HomeMy WebLinkAboutE2FAN/LIGHT SWITCH SCHEMATIC
NO SCALE
JUNCTION BOX
BUILDING STRUCTURE
CEILING
LP2-5 BPA-15
LABEL CKT. NO. OF EACH DEVICE ON
REAR SIDE OF COVER PLATE. USE
PERMANANT MARKER PEN, BRADY
MARKING SYSTEM OR OTHER METHOD
APPROVED BY THE ENGINEER
JUNCTION BOXES (EXPOSED OR
CONCEALED ABOVE ACCESSIBLE
CEILING)
LABEL COVERS WITH CKT.'S
CONTAINED WITHIN. USE
PERMANANT MARKER PEN OR
OTHER APPROVED METHOD.
FOR J.B.'S CONTAINING OTHER
THAN POWER OR LIGHTING
CKT.'S LABEL COVERS
INDICATING SYSTEM TYPE AND
ZONES.
LABEL EXAMPLES:
"FIRE ALARM-ZONES 2&3"
"P.A. ZONES 4,5,&6"
"DATA CIRCUITS A&B"
"EXIT SIGNS-EMI&2"
"EMERG. CKTS. BPEM-3,4"
CKT.S LP4-13,15,17
REAR SIDE
OF PLATE
FRONT
DUPLEX
RECEPTACLE PLATE
STANDARD TOGGLE
SWITCH PLATE
FRONT
REAR SIDE OF PLATE
ELECTRICAL IDENTIFICATION DETAIL
NO SCALE
NOT TO SCALE
PULL
STATION
SWITCH
NOTE: ALL DIMENSIONS ARE
TYPICAL FOR GIVEN DEVICE
UNLESS OTHERWISE NOTED ON
PLANS.
RECEPTACLEVOICE/DATA
OUTLET
FINISHED FLOOR
HORN/STROBE
48"
18" 18"
48"
80"
NOT TO SCALE
STAINLESS STEEL CLAMPS BY E.C.
CONDUIT BY E.C.
SPUN ALUMINUM FLASHING
BASE BY E.C.
BUILT-UP
ROOF DECK
CONDUIT BY E.C.
ROOFING
STEPPED PVC
BOOT BY E.C.
TYPICAL ROOF PENETRATION
NO SCALE
HANGER OR EQUAL
B-LINE #B3373 CONDUIT
TYPICAL DETAIL FOR OVERHEAD FEED TO INTERIOR
WALL OUTLET
OPERABLE DEVICE MOUNTING HEIGHT DETAIL
M
LBLK WHT
WHT
BLU BLKREDWHTGRDBLU
WHT
RED
BLK
BLKWHTGRDWHT
FAN/LIGHT
CONTROL
FAN/LIGHT
VARIES FLOOR
4" BOX WITH BLANK COVER
STRING TO ABOVE CEILING
3/4" ENT WITH PULL
CEILING
SINGLE GANG PLASTER RING
TYPICAL T.V. OUTLET ROUGH-IN DETAIL
AIR KING #AKDT60
NOT TO SCALE
LAY-IN FIXTURES SUPPORT DETAIL
ANGLE IRON UNISTRUT BY
E.C. AS REQIRED SECURELY
SUPPORTED FROM
STRUCTURE ABOVE
CADDY CLIPS OR EQUAL BY
E.C.
OUTLET BOX & SUPPORT
ROD BY E.C.
CEILING T-BAR
CEILING
FLEXIBLE CONDUIT BY E.C.
DOUBLE LOOP SAFETY
CHAIN BY E.C. MIN. 2 PER
FIXTURE
NOTE :
LIGHTING FIXTURES MUST BE SUPPORTED
INDEPENDENTLY OF CEILING SYSTEM.
UPON WRITTEN REQUEST TO THE
ENGINEER, OTHER MEANS OF SUPPORT
WILL BE CONSIDERED FOR APPROVAL.
FIXTURE
SCHEDULE OF CONDUIT APPLICATIONS
CONDUIT LOCATION OR
APPLICATION
IN CONCRETE SLAB
(NOT LARGER THAN 1"C)RIGIDCONDUIT TYPE
NOTE:
- TYPE OF CONDUIT TO BE USED.
- E.M.T. SHALL NOT BE USED IN SIZES LARGER THAN 2 INCH.
