5
6 7
A.1
B
C
D
E
E.9
1.9
F
A
6.1
E.2
4.5
/
FOR ENLARGED PLANS
REFER TO 1 H-304
GEF-1
GEF-2
GEF-1
EUH-6 EUH-8
EUH-7
EUH-9
EUH-4
EUH-5
GEF-3
LV1
60/20 J8800 60/20 60/20 66/424"ø COMBUSTION AIR AND EXHAUST AIR
VENTS ROUTE UP TO FLOOR ABOVE.
TERMINATE WITH MANUFACTURER
APPROVED CONCENTRIC VENT KIT.
6"ø EXHAUST AIR DUCT
ROUTES UP TO FLOOR ABOVE.
CC-1
EUH-10
EUH-10
EUH-10
EUH-10
18166
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateWINDSOR BUILDINGCarmel, IN 46032CONSTRUCTION
DOCUMENTS800 West Monon Green Blvd.H-100
HVAC FOUNDATION
PLAN
0702/20210702/2021
THOMAS KENNEDY JOE BOLYARD
1/8" = 1'-0"
HVAC FOUNDATION PLAN 1
11700201
No.
STATE OFJOSEPHR.BO
L
Y
ARDPROFE
S
SIONA L E N G INEERDATE SIGNED 07/02/21
R E G I STERE
D
I
ND I A N AN
0 16'8' 4'
01/03/22