HomeMy WebLinkAboutVWC CONV STORE23 P1.2 10-14-2021DOMESTIC WATER DISTRIBUTION GENERAL REQUIREMENTS:
PIPING SHALL BE SIZED TO PROVIDE A VELOCITY NOT EXCEEDING SIX FEET PER
SECOND (FPS) FOR COLD AND HOT WATER SYSTEMS.
PIPES:
UNDERGROUND: ‘K” COPPER: BRAISED JOINTS; SLEEVES THRU
CONCRETE. INSULATED IN GRAVEL BACKFILL.
ABOVE SLAB: ‘L’ COPPER TUBING; CPVC PIPING, SCHEDULE 40 WITH
SOLVENT WELDED JOINTS; PEX TUBING WITH BRASS FITTINGS.
VENTING AND DRAINAGE: SCHEDULE 40 PVC WITH SOLVENT WELDED
JOINTS.
INSULATION:
INTERIOR COLD WATER PIPING SHALL BE INSULATED TO PREVENT
CONDENSATION. INTERIOR HOT WATER PIPING SHALL BE INSULATED AS
REQUIRED BY CODE AND PER LATEST ASHRE STANDARD A90.1, TABLE
7.2.3.
WALL HYDRANTS:
PROVIDE FREEZE-PROOF WALL HYDRANTS ON EXTERIOR WALLS A
MAXIMUM OF 150 FEET APART. LOCATE APPROXIMATELY 18” ABOVE
FINISH GRADE. COORDINATE LOCATIONS WITH THE BUILDING OWNER
AND THE PROJECT ARCHITECT.
VALVES:
PROVIDE ACCESSIBLE CHECK VALVES IN THE INDIVIDUAL COLD AND HOT
WATER FIXTURE SUPPLY LINES SERVING MIXING VALVE TYPE FAUCETS
OR ASSEMBILES HAVING HOSE CONNECTION OUTLETS THAT ARE NOT
EQUIPPED WITH INTEGRAL CHECK STOPS.
PROVIDE LINE SHUT-OFF VALVES AT LOCATIONS REQUIRED FOR PROPER
OPERATION, SERVICING AND TROUBLESHOOTING OF THE DOMESTIC
WATER DISTRIBUTION SYSTEM AND CONNECTED COMPONENTS.
LOCATIONS SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: AT
EACH FIXTURE AND PIECE OF EQUIPMENT; AT EACH BRANCH TAKE-OFF
FROM MAINS; AT THE BASE OF EACH RISER; AT EACH BATTERY OF
FIXTURES; WHERE RECOMMENDED BY EQUIPMENT MANUFACTURERS
AND AT STRATEGIC LOCATIONS TO ALLOW FOR SECTIONAL ISOLATION
WHILE LIMITING DISRUPTION OF SERVICES.
ALL VALVES SHALL BE ACCESSIBLE FOR OPERATION AND SERVICING.
TRAP PRIMING DEVICES THAT RELY UPON LINE PRESSURE DIFFERENTIAL
FOR ACTIVATION ARE NOT ALLOWED.
DOMESTIC HOT WATER SYSTEMS
WATER HEATERS INSTALLED AND UTILIZED FOR FOOD WERVICE AREAS
SHALL COMPLY WITH NATIONAL SANITATION FOUNDATION (NSF)
STANDARD NUMBER 5. HOT WATER SERVING COMMERCIAL
DISHWASHERS AND POT SINKS SHALL BE 140 DEGREES F. ALL OTHER
HOT WATER SHALL BE 110 DEGREES MAXIMUM AT OUTLETS.
CONTAMINATION PROTECTION:
INSTALLATION OF DOMESTIC WATER SYSTEMS SHALL AVOID ALL CROSS
CONNECTIONS AND ELIMINATE THE POSSIBILITY OF WATER
CONTAMINATION. ON EACH WATER SUPPLY SERVING A FIXTURE WHERE
A DISCHARGE LINE PROVIDES AN OPPORTUNITY WHERE CROSS
CONTAMINATION COULD OCCUR, PROVIDE A VACUUM BREAKER OR
BACKFLOW PREVENTER.
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONNOT TO SCALE
PLUMBING ISOMETRIC
EXPAND TO 3"
THRU ROOF
2" TO ROOF
1 1/2" VENT
EXPAND TO 3"
THRU ROOF
2" TO ROOF
2" TO ROOF
GREASE INTERCEPTOR:
INSTALL GREASE INTERCEPTOR STRICTLY ACCORDING TO REQUIREMENTS OF
THE PLUMBING AND DRAINAGE INSTITUTE (PDI) STANDARD PDI-G101.
INSTALL GREASE INTERCEPTOR STRICTLY ACCORDING TO REQUIREMENTS OF
THE CITY OF CARMEL, INDIANA.
CAPACITY:PER CITY REGULATIONS
AT A MINIMUM, THE FOLLOWING FIXTURES MUST BE CONNECTED THROUGH
THIS GREASE INTERCEPTOR (“FOG” TYPE USES – FATS, OILS, GREASE):
POT SINKS
PRE-RINSE SINKS
SOUP KETTLES
SINKS INTO WHICK KETTLES ARE DRAINED
AUTOMATIC HOOD WASHING UNITS
BASIN SINKS
MOP SINK
THREE COMPARTMENT COMMERCIAL SINKS
FIXTURES THAT SHOULD NOT BE CONNECTED TO THE GREASE INTERCEPTOR
UNLESS REQUIRED BY LOCAL AUTHORITIES.
TOILET ROOM FIXTURES
HAND SINKS
FLOOR DRAINS
THE DRAWINGS ARE SCHEMATIC AND DO NOT SHOW ALL REQUIRED PARTS AND
FITTINGS.
IF INTERCEPTOR WILL BE UNDER AN AUTOMOBILE DRIVEWAY. IT SHALL BE THE
SOLE RESPONSIBILITY OF THE INSTALLER TO PROVIDE REQUIRED
INTERCEPTOR STRUCTURAL THICKNESS AND PAVING/CONCRETE COVER.
NOTIFY ARCHITECT IMMEDIATELY IF CONDITIONS ARE NOT AS EXPECTED.
STRICTLY FOLLOW WRITTEN INSTALLATION INSTRUCTIONS AND CITY
INSTRUCTIONS.
CO
N
D
E
N
S
AT
E LI
N
E CONDENSATE LINEXL 100 GREASE INTERCEPTOR
BELOW SLAB
MOP SINK
SS 3 COMP. SINK
HAND
SINK
HAND
SINK
FLOOR SINK
FLOOR SINK
BLDG
CLEANOUT
BACKFLOW
PREVENTER
FD
FD
ADA WC
ADA WC
ADA LAV
ADA LAV
ADA UR P1.2