HomeMy WebLinkAboutE113 OVERALL THIRD FLOOR ELECTRICAL PLAN1.All installations shall meet the requirements of the 2014 Indiana Mechanical Code and conform to all federal, state, and
local laws, ordinances, codes, and governing jurisdictions.
2.All shafts shown in BIM coordination model are to remain 3-sided until after completion of mechanical installation, at
which time they can be closed by finishing the 4th side.
3.Air filters will be in installed in the air handling units during construction. If units are utilized and operated for temporary
heating or cooling during construction, it is the builder's responsibility to turn units off during sanding and painting
operations. If units are not turned off during these operations, the coils will require cleaning prior to final turnover.
4.Balancing of air systems will be performed by the Mechanical contractor.
5.The mechanical contractor shall furnish and install complete and operable control systems, consisting of individual room
thermostats and central control system, as recommended by the equipment manufacturer.
6.All electrical power wiring, equipment disconnects, and final connections are to be coordinated with electrician. All
disconnect switches serving mechanical equipment shall be installed as required by NEC and proper service clearances
shall be maintained.
7.All low voltage control wiring for the proposed system will be performed by mechanical contractor.
8.Mechanical contractor shall layout ductwork and refrigerant piping to accommodate code compliance and
constructability of the project.
9.These drawings are intended to document the general requirements of / for the mechanicals systems. They may not be
complete in every respect. The M.C. is required to provide all necessary labor, equipment, materials, and accessories, etc.
for a complete and operational installation, whether or not indicated on these documents.
10.Submittals for all equipment, materials, or products must be provided by M.C. and approved prior to installation.
11.Flexible ducts shall be routed and supported in a fashion to avoid pinching or crushing of the pipe.
12.All non-insulated flexible duct connections to hard duct and diffusers shall be secured using flat, braided bonding
straps at the flexible inner liner of the duct.
13.Insulated flexible duct connections to hard duct and diffusers shall be secured using flat braided bonding straps at the
flexible inner liner of the duct. Once secure, the insulation and outer vapor barrier shall be pulled over the inner liner
connection and then strapped to the hard duct. Care shall be taken to verify that no hard duct is exposed at the connection.
14.Contractor shall coordinate the location of piping, ductwork, sprinkler lines, electrical routing, equipment and all floor,
roof and wall openings prior to installation. Any conflicts on site should be brought to the attention of the on site Project
Engineer.
15.Equipment and manufacturers scheduled and / or specified are intended to show a minimum standard of quality, and
are based on the owner's preference. Other non-specified / non-scheduled manufacturers will not be considered. If the
contractor submits equipment other than by the manufacturer shown on the drawings and in the specifications, it may be
rejected, or subject to review by the architect, engineer, or owner.
16.Any changes or modifications made to this project that deviate from the plans as shown, other than changes made in
coordination with other trades or as a result of unforeseen structural obstructions, must be approved in writing by the
Mechanical Engineer.
17.Contractor to coordinate the installation of all piping, duct and associated items with items requiring structural support
above the ceiling (i.e. projectors, movable partitions, can lights etc.) Any conflicts on site should be escalated to the on site
Project Engineer to be coordinated.
18.Route condensate piping to nearest discharge point, by gravity. The use of pumps to eliminate condensate should be
avoided wherever possible.
19.Insulate all condensate drain piping, inside the building that is located in a place where conditions may exist to cause
condensation.
20.Not all valves and accessories necessary to make this a complete and functioning project may be shown on the plans.
It is incumbent on all subcontractors to provide all elements and components necessary to make this a complete and fully
functional project.
21.Follow all manufacturers' recommendations with regards to outdoor equipment spacing and clearance for proper air
flow and serviceability.
22.Outside air intakes shall be located a minimum of 10' away from any exhaust duct, blower discharge, plumbing vent, or
source of noxious or hazardous fumes.
23.Provide tagging system that identifies equipment and area served.
24.Provide fire dampers, radiation dampers, or smoke dampers as required by code and as noted.
25.Fire stop pipe penetrations of rated walls or structure as required by local code.
26.Paint interior surfaces visible through return air grills. Use flat black paint.
27.Thermostats or sensor controls are to be 48” AFF Max. and located to comply with ADA accessibility requirements.
28.Equipment and installation techniques and methods to be International Energy Code compliant to include the following
ASHRAE 90.1, 62.1 requirements.
a. HVAC equipment must be compliant with Tables 6.8.1A, and 6.8.1B.
b. Refrigerant lines must be insulated with minimum 1/2” thick cellular foam insulation.
c. Insulation exposed to weather must be suitable for outdoor service (e.g. protected by aluminum, sheet metal, painted
canvas, or plastic cover) and must be water retardant and provide shielding from solar radiation.
d. All HVAC systems with field installed ductwork must be air balanced in accordance with industry accepted
procedures.
e. Any exhaust fan that does not have continuous service must be equipped with motorized or gravity damper that will
automatically close when fan is not running.
f. Transverse joints on all ductwork must be sealed with a UL181 approved mastic or sealing system.
g. Ductwork and plenums must be insulated in accordance with Tables 6.8.2A & 6.8.2B.
32. Fire dampers to be constructed of heavy gauge galvanized steel frames, 301 stainless steel closure springs (for
horizontal mount only), 165°F fusible link, and galvanized steel sleeve that is two gauges thicker than service ductwork.
Fire dampers to be UL listed and labeled and must be manufactured in conformance with NFPA standards.
GENERAL NOTES RI
G EEIS
PE60860351
No.REENIGNELANOISSEFORPDOUGLAS.RMOO
RET R
NNDIA A
STATE OF DEMOORE ENGINEERING
SERVICES, INC.