- CONVERT TO RIGID OR INTER. THROUGH SLAB.
- USE THREADED FITTINGS ONLY.
3
BELOW LOWEST FLOOR SLAB
CONCEALED IN WALLS, ABOVE
CEILINGS AND IN FURRED SPACES
INSIDE, ABOVE BOTTOM OF
ROOF STEEL
FEEDER, POWER AND SIGNAL
CIRCUITS RUN EXPOSED
FINAL CONNECTION TO EQUIP.
SUBJECT TO VIBRATION
FINAL CONNECTION TO EQUIP.
IN DAMP LOCATIONS
SHORT CONNECTIONS WHERE
NON-FLEXIBLE CONDUIT IS
IMPRACTICAL
3
3
3 1
2INTERMEDIATE3E.M.T.FLEXIBLEFLEXIBLE W/ W.P.JACKETP.V.C. SCHED 40A.C. CABLE1
2
3
NO SCALE
5/16"x3"x3" STEELANGLE SEHPRED TOCONDUIT HANGERAND ROOF STARTERTYPICAL FOR TWO
SERVICE ENTRANCE
THHN-THWN
EXPOSED FEEDERS
CONCEALED FEEDERS
FEEDERS BELOW
CONCRETE
FEEDERS UNDERGROUND
FEEDERS BELOW
RAISED FLOORING
FEEDERS IN CABLE TRAY
EXPOSED BRANCH CIRCUITS
CONCEALED BRANCH CIRCUITS
BRANCH CIRCUITS BELOW CONCRETE
BRANCH CIRCUITS UNDERGROUND
BRANCH CIRCUITS BELOW
RAISED FLOORING
BRANCH CIRCUITS IN
CABLE TRAY
CLASS 1 CONTROL CIRCUITS
CLASS 2 CONTROL CIRCUITS
XHHW MI NM MC UF AC
CONDUCTOR INSULATION AND
MULTICONDUCTOR SCHEDULE TABLE
SIZE (AWG OR KCMIL)
MINIMUM SIZE
EQUIPMENT
GROUNDING
CONDUCTORS FOR
GROUNDING
RACEWAY AND
EQUIPMENT
AUTOMATIC OVER
CURRENT SETTING
(AMPS - NOT
EXCEEDING)
COOPER
ALUMINUM
OR COPPER
CLAD
ALUMINUM
15 14 12
20 12 10
60 10 8
100 8 6
200 6 4
300 4 2
400 3 1
500 2 1/0
600 1 2/0
800 1/0 3/0
1000 2/0 4/0
1200 3/0 250
1600 4/0 350
2000 250 400
2500 350 400
3000 400 600
4000 500 600
5000 700 750
6000 800 1200
SIZE AWG
OR KCMIL COOPER
12 25 20
10 35 30
8 50 40
6 65 50
4 85 65
3 100 75
2 115 90
1 130 100
1/0 150 120
2/0 175 135
3/0 200 155
4/0 230 180
250 255 205
300 285 230
350 310 250
400 335 270
500
420
310
600
460
340
700
475
375
CONDUCTOR
SIZING FOR RHW,
THHW, THW,
THWN, XHHW, USE,
ZW AT 167°F
ALUMINUM
750
800
900
1000
1250
1500
2000
1750
490
520
545
590
625
650
665
380
385
395
425
445
485
520
545
560
THE PLANS, IDEAS & DESIGNS REPRESENTED
HERE ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF APRIL MCCLURG DESIGN CO.
ALL RIGHTS RESERVED, EXCEPT WHEN WRITTEN
CONSENT IS GIVEN.
CONTRACTORS ARE TO VERIFY AND ARE
RESPONSIBLE FOR ALL JOB SITE DIMENSIONS.UNIT 130- DIVIDEWEST CARMEL 'B' SHOPPES9873 NORTH MICHIGAN ROADCARMEL, INDIANA 46032Mechanical, Electrical, &
Energy Engineering
2707 Rand Road Indianapolis, In 46241
voice: 317-464-9090 fax: 317-464-9393
www.daengineering.com
DESIGN-AIRE ENGINEERING, INCSOUTH BUILDINGISSUE: SUBMITTAL SET
DATE: 11/18/2021
E-2
ELECTRICAL
DETAILS
01/03/22