HomeMy WebLinkAboutPM1GENERAL NOTES:
A. EVERYTHING SHOWN IS NEW UNLESS OTHERWISE NOTED.
B. FOR GENERAL DUCT CONSTRUCTION SEE DETAILS.
C. ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE TRADE, AND SHALL
CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND STANDARDS.
D. THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS REQUIRED TO COMPLETELY AND
PROPERLY INSTALL ALL WORK REQUIRED FOR THE PROJECT, AND SHALL EXAMINE THE SCOPE OF WORK OF
OTHER TRADES PRIOR TO SUBMITTING A BID PROPOSAL.
E. CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, HOWEVER, SYSTEMS HAVE
BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES, ENLARGED FOR CLARITY. ANY OFFSETS,
ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO PROVIDE A COMPLETE AND COORDINATED
SYSTEM SHALL BE BORNE BY THE CONTRACTOR.
F. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED
MATERIALS INCLUDING ALL DIFFUSERS, GRILLES, AND REGISTERS. THE H.C. SHALL COORDINATE
DUCTWORK INSTALLATIONS WITH OTHER TRADES. LIGHTING AND DUCTWORK DESIGNS INDICATED ON
CONTRACT DRAWINGS WERE COORDINATED, HOWEVER CONFLICTS WITH DUCTWORK AND LIGHTS MAY
ARISE DUE TO GRID INSTALLATION. H.C. SHALL BE RESPONSIBLE FOR ALL DUCTWORK MODIFICATIONS AND
OFFSETS REQUIRED TO AVOID FIELD CONDITIONS.
G. BALANCE DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO THE MAIN.
H. FLEXIBLE DUCTWORK IS LIMITED TO A MAXIMUM LENGTH OF 3 FEET, WITH NO DIPS, SAGS, OR TIGHT
ELBOWS; AND ON SUPPLY DUCTWORK ONLY. FLEXIBLE DUCTWORK SHALL BE AN INSULATED, SEMI-RIGID
AND LIGHT WEIGHT AIR DUCT, MANUFACTURED BY USING DEAD SOFT ALUMINUM STRIP WHICH IS
SPIRALLY WOUND AND MECHANICALLY JOINED TOGETHER FORMING AN AIR TIGHT-LEAKPROOF TRIPLE
LOCK SEAM. DUCT TO BE SELF-SUPPORTING AND CORROSIVE RESISTANT UL-181 CLASS I PRODUCT, WITH A
POLYETHYLENE VAPOR BARRIER. FLEXIBLE DUCTWORK TO BE LIKE MASTERFIT UPC-018 (ACOUSTICAL) OR
AN APPROVED EQUAL.
I. LABEL ALL THERMOSTAT, SENSOR, ETC. AS TO WHAT THE DEVICE CONTROLS WITH AN ENLARGED, PLASTIC
LABEL; MOUNTED UNDER OR ON THE DEVICE.
J. PROVIDE NECK PLENUMS ON RETURN AND EXHAUST GRILLES AS REQUIRED. SEE DETAILS.
K. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS. SEE DETAILS.
L. ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO DUCTWORK, PIPING, UNIT HEATERS, ETC. SHALL BE
HUNG FROM THE TOP CHORD OF THE STRUCTURAL STEEL.
M. ALL EXTERIOR PENETRATIONS SHALL BE WEATHER AND WATER TIGHT.
N. PROVIDE DUCT CLEANOUTS AS REQUIRED.
O. REFRIGERANT PIPE SIZING AND CONFIGURATION BY UNIT MANUFACTURER.
P. HVAC CONTRACTOR SHALL COORDINATE DUCT, DIFFUSERS, REGISTERS AND GRILLES WITH LIGHT FIXTURE
LOCATIONS.
Q. CONTRACTORS ARE TO REVIEW STRUCTURAL PLANS AND ACTUAL LAYOUT OF BEAMS, JOISTS, ETC. TO
AVOID CONFLICT BETWEEN DUCT. ADJUST DUCT ROUTING TO ACCEPT STRUCTURAL CONDITIONS.
R. ALL EXHAUST DISCHARGES AND GAS FLUES WHERE INDICATED SHALL BE LOCATED A MINIMUM OF 10'-0"
AWAY FROM OUTSIDE AND COMBUSTION AIR INTAKES UNLESS LOCAL AND STATE CODES MANDATE
ADDITIONAL DISTANCE.