6340 LaPas Trail
Indianapolis, IN 46268
Phone (317) 291-1052
FAX (317) 298-2729
UP
UP
GREAT ROOM
KITCHEN
DINING
FOYER
CLO.
STOR.BEDROOM 2
BATH 2
CLOSET
HVAC
GREAT ROOM
KITCHEN
DINING
FOYER
CLO.
STOR. BEDROOM 2
CLOSET
HVAC
FIREPLACEFIREPLACEST1-3
ELEVATOR
LOBBY
ELEVATOR
TENANT TENANT
LAUNDRY LAUNDRY
CLOSET CLOSET
POCKET
OFFICE
POCKET
OFFICE
CLOSET CLOSET
POWDER
BATH
POWDER
BATH
BATHROOM
PANTRY PANTRY
OWNER'S
BATH OWNER'S RETREAT
OWNER'S
BATHOWNER'S RETREAT
UTILITY UTILITY
1/4"/12" 1/4"/12"1/4"/12"1/4"/12" 1/4"/12"1/4"/12"1/4"/12" 1/4"/12" EDP
GFI
GFI
GFI 444
GFI
F
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI WP
DISPOSAL/DW
SEE NOTE #11
A
A
A
A
A
A
K
B
B
C
C C
C
D
D
E
J
H
H
H
H
G G
G G
G
G
G
G
G G
V
G G
G G
D
L
L
L
L
S
G
G
G
G
F
F
F
WP
GFI FOR
FAN CKTS
AV
CAT5
G
U
U
U
D 66" AFFGFI
WP 66" AFFEDP
GFI
GFI
GFI
444
GFI
F
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
DISPOSAL/DW
SEE NOTE #11
A
A
A
A
A
A
K
B
B
C
C C
C
D
D
E
J
H
H
H
H
GG
GG
G
G
G
G
GG
V
GG
GG
D
G
G
G
G
F
F
F
GFI FOR
FAN CKTS
AV
CAT5
G
U
U
U
D
GFI GFI
66" AFF 66" AFF
66" AFF66" AFF 66" AFF
66" AFF66" AFF66" AFFGFI WP GFI
WP
66" AFF66" AFFGFI
WP
GFIWP
CEILING MOUNT
PATIO SCREEN
RECP GFI
WP
GFIWP
CEILING MOUNT
PATIO SCREEN
RECP
F F ELECTRICAL FIXTURE SCHEDULE
TYPE MFGR & MODEL NUMBER LAMP TYPE MOUNTING DESCRIPTION & USE
A SEAGULL, 14520S-15 LED CEILING UNIT CLOSET, BATH,
LAUNDRY, FOYER
B SEAGULL, 61160EN3-839 LED PENDANT UNIT KITCHEN BAR
C SEAGULL, 41162-839 LED WALL BATHROOM VANITY
D BROAN 744 VERIFY WITH M.C. LED RECESSED SHOWER LIGHT/VENT
E CEILING FAN ROYAL STAR 1052BN-ES LED CEILING BEDROOM CEIL FAN
F SEE MECHANICAL SHEETS N/A WALL/CEIL EXHAUST FAN
G SEAGULL, 14520S-15 LED RECESSED GREAT ROOM, BEDROOMS,
KITCHEN, CORRIDORS
H SEAGULL, 14520S-15 LED RECESSED OUTDOOR PATIOS AND
LIVING
I RP LIGHTING BOSQUE 1018W FAN LED CEILING OUTDOOR FAN/LIGHT
J ARLINGTON, CP3540 N/A CEILING UNIT CEILING FAN
ROUGH-IN
K SEAGULL, 31160EN3-839 LED CHANDELIER UNIT DINING ROOM
L SEAGULL, 14520S-15 LED CEILING COMMON AREAS
M LITHONIA LED STRIPLIGHT MNSL L46 1LL
MVOLT GZN 40K 80RI M6 LED CEILING SPRINKLER ROOM
N CERAMIC KEYLESS SOCKET W/ LED BULBS
ALLIED MOULDED LH11P LED CEILING GARAGES
R LSI SDL4 LED 40L FL UNV DIM1 40 80CRI LED WALL/CEIL ELEVATOR PIT
S RAB, SLIMFC37N LED WALL EXTERIOR WALL PACK
T COORDINATE WITH OWNER LED WALL COMMON AREA SCONCE
U COORDINATE WITH OWNER LED CABINET UNDER CABINET LIGHTS
V COORDINATE WITH OWNER LED CEILING BEDROOM SURFACE
MOUNT LIGHT
RM BEST, RHLED-2-WP-9.6 LED WALL REMOTE EGRESS
EXIT/ EM BEST, CLPU-2-R-W-RC LED WALL/CEIL EXIT SIGN w/ EM. LIGHT
EXIT BEST, EZRXTEU-2-R-W-EM LED WALL/CEIL EXIT SIGN
EM BEST, LEDR-1 LED WALL EMERGENCY LIGHT ARCHITECTCLIENT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20022
February 26, 2021
# DESCRIPTION DATEMAGNOLIACONDOMINIUMSCARMEL, INCONSTRUCTION SET GC/CM
2 Revised Per Owner Comments 2021-02-26OVERALL THIRD FLOORELECTRICAL PLANE113
SCALE:
OVERALL THIRD FLOOR ELECTRICAL PLAN
E113
1
1/4" = 1' - 0"
2 2
2
2
2
2
2
2
2
2 2
Powered by TCPDF (www.tcpdf.org)
10/25/21