S. CONTRACTOR SHALL VERIFY ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL EQUIPMENT WITH THE
ELECTRICAL CONTRACTOR PRIOR TO PLACING EQUIPMENT ON ORDER.
T. WHERE WALL TYPE LOUVERS ARE INDICATED, MECHANICAL CONTRACTOR SHALL SEAL WATER-TIGHT ALL
AROUND LOUVER WITH SILICON CAULKING. CONTRACTOR SHALL COORDINATE PAINTING REQUIREMENTS
FOR LOUVERS WITH GENERAL CONTRACTOR PRIOR TO SUBMITTING BID.
E.S.P.
0.70"
EVAPORATOR FAN
NOTES:
RTU-1 1,600
CFM
1.0 1.2 1180
H.P. BHP RPM
TRANE YSC048G3RHBDOD1A
MANUFACTURER/ MODEL NO.
HEATING
105.3
OUTPUT
47.9 39.0 79 65.9
MBH
TOTAL SENS.
COOLING
EDB EWB
12.0 55.8 55.8 130.0
EER LWBLDB INPUT
MBH APPROX.
WEIGHT (lbs)
208/3Ø 26.0
UNIT POWER
VOLTAGE MCA
760
SCHED9
ALL
NOTESTAG
1. Constant volume, single zone unit.
2. Unit mounted disconnect and 120V outlet.
3. Cooling capacity @ 105°F outside air temperature.
4. Pre-fabricated manufacturer built acoustical roof curb with solid bottom
5. Enthalpy based economizer with relief damper.
6. Coil guard, modulating o.a. damper, crank case heater.
7. 7 day 24/7 programmable thermostat, 2-stage cooling.
ROOF TOP UNIT SCHEDULE
SYMMONSMX-1 8210CK POINT OF USE
MIXING VALVE - -WITH SEPARATE STOPS SET 110°F DISCHARGE TEMP
MANUFACTURERMARK
NO.
PLUMBING EQUIPMENT SCHEDULE
ELECTRICAL
V/PHHP NOTESMODELDESCRIPTION
AMTROLET-1 EXPANSION
TANK - - ST-25 PROVIDE WITH SHUT OFF VALVE
PIPING INSULATION SCHEDULE (INDOOR)
NOTES:
FLUID TEMP. RANGE (°F)
SYSTEM
1. RUNOUTS NOT EXCEEDING 12 FEET IN LENGTH AND 2" PIPE TO INDIVIDUAL HVAC TERMINAL UNITS.
2. RUNOUTS THAT ARE NOT LARGER THAN 1" AND NON-CIRCULATING TO INDIVIDUAL PLUMBING UNITS.
3. INCLUDES ROOF DRAIN BODY AND VERTICAL RUN UP TO THE ROOF DRAIN BODY.
4. PROVIDE PVC JACKET ON EXTERIOR REFRIGERANT PIPING.
5. INSTALL 3'X3'X1" ARMAFLEX GLUED TO BOTTOM OF RD AND OFD BODY'S. (EXISTING & NEW
REFRIGERANT
(SEE NOTE 4)
40 & BELOW
DOMESTIC HOT
WATER & RETURN
100-300
DOMESTIC COLD
WATER
40-75
CONDENSATE
DRAIN
40-55
INSULATION TYPE MF OR FE MF OR FE MF OR FE MF OR FE
JACKET TYPE FP FP FP FP
VAPOR BARRIER REQ'D
RUNOUTS (NOTE 1& 2
1" & LESS
1.25" TO 2"
2.5" TO 4"
5" & ABOVE
1.0
1.0
1.5
1.5 1.0
0.5
0.5
0.5
-
0.5
0.5
-
----
0.5
0.5
0.5
----INSULATIONTHICKNESS (IN)ABBREVIATIONS
INSULATION TYPES
FE FLEXIBLE ELASTOMERIC
CG CELLULAR GLASS
MF MINERAL FIBER (FIBERGLASS)
PO POLYOLEFIN
CS CALCIUM SILICATE
CCF CLOSED-CELL FOAM
FP FOIL & KRAFT PAPER
PVC CELLULAR GLASS
AL ALUMINUM
SS STAINLESS STEEL
NOTES
ELECTRICAL
MANUFACTURER/MODEL NOTESTAG
ELECTRIC WATER HEATER SCHEDULE
1. PROVIDE WITH T&P VALVE, PIPE TO NEAREST DRAIN.
2. PROVIDE 2" TALL DRIP PAN.
3. PROVIDE HEAT TRAP IF NOT BUILT INTO TANK CONNECTIONS.
4. PROVIDE 10 YEAR RESIDENTIAL WARRANTY.
POWER
RECOVERY
GPH 90° RISE
WH-1 STATE PCE30-20LSA
DESCRIPTION
ELECTRIC WATER HEATER
WATTS
208/1Ø 2500 11
1ST HOUR
30
GALLON
CAPACITY
30 ALL
NOTES MANUFACTURER/ MODEL NO. VOLTAGE
NOTES:
EF-1
TAG CFM E.S.P.RPM SONES WATTS SPEED CONTROLLED BY: BHP
EXHAUST FAN SCHEDULE
FAN DATA
TIP
ELECTRICAL DATA
LOCATION
Unit mounted disconnect, backdraft damper, variable speed controller, deluxe metal, and 6" wall cap.
All ductwork to be hard sheetmetal (no flex).
Connect ductwork to fan with flexible connection.
1.
2.
3.
ALL 120V/1Ø 80 - PANASONIC FV-0511VKS2 RESTROOM -LIGHT SWITCH
PLUMBING FIXTURE SCHEDULE
MARK
P-2
FIXTURE MANUFACTURER MODEL No. TYPE MATERIAL STYLE COLOR FAUCET / VALVE
MANUFACTURER MODEL SPOUT HANDLES CENTERS SUPPLY STOPS DRAIN
TYPE/MFR/MODEL TRAP SIZE
DOMESTIC
CW
DOMESTIC
HW
SANITARY
WASTE
SANITARY
VENT REMARKS NOTES
NOTE:
LAVATORY V.C.
KOHLER
KOHLER
WATER
CLOSET ADA
K-2005 21x14 WALL HUNG WHITE
110-GNZ-
AE35- 317A8 BRASS CRAFT
CS400AC 1-1/2 WITH/ MX-1 VALVE, WITH LAMINAR FLOW SPRAY HEAD 1,3
2" 3" --- --- --- ---ELONGATED K3578 TANK --- ------1/2"
2" 1-1/2"
KOHLER K-4670-C-O ELONGATED SEAT
1. INSTALL ADA PLUMBING FIXTURES PER ANSI 117.1 GUIDELINES.
2. PROVIDE WITH PROSET SYSTEMS "TRAP GUARD". COORDINATE WITH PROSET SYSTEMS FOR PART NUMBERS AND INSTALLATION. TEL. #1-800-262-5355.
3. TRAPS, SUPPLIES, ETC TO BE CHROME.
4. PROVIDE ADA OFFSET GRID STRAINER AND PADDED SUPPLIES AND DRAIN.
5. VERIFY LOCATION OF FLOOR DRAIN AND SIZE REQUIRED.
6. SANITARY WASTE LINE SIZE AS INDICATED ON PLANS.
7. PROVIDE 0.5 AERATOR ON FAUCET.
8. PROVIDE WITH 16 GAUGE STAINLESS STEEL SHROUD, BUILT TO ENCLOSE REAR OPENING OF P-1 WATER CLOSET, INSTALL 2x4 BACKING, FASTEN TO WALL WITH 6-#8
S.S. VANDAL PROOF SCREWS, COVER TO ENCOMPASS TOP AND SIDE OF W.C.
9. PIPE OFD INTO RD RISER PER INDIANA PLUMBING CODE.
P-1 1,3V.C.WHITE --- ---
3/8" 3/8" CAST GRID
ZURN Z8743------ --- CHICAGO
-- - -
THE PLANS, IDEAS & DESIGNS REPRESENTED
HERE ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF APRIL MCCLURG DESIGN CO.
ALL RIGHTS RESERVED, EXCEPT WHEN WRITTEN
CONSENT IS GIVEN.
CONTRACTORS ARE TO VERIFY AND ARE
RESPONSIBLE FOR ALL JOB SITE DIMENSIONS.UNIT 130- DIVIDEWEST CARMEL 'B' SHOPPES9873 NORTH MICHIGAN ROADCARMEL, INDIANA 46032Mechanical, Electrical, &
Energy Engineering
2707 Rand Road Indianapolis, In 46241
voice: 317-464-9090 fax: 317-464-9393
www.daengineering.com
DESIGN-AIRE ENGINEERING, INCSOUTH BUILDINGISSUE: SUBMITTAL SET
DATE: 11/18/2021
PM-1
PLUMBING AND
HVAC SCHEDULES
01/03/22